• Title/Summary/Keyword: Penthouse

Search Result 11, Processing Time 0.013 seconds

A Study on the Fire Reconstruction of Exterior on High-rise Building (Focus on Fire Case Including the Woosin Golden Suite in Haeundae) (고층 건축물 외장재의 화재 재현에 관한 연구 (해운대 우신골든스위트의 화재사례를 중심으로))

  • Min, Se-Hong;Lee, Jae-Moon
    • Fire Science and Engineering
    • /
    • v.27 no.2
    • /
    • pp.25-30
    • /
    • 2013
  • 'Heaundae Woosin Building' fire was the case that a fire breaking out on the $4^{th}$ floor spread out the $38^{th}$ floor which is a top story and the penthouse was destroyed by fire. After this fire, the fire safety for high rise buildings has been on the rise and several new laws and regulations related in the buildings were created. The study is to analyze Heaundae officetel building case using FDS which is one of the CFD programs for fire. The methodology of this study is to analyze the case comparing with fire spread and route from a virtual fire simulation and related articles and a video clip of actual scene fire. This study shows that a fire spreading on top of levels spent approximately 30 minutes and, which is similar to the actual fire case. Also the pattern of spread has similarity with the case. However, even if the actual fire case shows the fire pattern was "V shape", the smoke-view presents the fire dose not spread horizontally as much as the real fire case. The result shows uncertainty of the modeling based on many grids and a limitation of putting interior finish input sources and the direction of the wind might cause the difference. Also, to analyze factors influencing on a vertical fire, another fire modeling is performed by in condition of modeling environment considering concrete interior finish between buildings and no wind. The result presents the fire spread in smoke-view does not spread vertically as much as the actual case.