Tuning of Dual-input PSS and Its Application to 612 MVA Thermal Plant: Part 1-Tuning Methology of IEEE Type PSS2A Model (다중입력 PSS 튜닝 방법과 612 MVA 화력기 적용: Part 1-IEEE PSS2A 튜닝 방법)

  • Kim, Dong-Joon;Moon, Young-Hwan;Kim, Sung-Min;Kim, Jin-Yi;Hwang, Bong-Hwan;Cho, Jong-Man
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.4
    • /
    • pp.655-664
    • /
    • 2009
  • This paper, Part 1, describes the effective dual-input PSS parameter design procedure for the IEEE Type PSS2A against the Dangjin 612 MVA thermal plant's EX2000 excitation system. The suggested tuning technique used the model-based PSS tuning method and consisted of three steps: 1) generation system modeling; 2) determination of PSS2A model parameters using linear, time-domain transient and 3-phase simultaneous analyses, and 3) field testing and verification, which are described in Part 2. The effective PSS2A model parameters of EX2000 system in the Dangjin T/P #4 were designed according to the suggested procedure, and verified by using three analyses.

Tuning of Dual-input PSS and Its Application to 612 MVA Thermal Plant: Part 2-Field Testing and Performance Verification (다중입력 PSS 튜닝 방법과 612 MVA 화력기 적용: Part 2-현장 튜닝시험 및 성능검증)

  • Kim, Dong-Joon;Moon, Young-Hwan;Kim, Sung-Min;Kim, Jin-Yi;Hwang, Bong-Hwan;Cho, Jong-Man
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.4
    • /
    • pp.665-670
    • /
    • 2009
  • The second paper, Part 2, describes the field testing of IEEE type PSS2A EX2000 excitation in the Dangjin 612 MVA T/P #4. The final PSS gain, $K_s$, was determined by inputting 2%-step signals into AVR at a loading of 500MW and increasing $K_s$, from 0 to 15 in increments of 3. After the field testing, the measured data was also analyzed by Discrete Fourier Transformation(DFT) analysis, and the model parameters of generation system were verified by replicating the measured data with the transient stability program.