• 제목/요약/키워드: Photoelectric smoke detector

검색결과 15건 처리시간 0.024초

다양한 화원으로부터 발생된 연기를 감지하는 광전식연기감지기의 필요성에 대한연구 (A Study on the Need for Developing a Photoelectric Smoke Detector Detecting Smokes Emitted from Diverse Fire Sources)

  • 이종화
    • 대한안전경영과학회지
    • /
    • 제18권1호
    • /
    • pp.65-73
    • /
    • 2016
  • In this paper which was performed to bring public attention to the need for developing an photoelectric smoke detector that detects smokes emitted from diverse fire sources, it was confirmed that the photoelectric smoke detector may not respond to certain smoke types depending on the size and color of smoke particles. The test was performed on a photoelectric smoke detector which is being used generally for specific fire targets specified in UL268, including paper fire, wood fire and flammable liquid fire, while the actual response performance of the fire detector, as well as respective smoke particles collected from different fire source which were photographed with a SEM(Scanning electron microscope) were analyzed in the test for this study.

화원에 따른 광전식 연기감지기 반응시간 분석 (Analysis of the Response Time of a Photoelectric Spot-Type Smoke Detector Depending on the Type of Fires)

  • 지승욱
    • 조명전기설비학회논문지
    • /
    • 제27권5호
    • /
    • pp.89-94
    • /
    • 2013
  • The fire testing performed for smoke detector model approval in Korea tests only one kind of fire smoke. A photoelectric spot-type smoke detector using Mie scattering is affected by the wavelength of light beam and the particle diameter. According to UL (Underwriters Laboratories Inc.) 268 standard, this paper analyze the characteristic of the response for a photoelectric spot-type smoke detector on sale in Korea using various fire smokes. Probability that the response time is included in non-defective range is 100% in paper fire, 90% in wood fire and 75% in flammable liquid fire, 90% in wood fire and 75% in flammable liquid fire. According to the estimation for population mean of the response time choosing a confidence level of 99%, a maximum of 19% for wood fire and that of 38% for flammable liquid fire are defective. As the result of analysis of smoke particle, this paper is found that these results are caused by the smoke particles are wide variations in size or have very black.

광전식연기감지기 현장점검기기의 문제점에 관한 연구 (A Study on the Problem of Tester for the Field Inspection of the Photoelectric Smoke Detector)

  • 김시국;육현대;양승현;지승욱;이춘하
    • 한국화재소방학회논문지
    • /
    • 제23권4호
    • /
    • pp.137-144
    • /
    • 2009
  • 본 논문은 광전식연기감지기 현장점검기기의 문제점에 관한 연구로서 현재 소방점검 시 광전식연기감지기의 성능확인을 위해 사용되는 A Type(향), B Type(디메틸실리콘오일), C Type(탄화수소혼합물)의 점검기기들을 실험대상으로 선정하고, 현장점검기기의 문제점을 도출하고자 신뢰성확인실험 및 성능확인실험, 연기시료에 따른 감지기 성능변화 실험을 실시하였다. 실험결과 소방점검 시 현장점검기기를 이용한 감도실험은 연기농도조건 및 풍속조건, 연기시료의 문제점을 확인할 수 있었으며, 결과적으로 현재 소방점검시 사용되는 광전식연기감지기 현장점검기기의 신뢰성에 문제가 있는 것을 확인할 수 있었다.

아날로그 광전식 연기감지기 비화재보 개선에 대한 연구 (Study of the Improvement of False Fire Alarms in Analog Photoelectric Type Smoke Detectors)

  • 서병근;남상규
    • 한국화재소방학회논문지
    • /
    • 제30권5호
    • /
    • pp.108-115
    • /
    • 2016
  • 화재감지기는 화재를 조기에 감지하여 관계인에 통보함으로써 자산보호 및 인명안전에 중요한 역할을 한다. 따라서 화재를 조기에 탐지할 수 있는 성능과 비화재보를 발생하지 않는 신뢰성이 중요하다. 최근 공동주택 오피스텔 숙박시설 노유자시설 의료시설 등과 같이 취침, 숙박, 입원 등 이와 유사한 용도로 사용되는 거실에는 조기화재 감지를 위한 연기감지기를 설치하도록 국가 화재안전기준이 개정되어 연기감지기의 적용이 증가되고 있다. 반면 현재 비화재보를 예방하기 위한 연구가 부족하다. 본 연구는 아날로그 광전식 연기감지기의 순간적으로 발생되는 먼지 등으로 인해 발생되는 비화재보를 예방하기 위한 알고리즘 개선과 감지기의 자기보상기능을 통해 감지기의 오염과 화재신호를 구분할 수 있도록 개선하였다. 본 연구를 통해 최근 수요가 증가하는 아날로그 광전식 연기감지기의 비화재보 개선으로 제품의 신뢰성을 확보하여 비화재보로 인한 경제적 손실을 예방할 것으로 기대된다.

