• Title/Summary/Keyword: Potential rise

Search Result 651, Processing Time 0.032 seconds

Ground Surface Potential Distribution near Ground Rod Associated with Soil Structures (대지구조에 따른 접지봉 주번의 대지표면전위분포)

  • Lee, Bok-Hee;Jung, Hyun-Uk;Baek, Young-Hwan
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.1
    • /
    • pp.142-147
    • /
    • 2007
  • This paper presents the distributions of ground surface potential rises as functions of soil structure and buried depth of ground rod. To propose fundamental data relevant to the reduction of electric shock of human beings due to ground surface rise, the ground surface potential rises near the ground rod were computed and measured. Ground surface potential rises near ground rod strongly depend on the soil structure, and an increase of the buried depth of ground rod results in a decrease of the ground surface potentials. The maximum ground surface potential appeared at the just above point of ground rod. Also, the measured results were in reasonably agreement with the data computered by grounding analysis program.

Characteristic Analysis elf Large Grounding system by Using Reduced Scale Model Method (축소모델 기법을 이용한 대규모 접지계의 특성분석)

  • 장석훈;이재복;명성호;조연규;김점식
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.3
    • /
    • pp.162-167
    • /
    • 2004
  • The scale model grounding systems to study the behavior of grounding system in uniform soils have been designed and fabricated. Constructional details and instrumentation have been discussed. To verify the accuracy of the results obtained from the experimental tests, they have been compared with computer calculation results. Also, in order to assess the effectiveness of bonding two grounding systems, grounding grid conductors which were downsized as a scale factor of 100:1 were analyzed by using the scale model method. A profile of GPR(Grounding Potential Rise) of each case was measured. The scale model grounding system presented in this paper can be valuable tool to analyze the ground potential profile and ground resistance of practical grounding system.

The Indoor Environmental Quality Improving and Energy Saving Potential of Phase-Change Material Integrated Facades for High-Rise Office Buildings in Shanghai

  • Jin, Qian
    • International Journal of High-Rise Buildings
    • /
    • v.6 no.2
    • /
    • pp.197-205
    • /
    • 2017
  • The conflict between indoor environmental quality and energy consumption has become an unneglectable problem for highrise office buildings, where occupants' productivity is highly affected by their working environment. An effective Façade, therefore, should play the role of an active building skin by adapting to the ever-changing external environment and internal requirements. This paper explores the energy-saving and indoor environment-improving potential of a phase-change material (PCM) integrated Façade. Building performance simulations, combined with parametric study and sensitivity analysis, are adopted in this research. The result quantifies the potential of a PCM-integrated Façade with different configurations and PCM properties, taking as an example a south-oriented typical office room in Shanghai. It is found that a melting temperature of around $22^{\circ}C$ for the PCM layer is optimal. Compared to a conventional Façade, a PCM-integrated Façade effectively reduces total energy use, peak heating/cooling load, and operative temperature fluctuation during the periods of May-July and November-December.

Calculation Method of Transient Potential Rises of Horizontal Ground Electrodes Depending on Injection Point of the Ground Current (접지전류의 입사점에 따른 정보통신설비용 수평접지전극의 과도전위상승 계산 방법)

  • Ahn, Chang-Hwan
    • Journal of the Institute of Electronics and Information Engineers
    • /
    • v.51 no.12
    • /
    • pp.197-203
    • /
    • 2014
  • When the lightning current is injected to the ground system of information and communication facilities, analysis of the transient potential rise in the ground system is one of main factors to effectively design the ground system. The performance of grounding systems is normally estimated with the grounding impedance and the transient potential rise which represents the electrical characteristics of the grounding system. The method for calculating the grounding impedance depending on the injection point of the lightning current was proposed. The delta-gap source model was proposed to calculate the grounding impedance in the case that the lightning current is injected to the center of the horizontal ground electrode. A new program which is possible to apply the frequency-dependent soil parameters using the Debye model was developed, because a commercial program for analyzing the performance of the grounding system can not apply to the frequency-dependent soil parameters. The experiment was carried out to confirm the availability of the simulation results with the same condition. Finally, the transient potential rises of a horizontal ground electrode depending on the lightning current waveforms were analyzed by using the results of the grounding impedance which is associated with the frequency-dependent soil parameters.

