통합형 직류철도 보호계전 방식 (Integrated Protection Method for DC Railway Systems)

  • 강상희;최창영;이원석;정호성
    • 전기학회논문지
    • /
    • 제60권2호
    • /
    • pp.285-292
    • /
    • 2011
  • DC traction power system is operated ungrounded so that minimize the stray current. Because the stray current is still present, a rail potential is increased. The ground faults in the DC railway systems are usually detected by a potential relay(64P). Moreover, if the rail potential goes high in the ordinary operating state because of the traction load, the potential relay would be maloperated. A presented protective relaying algorithm that can identify exactly the faulted region and can distinguish a ground fault from the potential rising of the rail is presented in this paper. This paper presents simulation technique that is very similar to the real operation situation using PSCAD/EMTDC.

DC 급전시스템의 지락보호계전시스템 개발 (Development of Ground Fault Protective Relaying Schemes for DC Traction Power Supply System)

  • 정상기;정락교;조홍식;이안호;권삼영
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제54권9호
    • /
    • pp.427-433
    • /
    • 2005
  • In DC tracking power supply system, ground faults are currently detected by the potential relay, 64P. Though 64P relay detects ground fault, it cannot Identify the faulted region which causes long traffic delays and safety problem to passengers. Two new ground fault protective relay schemes that can identify the faulted region are presented in this paper. One is bus differential protective relay and the other is ground overcurrent protective relay. Both type of relays is similar in principle to the ordinary bus differential protective relay and the ground overcurrent relay used in other power system. In DC traction power supply system, since it is ungrounded, ground fault current is not big enough to operate those relays. To solve the problem, a current control device, called device 'X', is newly introduced in both system, which enables large amount of ground fault current flow upon the positive line to ground fault. Algorithms for these relays are developed and their validity are verified by EMTP simulation.

비접지 DC 급전시스템에서의 Delta-I 지락보호계전 시스템 (Development of Delta-I ground fault Protective Relaying Scheme for DC Traction Power Supply System)

  • 정상기;권삼영;정호성;김주락
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제55권12호
    • /
    • pp.529-535
    • /
    • 2006
  • In DC tracking power supply system, ground faults are currently detected by the potential relay, 64P. Though 64P relay detects ground fault, it cannot identify the faulted region which causes long traffic delays and safety problem to passengers. A new ground fault protective relay scheme, ${\Delta}I$ ground fault protective relay, that can identify the faulted region is presented in this paper. In ${\Delta}I$ ground fault protective relaying scheme, ground fault is detected by 59, overvoltage relay, which operates ground switch installed between the negative bus and the ground. It preliminarily chooses the faulted feeder after comparing the current increases among feeders and trips the corresponding feeder breaker. After some time delay, it then recloses the breaker if it finds the preselected feeder is not the actual faulted feeder. Whether or not the preselected feeder is the actual faulted feeder is determined by checking the breaker trip status in the neighboring substation in the direction of the tripped breaker. If the corresponding breaker in the neighboring substation is also tripped, it finally judges the preselected feeder is actually a faulted feeder. Otherwise it recloses the tripped breaker. Its algorithms is presented and verified by EMTP simulation.

비접지 DC 급전계통에서 전류형 지락보호계전기의 사용 (New Ground Fault Protective Relay in DC Traction Power System)

  • 정상기;백남욱;김연수;이성혁;이한민
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2004년도 춘계학술대회 논문집
    • /
    • pp.1297-1302
    • /
    • 2004
  • In DC power distribution system for urban rail transits potential relay, 64P, is used to detect the ground faults. The problem with this 64P is that though it detects the ground fault it cannot identify the faulted region. Therefore the faulted region cannot be isolated properly. It could results in power loss of the trains on the healthy regions and the safety of the passengers in the trains could be affected adversely. A new ground fault protective relaying scheme that can identify the faulted region is presented in this paper. The new concept uses the current differential scheme and the permissive scheme to identify the faulted region correctly. A device with similar characteristic to the arrestor is adapted to use the current relay for the ground fault detection. The role of the device is to block the ground leakage current in normal operating condition and enable the ground fault current to flow in ground fault condition. The algorithm of the new relay and the effect of the newly adapted device in the new relaying scheme are discussed.

  • PDF

비접지 DC 급전계통에서 전류형 지락보호계전 방법 (Ground fault protective relaying schemes for DC traction power supply system)

  • 정상기;정락교;이성혁;김연수;조홍식
    • 한국철도학회논문집
    • /
    • 제7권4호
    • /
    • pp.412-417
    • /
    • 2004
  • In urban rail transit systems, ground faults in the DC traction power supply system are currently detected by the potential relay, 64P. Though it detects the fault it cannot identify the faulted region and therefore the faulted region could not be isolated properly. Therefore it could cause a power loss of the trains running on the healthy regions and the safety of the passengers in the trains could be affected adversely. Two new ground fault protective relay schemes that can identify the faulted region are presented in this paper. A current limiting device, called Device X, is newly introduced in both system, which enables large amount of ground fault current flow upon the positive line to ground fault. One type of the relaying schemes is called directional and differential ground fault protective relay which uses the current differential scheme in detecting the fault and uses the permissive signal from neighboring substation to identify the faulted region correctly. The other is called ground over current protective relay. It is similar to the ordinary over current relay but it measures the ground current at the device X not at the power feeding line, and it compares the current variation value to the ground current in Device X to identify the correct faulted line. Though both type of the relays have pros and cons and can identify the faulted region correctly, the ground over current protective relaying scheme has more advantages than the other.