화재모델링을 위한 광전식 연기감지기의 장치물성 측정 (Measurement of the Device Properties of Photoelectric Smoke Detector for the Fire Modeling)

  • 조재호;문선여;황철홍;남동군
    • 한국화재소방학회논문지
    • /
    • 제28권6호
    • /
    • pp.62-68
    • /
    • 2014
  • 화재모델링 결과를 이용한 신뢰성이 확보된 피난안전설계를 위해서는 화재감지기 모델들의 높은 예측성능이 필수적으로 요구된다. 본 연구의 목적은 대표적인 화재모델인 FDS에 적용된 광전식 연기감지기의 정확한 작동 개시시간을 예측하기 위한 입력정보를 측정하는 것이다. 이를 위해 화재감지기의 장치특성을 측정할 수 있는 fire detector evaluator(FDE)가 사용되었으며, 스포트형 광전식 연기감지기에 대한 Heskestad 및 Cleary 모델의 입력정보가 얻어졌다. 또한 일반적으로 사용되는 FDS의 기본 값과 측정된 값이 적용된 연기감지기의 작동 개시시간을 정량적으로 비교하였다. 주요 결과로써, Heskestad 모델은 Cleary 모델에 비해 광전식 연기감지기의 작동 개시시간 예측에 부정확한 결과를 초래할 수 있다. 또한 본 연구에서 검토된 광전식 연기감지기의 장치물성은 FDS에 적용된 기본 값과 매우 명확한 차이를 가지며, 장치물성의 변화에 따라 연기감지기 작동 개시시간 또한 매우 큰 차이가 보였다.

장애경보 방지를 위한 연소 연기입자와 비연소 연기입자의 광 특성 분석 (Analysis of Optical Properties of Fire Smoke and Non-fire Smoke for Reduction of Nuisance Alarm)

  • 지승욱
    • 조명전기설비학회논문지
    • /
    • 제28권10호
    • /
    • pp.49-55
    • /
    • 2014
  • This paper is basic study for development of an advanced photoelectric type smoke detector that has high reliability by reducing the occurrence of nuisance alarms. This paper was attempted to distinguish optical characteristics of the typical fire smoke particle and non-fire smoke particle. According to UL 268 standards, three types of test fires (the paper, the wood and the flammable liquid) were used in this paper for measurement of the fire smoke particles, and the water vapor and the cigarette smoke that were known as the main cause of the nuisance alarms were also used for the non-fire smoke particles. A smoke detection chamber was created, which was equipped with one light source and several light sensors for enabling simultaneous detection of light extinction and scattering, respectively. This paper analyzes the optical characteristics of each smoke particle using this chamber.

랙크식 물류창고 조기 화재감지를 위한 최적 화재감지기 설치방법에 관한 실험연구 (An Experimental Study on the Optimum Installation of Fire Detector for Early Stage Fire Detecting in Rack-Type Warehouses)

  • 최기옥;김동석;홍성호
    • 한국안전학회지
    • /
    • 제32권2호
    • /
    • pp.38-45
    • /
    • 2017
  • This paper is an experimental study to find an optimal detection method for detecting fire early in a rack-type warehouse stored with goods. In this study, we constructed rack-type structure with the fourth floor of 13.5 m high and conducted fire experiments which were to measure flow of heat/smoke in rack-type structure and response time of fire detectors. The detectors used at experiments were fixed temperature type detectors, rate of rise detectors, photoelectric smoke detectors, air sampling smoke detectors and flame detectors. The used ignition sources are n-heptane fire for response of heat detection and cotton fire for response of smoke detection. The fixed temperature type detectors, rate of rise detectors and photoelectric detectors were installed to every rack level respectively. The results show that the rate of rise detector should be installed every 2 levels and photoelectric smoke detector should be installed every 4 levels for the early stage fire detection. Air sampling smoke detectors can detect fire early in response to control of sensitivity, but there is a problem in false alarm. The fixed temperature detector is not suitable for early stage fire detection in warehouse and flame detector not worked if flame is not visible, so it need to install combination with other detector.

