• Title/Summary/Keyword: PVC Sodding

Search Result 1, Processing Time 0.018 seconds

Failure Analysis of LV URD Cable based on FMEA (FMEA에 근거한 LV URD 케이블의 고장분석)

  • Shong, Kil-Mok;Han, Woon-Ki;Kim, Young-Seok;Kim, Sun-Gu;Kwak, Hee-Ro
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.5
    • /
    • pp.90-98
    • /
    • 2007
  • The objective of this investigation was to reveal the cause of the faulted cable(LV URD(low voltage underground) cable). For the analysis, various types or equipments such as external pattern, thermal pattern, surface structure, thermal analysis, and property distribution were deployed. The international standards and the specification provided by the manufacturer of faulted cable were examined whether it fit the standards. The summary is as follows. (1) Discovered as a factor lowering insulation performance of the faulted cable: minimum thickness of the insulation layer specified by IEC 60502-1 and IEC 60811-1-1 was not fit. (2) Infrared absorption peaks measured by FT-IR spectrometer revealed that the measurements made for the same material did not conform and it is an important basis for proving heterogeneous composition of the insulation material. (3) It was found that PVC bedding was thermally fragile and therefore long term exposure at the site could cause similar fault pattern.