9 kW 출력용 태양열 스털링엔진 발전시스템의 설계와 성능예측 (Design and Performance Prediction of Power System in a Solar Stirling Engine for 9 kW Output)

  • 배명환;강상율
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2003년도 춘계학술대회
    • /
    • pp.2198-2204
    • /
    • 2003
  • In order to make a match of the insufficient direct solar radiation, in this study, the target output is lowered to 9 kW smaller than 25 kW in former studies. It is also necessary to match the collector/receiver with engine/generator systems to accomplish the power level of a system. The simulation analyses of a dish solar power system with stirling engine are totally carried out to predict the system performance with the designed values. In addition, an influence of direct solar radiation on system performance and operation control is discussed in simulation. It is found that the diameter of concentrator could be made small to 8 m regardless of slope errors with 2.5 and 5.0 mrad radiation, and the operation range of mean pressure control. is wide even if the direct solar radiation is a quit low.

  • PDF

Novel Topology and Control Strategy of HVDC Grid Connection for Open Winding PMSG based Wind Power Generation System

  • Zeng, Hengli;Nian, Heng
    • Journal of international Conference on Electrical Machines and Systems
    • /
    • 제3권2호
    • /
    • pp.215-221
    • /
    • 2014
  • To satisfy the high voltage direct current (HVDC) grid connection demand for wind power generation system, a novel topology and control strategy of HVDC grid connection for open-winding permanent magnet synchronous generator (PMSG) based wind power generation system is proposed, in which two generator-side converter and two isolated DC/DC converters are used to transmit the wind energy captured by open winding PMSG to HVDC grid. By deducing the mathematic model of open winding PMSG, the vector control technique, position sensorless operation, and space vector modulation strategy is applied to implement the stable generation operation of PMSG. Finally, the simulation model based on MATLAB is built to validate the availability of the proposed control strategy.

발전소 직류 제어회로 과도현상 분석 및 보조계전기 선정 적합성 검토 (A Analysis of DC Control Circuit Transient and a Study of Auxiliary Relay Design Compatability in the Power Plant)

  • 선현규;홍영희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.1948_1949
    • /
    • 2009
  • All the power generating station require dc auxiliary power systems to operate those dc components that must be available if a loss of ac power occur. Some examples of such components are auxiliary motors, circuit breakers, relays and solenoids. The dc source may be one common battery for both power and control or two separate batteries; one for power and another for control. Typically, a dc auxiliary power system is designed as an ungrounded system, instead of grounded system, so that a low-resistance ground fault on one of its two polarities will not affect the operation of the system, thus increasing system reliability and continuity of service. A ground detector should provide a high polarity-to-ground resistance so that a single ground fault occurring on the system will not affect the operation of that system. Sensitive relays have been known to energize momentarily while the cable and capacitive charge to ground shifts[1]. A power station had experienced this kind of incident and performed root cause analysis based on PC based simulation program known as PSpice. This simulation showed adapted relays on the system energize momentarily and design criteria on this relay should be corrected.

  • PDF

수용가 전력관리시스템 개발 연구 (A Study on the Development of Industrial Power Management System)

  • 문영환;성기철;윤상현;김언충
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1995년도 하계학술대회 논문집 B
    • /
    • pp.550-552
    • /
    • 1995
  • Real time informations from industrial power system in operation can be used for efficient energy conservation, optimal operation of electrical equipments, and expansion planning of apparatus. Requirements for energy conservation and supplied power quality in customers are increasing significantly because of their effects on the production cost and efficiency. Thus, the development of low cost power management system which can can operate in domestic power system properly is substantially requested. In this research, operation software for real time monitoring and control system in customer power system has been developed to achieve the above purposes. The development of the operating software and related technologies are expected to be applied successfully for reducing electricity cost, enhancing power quality, determining facility expansion planning, operating optimal power system, increasing production efficiency, and reducing maintenance cost.

  • PDF

A Control Method for Power-Assist Devices using a BLDC Motor for Manual Wheelchairs

  • Kim, Dong-Youn;Kim, Yong-Hyu;Kim, Kwang-Sik;Kim, Jang-Mok
    • Journal of Power Electronics
    • /
    • 제16권2호
    • /
    • pp.798-804
    • /
    • 2016
  • This paper proposes a new operation and control strategy for Power-Assisted Wheelchairs (PAW) using one brushless DC (BLDC) motor. The conventional electrical wheelchairs are too heavy and large for one person to move because they have two electric motor wheels. On the other hand, the proposed PAW system has a small volume and is easy to move due to the presence of a single wheel motor. Unlike the conventional electric wheelchairs, this structure for a PAW does not have a control joystick to reduce its weight and volume. To control the wheelchair without a joystick, a special control system and algorithm are needed for proper operation of the wheelchair. In the proposed PAW system uses only one sensor to detect the acceleration and direction of PAW's movement. By using this sensor, speed control can be achieved. With a speed control system, there are three kinds of operations that can be done on the speed of a PAW: the increment of PAW speed by summing external force, the decrement of PAW speed by subtracting external force, and emergency breaking by evaluating the time duration of external force. The validity of the proposed algorithm is verified through experimental results.