An Experimental Study of Fire Risk Characteristic by Extended Balcony of High-Rise Apartments in Fire (고층아파트 화재시 발코니 확장에 따른 화재 위험성에 관한 실험 연구)

  • Kim, Woo-Suk;Kim, Wha-Jung;Lee, Gwang-Won;Lee, Ji-Hee
    • Journal of the Korean Society of Safety
    • /
    • v.27 no.2
    • /
    • pp.65-71
    • /
    • 2012
  • Changes in the styles of communities are leading of increases in the number of high-rise apartments and commercial-apartment structures. Tall high-rise structures, while presenting unique economies of scale and cost effectiveness, tend to be highly engineered and complex structures. In the event of a fire, this complexity in design also results in a complexity in the behavior of fire propagation and control. High-rise structures are among the most potentially dangerous due to the high population density in the building, and the inherent limitations on evacuation and on fire control services. One of the most critical points of fire propagation is the movement of fire through the outer wall structures. Controlling such propagation is essential in controlling the spread of the fire throughout the building itself, as well as controlling the potential for its spread to adjacent buildings. In this study, we will be examining the potential for fire control design and effects mitigation using a 1/4.5 scale model. The primary focus of the study will be the effects of extended balconies into the structure of high-rise apartments. The authors will also consider the effectiveness of reduced-scale model tests.

The Effect of Mutual Coupling between Current and Potential Test Leads on Ground Impedance (전류 및 전위 측정선간 상호유도가 접지임피던스에 미치는 영향)

  • Eom, Ju-Hong;Cho, Sung-Chul;Lee, Tae-Hyung
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.7
    • /
    • pp.1223-1228
    • /
    • 2008
  • While a high frequency source is used for measuring the ground impedance, there are several factors having an effect on the measured value. A primary factor of the measurement error is the ac mutual coupling between current and potential test leads. The mutual coupling causes the test current to induce a voltage into the potential test lead that adds to the actual ground potential rise and produces a significant measurement error as the length of the test leads paralleled is prolonged. In order to avoid the mutual coupling, it is recommended that the ground impedance be measured by angled arrangement of test leads. The mutual impedance due to the inductive coupling with an angle of $90^{\circ}$ was calculated at $0^{\circ}$ by Campbell/Foster Method. With an angle of $180^{\circ}$, the mutual impedance was calculated large value enough to introduce a fairly large margin of error, however, the measured value of ground impedance was close to the value at $90^{\circ}$.

Comparison of DME HCCI Operating Ranges for the Thermal Stratification and Fuel Stratification based on a Multi-zone Modeling (Multi-zone 모델링을 통한 온도성층화와 농도성층화가 존재하는 DME HCCI 엔진의 운전영역에 관한 수치해석연구)

  • Jeong, Dong-Won;Lim, Ock-Taeck
    • Transactions of the Korean Society of Automotive Engineers
    • /
    • v.19 no.2
    • /
    • pp.35-41
    • /
    • 2011
  • This work investigates the potential of in-cylinder thermal stratification and fuel stratification for extending the operating ranges in HCCI engines, and the coupling between thermal stratification and fuel stratification. Computational results areemployed. The computations were conducted using both a custom multi-zone version and the standard single-zone version of the Senkin application of the CHEMKINII kinetics rate code, and kinetic mechanism for di-methyl ether (DME). This study shows that the potential of thermal stratification and fuels stratification for extending the high-load operating limit by a staged combustion event with reduced pressure-rise rates is very large. It was also found that those stratification offers good potential to extend low-load limit by a same mechanism in high-load. However, a combination of thermal stratification and fuel stratification is not more effective than above stratification techniques for extending the operating ranges showing similar results of fuel stratification. Sufficient condition for combustion (enough temperature for) turns misfire in low-load limit to operate engines, which also leads to knock in high-load limit abruptly due to the too high temperature with high. DME shows a potential for maximizing effect of stratification to lower pressure-rise rate due to the characteristics of low-temperature heat release.