분진색상에 따른 광전식연기감지기 챔버의 응답특성에 관한 연구 (A Study on Response Characteristics of Photoelectric Type Smoke Detector Chamber Due to Dust Color)

  • 이호성;김시국
    • 한국화재소방학회논문지
    • /
    • 제31권5호
    • /
    • pp.44-52
    • /
    • 2017
  • 본 논문은 분진 색상에 따른 광전식연기감지기 챔버의 응답특성에 관한 연구이다. 국내 자동화재탐지설비 및 경보설비의 화재안전기준의 개정으로 연기감지기의 실내 적용이 의무화되었으나, 아직까지 국내에서는 실내 환경에서 발생되는 실내먼지 및 환경조건 등에 의해 발생될 수 있는 부작동 및 비화재보에 대한 연구가 미비한 편이다. 이에 본 연구에서는 실내먼지 중 가장 많이 발생될 것으로 판단되는 다양한 색상의 섬유분진에 따른 연기감지기의 실내적응성을 연구하기 위해 국내에 가장 많이 보급화 되어 있는 격자형의 연기챔버를 가진 광전식 연기감지기를 실험대상으로 하고, 갈색, 백색, 회색, 흑색 4종류의 섬유분진을 실험분진으로 하여 분진시험 및 감도시험을 진행하였다. 또한, 연기챔버의 수광부 전압을 측정하여 챔버 내부의 산란현상을 관찰하였다. 실험결과 4종류의 분진 모두 오염도 A에서는 분진시험 및 감도시험에서 모두 적합한 것으로 나타났다. 반면, 오염도 B와 C에서는 갈색, 백색, 회색분진의 경우 작동시험 및 부작동시험에서 분진오염에 의한 오작동이 나타났고, 흑색분진의 경우 작동시험에서 부작동이 발생되는 것으로 확인되었다. 연기챔버의 수광부 전압측정 결과는 갈색 및 백색분진의 경우 오염도가 증가할수록 전압이 증가하였고, 회색 및 흑색분진의 경우 전압이 감소하는 것을 확인하였다.

화재실험을 통한 주택용 연기감지기 응답특성에 관한 연구 (A Study on the Response Characteristics of the Residential Smoke Detector Depending on Controlled Fire Tests)

  • 사공성호;김시국;이춘하;정종진
    • 한국화재소방학회논문지
    • /
    • 제23권4호
    • /
    • pp.98-103
    • /
    • 2009
  • 본 논문은 연기감지기의 응답특성을 분석하여 주택용 화재감지기로 적합한지를 분석하고자 광전식연기감지기, 아날로그연기감지기, 단독경보형연기감지기를 시험체로 선정하여 UL 268에서 정하는 화재시험방법을 응용하여 화재성상(종이화재와 인화성액체화재)에 따른 연기감지기의 응답특성을 분석하고자 화재실험을 실시하였다. 실험결과 화재성상에 따라 연기감지기의 응답특성 차이가 나타나는 것을 확인할 수 있었다.

FDS 기반의 연기감지기 예측모델을 위한 입력인자 재검토 (Revision of the Input Parameters for the Prediction Models of Smoke Detectors Based on the FDS)

  • 장효연;황철홍
    • 한국화재소방학회논문지
    • /
    • 제31권2호
    • /
    • pp.44-51
    • /
    • 2017
  • 성능위주 소방설계(PBD)의 과정에서 요구피난시간(RSET) 산정의 신뢰성을 확보하기 위해서는 화재시뮬레이션을 이용한 정확한 연기감지기 작동시간 예측이 필수적이다. 본 연구의 목적은 FDS 기반의 연기감지기 수치모델에서 요구되는 입력인자의 정확도를 개선시키는 것이다. 이를 위하여 선행연구에서 적용된 화재감지기 시험장치(FDE)의 개선이 이루어졌다. 구체적으로 FDE 내부의 유동 및 연기농도 균일성이 개선되었으며, 연기입자의 전방산란 저감을 통해 감지기가 작동되는 순간의 정확한 광 소멸률이 측정되었다. 개선된 FDE를 이용한 입력인자는 기존 결과와 정량적으로 상당한 변화를 보이고 있으며, 이온화식 감지기에 비해 광전식 감지기에서 더 큰 차이가 확인되었다. 연기감지기의 작동조건은 감지기 종류, 가연물, 연기입자 및 색상에 따라 큰 차이가 발생됨을 고려할 때, PBD의 신뢰성을 향상시키기 위하여 향후 연구에서는 보다 다양한 감지기 및 가연물에 대한 입력인자 DB가 구축되어야 할 것이다.