등호제약조건을 이용한 계통 해석 및 고장판단 계산 구현 (Calculation of Network Analysis and Fault Decision using Equality Constraint Condition with MATLAB)

  • 양민욱;김건중;황인준
    • 전기학회논문지
    • /
    • 제58권11호
    • /
    • pp.2101-2106
    • /
    • 2009
  • The power system state estimation and prediction are very important for operation. Because that accidents of the Power system are the cause that many devices and etc are damaged. Currently, almost every power systems have 2nd,3rd back-upsystem for prevention of accident. But prevention of accident by miss-operation, due to operator or miss data, has not acounter plan. Because, we need to estimate the power system for correcting miss data and preventing miss operation by operator. We suggest algorithm for integrity of power system network data.

광양제철소 전력계통 단독 운전시 발전기 최적제어방안 연구 (The study on the optimal control of generators on the single operation of electric power system in Gwangyang steel works)

  • 곽인철;신민교;최윤종;박부견
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년 학술대회 논문집 정보 및 제어부문
    • /
    • pp.357-359
    • /
    • 2006
  • The electric power system of Kwangyang steel works needs to keep the parallel operation with the system of KOPEC(Korea Electric Power Corporation) for supplying the power with safety. Once it is separated from KOPEC due to an accident, it operates the automatic Mill trip system to prevent huge fluctuating loads from the serious frequency drop. In spite of that, it is recent situations that the continuous growth of electric loads facilitates the frequency drop. Therefore, this paper proposes a model of generator control system so as to quantitatively analyze the response characteristics to the frequency change under the single operation, and also suggests the strategy for minimizing the frequency changes. The simulation results show it is desirable to operate the generators by 3% speed droop and 10% load limiter.

  • PDF

계통연계형 직렬운전 소형풍력발전시스템의 해석 및 운전방안 연구 (The Analysis and Study on Operation Strategy of Grid-connected Series Small Wind Turbine System)

  • 김창하;구현근;손영득;김장목
    • 전력전자학회논문지
    • /
    • 제20권1호
    • /
    • pp.59-64
    • /
    • 2015
  • This paper proposes an analysis and operation strategy of a grid-connected wind turbine system using a diode rectifier. The currents of generators are the same as that of a small wind turbine system. Therefore, the analysis of generator torque is required as opposed to an analysis of blade speed. In this paper, the appropriate MPPT control method is proposed to control generator torque. Usefulness of the proposed operation strategy is verified by simulations and experiments.

Supplementary Control of Conventional Coordinated Control for 1000 MW Ultra-supercritical Thermal Power Plant using Dynamic Matrix Control

  • Lee, Youngjun;Yoo, Euiyeon;Lee, Taehyun;Moon, Un-Chul
    • Journal of Electrical Engineering and Technology
    • /
    • 제13권1호
    • /
    • pp.97-104
    • /
    • 2018
  • This paper proposes supplementary control of conventional coordinated control of a power plant which directly affects network frequency. The supplementary control with dynamic matrix control is applied for 1000 MW power plant with ultra-supercritical (USC) once-through boiler. The supplementary control signal is added to the boiler feedforward signal in the existing coordinated control logic. Therefore, it is a very practical structure that can maintain the existing multi-loop control system. This supplementary controller uses the step response model for the power plant system, and on-line optimization is performed at every sampling step. The simulation results demonstrate the effectiveness of the proposed supplementary control in a wide operating range of a practical 1000 MW USC power plant simulator. These results can contribute the stable operation of power system frequency.

Field Implementation of Voltage Management System (VMS) into Jeju Power System in Korea

  • Shin, Jeonghoon;Nam, Suchul;Song, Jiyoung;Lee, Jaegul;Han, Sangwook;Ko, Baekkyung;An, Yongho;Kim, Taekyun;Lee, Byungjun;Baek, Seungmook
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권3호
    • /
    • pp.719-728
    • /
    • 2015
  • This paper presents the results of field tests on Voltage Management System (VMS) using hybrid voltage control, which utilizes coordinated controls of various reactive power resources such as generators, FACTS and switched shunt devices to regulate the pilot bus voltage in a voltage control area. It also includes the results of performance test on RTDS-based test bed in order to validate the VMS before installing it in Jeju power system. The main purpose of the system is adequately to regulate the reactive power reserve of key generators in a normal condition with coordination of discrete shunt devices such as condensers and reactors so that the reserves can avoid voltage collapse in emergency state in Jeju system. Field tests in the automatic mode of VMS operation are included in steady-states and transient states. Finally, by the successful operation of VMS in Jeju power system, the VMS is proved to effectively control system voltage profiles in steady-state condition, increase system MVAR reserves and improve system reliability for pre- and post-contingency.