An Analysis of the Ground Potential Rises and Dangerous Voltages Associated with the Frequency of Ground Currents (접지전류의 주파수에 따른 대지표면전위 상승 및 위험전압의 분석)

  • Choi, Jong-Hyuk;Cho, Yong-Sung;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.4
    • /
    • pp.97-103
    • /
    • 2011
  • The most important object of grounding systems is to protect human being from electric shock. Touch and step voltages are measured to evaluate the performances of grounding systems. Dangerous voltages have been largely studied by the power frequency fault currents, on the other hand, the ground current containing the high frequency components and surge currents haven't been considered. Many attempts about the grounding impedances reported in these days show that the performance of the grounding systems in high frequency range is very different with the ground resistance. It is necessary to analyze the dangerous voltages formed by the ground currents containing high frequency components. In this paper, the ground surface potential rises near the vertical and horizontal grounding electrodes are measured at the frequency of 100[Hz], 30[kHz], and 100[kHz]. Dangerous voltages are investigated with the frequency-dependent grounding impedance. As a result, the ground surface potential rise is increased as the grounding impedance increases. Touch and step voltages near the grounding electrode whose impedance increases with the frequency are sharply raised.

The Analysis of Structure Grounding Using Reduced Scale Model (축소모델을 이용한 구조체 접지 분석)

  • Gil, Hyoung-Jun;Kim, Hyang-Kon;Han, Woon-Ki;Lee, Ki-Yeon;Choi, Chung-Seog
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2046-2048
    • /
    • 2005
  • This paper deals with ground potential rise of structure grounding electrode when a test current flows through grounding electrode. In order to analyze the potential gradient of ground surface on structure grounding electrode, the reduced scale model has been used. The structures were designed through reducing real buildings and fabricated with four types on a scale of one-one hundred sixty. The supporter was made to put up with weight of structure and could move into vertical, horizontal, rotary direction. When a test current flowed through structure grounding electrodes, ground potential rise was the lowest value at electric cage type(type B). According to resistivity and absorption percentage in concrete attached to structure, the potential distribution of ground surface appeared differently.

  • PDF

Study for the Grounding Resistance of the Mesh Grounding Electrode by Water Tank Model (수조모델을 이용한 메쉬접지극의 접지저항에 관한 연구)

  • Kim, Ju-Chan;Kim, Sung-Sam;Choi, Jong-Gyu;Lee, Chung-Sik;Koh, Hee-Seog
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.3
    • /
    • pp.28-35
    • /
    • 2006
  • Recently, a number of equipments related with electricity, electronics, and communication in the same building are needed to the grounding system for safety from unexpected accidents. When the faulted electric current flows into a certain grounding system, the potential rise in that system takes place and it might induce the potential rise to other grounding system. This potential interference was strongly affected by the surface potential, which was deeply related with the electrode shape. In this paper, the fundamental formula was deduced on the basis of surface potential of two grounding electrodes. Which corresponds to source of the potential interference and other grounding electrode, respectively. Therefore, the degree of potential interference in this mesh grounding electrode system was verified by the simple model simulation. In addition, in order to identify the difference between the grounding resistance in the realistic construction site and the expected value from the corresponding simulation, the experiment was performed with model on a reduced scale about the realistic grounding system. It consists of stainless steel hemisphere electrodes in a water tank. From this work, the grounding resistance in the mesh grounding electrode showed the good coincidence results between those. Consequently, it is confirmed that the grounding resistance in the mesh electrode is possible to be estimated by performing the experiment using the water tank model.