• Title/Summary/Keyword: Over Current Ground Relay

검색결과 15건 처리시간 0.025초

비접지 DC 급전계통에서 전류형 지락보호계전 방법 (Ground fault protective relaying schemes for DC traction power supply system)

  • 정상기;정락교;이성혁;김연수;조홍식
    • 한국철도학회논문집
    • /
    • 제7권4호
    • /
    • pp.412-417
    • /
    • 2004
  • In urban rail transit systems, ground faults in the DC traction power supply system are currently detected by the potential relay, 64P. Though it detects the fault it cannot identify the faulted region and therefore the faulted region could not be isolated properly. Therefore it could cause a power loss of the trains running on the healthy regions and the safety of the passengers in the trains could be affected adversely. Two new ground fault protective relay schemes that can identify the faulted region are presented in this paper. A current limiting device, called Device X, is newly introduced in both system, which enables large amount of ground fault current flow upon the positive line to ground fault. One type of the relaying schemes is called directional and differential ground fault protective relay which uses the current differential scheme in detecting the fault and uses the permissive signal from neighboring substation to identify the faulted region correctly. The other is called ground over current protective relay. It is similar to the ordinary over current relay but it measures the ground current at the device X not at the power feeding line, and it compares the current variation value to the ground current in Device X to identify the correct faulted line. Though both type of the relays have pros and cons and can identify the faulted region correctly, the ground over current protective relaying scheme has more advantages than the other.

저장 탱크용 임시전력설비의 보호계전기 정정에 관한 연구 (A Study on the Correction of Protection Relay of Temporary Electric Power Installations for Storage Tank)

  • 손석금
    • 한국정보전자통신기술학회논문지
    • /
    • 제13권6호
    • /
    • pp.562-567
    • /
    • 2020
  • 본 논문은 저장 탱크용 임시전력설비를 보호하기 위한 목적으로 특히 변압기를 감시하고 절연파괴 등과 같은 고장을 차단하고 보호하기 위한 보호계전기 정정에 관한 연구이다. 전력계통에 단락 또는 지락고장 등과 같은 이상이 발생하였을 때 이를 검출하여 고장이 발생한 기기 및 설비를 신속하게 차단하고 전력계통으로부터 분리하여 전력공급에 지장이 없도록 하여야 한다. 전력계통의 이상 상태를 빠르고 정확하게 감지할 수 있는 보호계전기의 정정이 중요하다. 또한 보호협조를 위해 고장종류와 고장의 원인을 정확히 적용한 고장전류 계산이 보호계전기 정정에 가장 중요한 요소이다. 저장 탱크용 임시전력설비 보호를 위해 적용하는 과전류계전기, 지락과전류계전기, 부족전압계전기, 지락과전압계전기 등이 보호협조가 가능하도록 보호계전기 정정 방법에 대해 연구하였다.

분산전원 연계선로에서 지락고장시 중성선의 과전류 해석 및 보호계전기의 새로운 알고리즘 (An Overcurrent Analysis in Neutral Line and Algorithm to Prevent Malfunction of Relay in Distributed Generations)

  • 신동열;김동명;차한주
    • 전기학회논문지
    • /
    • 제58권10호
    • /
    • pp.1916-1922
    • /
    • 2009
  • Introducing distributed generators(DGs) to utility distribution system can cause malfunction of relay on the grid when ground faults or severe load unbalances are occurred on the system. Because DGs interconnected to the grid can contribute fault currents and make bidirectional power flows on the system, fault currents from DGs can cause an interference of relay operation. A directional over current relay(DOCR) can determine the direction of power flow whether a fault occurs at the source side or load side through detecting the phases of voltage and current simultaneously. However, it is identified in this paper that the contributed fault current(Ifdg) from the ground source when was occurred to contribute single-line-to-ground(SLG) fault current, has various phases according to the distances from the ground source. It means that the directionality of Ifdg may not be determined by simply detecting the phases of voltage and current in some fault conditions. The magnitude of Ifdg can be estimated approximately as high as 3 times of a phase current and its maximum is up to 2,000 A depending on the capacity of generation facilities. In order to prevent malfunction of relay and damage of DG facilities from the contribution of ground fault currents, Ifdg should be limited within a proper range. Installation of neutral ground reactor (NGR) at a primary neutral of interconnection transformer was suggested in the paper. Capacity of the proposed NGR can be adjusted easily by controlling taps of the NGR. An algorithm for unidirectional relay was also proposed to prevent the malfunction of relay due to the fault current, Ifdg. By the algorithm, it is possible to determine the directionality of fault from measuring only the magnitude of fault current. It also implies that the directionality of fault can be detected by unidirectional relay without replacement of relay with the bidirectional relay.

분산전원 연계 계통에서의 과전류계전기 오동작에 관한 연구 (A Study on the Over Current Relay Misoperation in Power System with Distributed Generations)

  • 박종일;이계병;박창현
    • 전기학회논문지
    • /
    • 제67권12호
    • /
    • pp.1705-1710
    • /
    • 2018
  • This paper deals with an analysis of the causes of over current relay(OCR) misoperation in power system with distributed generations(DG). In general, Y-D and Y-Y-D transformer connections are used for grid interconnection of DG. According to the interconnection guideline, the neutral point on Y side should be grounded. However, these transformer connections can lead to OCR misoperation as well as over current ground relay(OCGR) misoperation. Several researches have addressed the OCGR misoperation due to the interaction between transformer connections and zero-sequence voltage of distribution system. Recently, a misoperation of OCR at the point of DG interconnection to the utility system has been also reported. With increasing the interconnections of DG, such OCR as well as OCGR misoperations are expected to increase. In this paper, PSCAD/EMTDC modeling including DG interconnection transformer was performed and various case studies was carried out for identifying the cause of OCR misoperation.

방향지락과전류계전기를 이용한 고저항지락사고 검출능력의 향상방안 (A New Scheme to Improve High Impedance Fault Detection Capability Using Directional Over-Current Ground Relay)

  • 이승재;임종윤;김일동;한경남
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 D
    • /
    • pp.1000-1002
    • /
    • 1997
  • In this paper we proposes a scheme which can improve the detecting capability of the high impedance fault of the conventional distance relaying. It utilizes the directional ground overcurrent relay called HIFR together with the distance relay in order to secure the security and selectivity.

  • PDF

비상발전기 보호용 원판형 지락과전류계전기의 고조파영향에 관한 연구 (A Study on the Harmonics Effect of Disc-Type Over Current Ground Relay for Emergency Generator Protection)

  • 김경철;고훈
    • 조명전기설비학회논문지
    • /
    • 제29권6호
    • /
    • pp.58-62
    • /
    • 2015
  • When an emergency generator is running, it supplies the power for critical loads. Generator protection requires the consideration of many abnormal conditions that may occur with generators include overvoltages and ground faults. Modern day power systems create harmonics within the electrical network that can have an impact upon the associated protective system. This paper focuses on the analysing of the cause and development of a solution for the malfunction of induction disc type overcurrent ground relay by generation of harmonics during emergency generator operation.

무부하 충전케이블 개방시 잔류전압에의한 과전압계전기 동작현상 연구 (A Study of Over Voltage Ground Relay Operation Status at Opening of No-load Charged Cable)

  • 김영한;최종혁;윤기섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 A
    • /
    • pp.185-187
    • /
    • 2000
  • Fault current is flowed into 154/23kV M. Tr when line-to-ground fault occurs in power system. NGR(Neutral Grounded Reactor) is set up in order to prevent M.Tr fault by limiting magnitude of fault currents. Here, disconnection of NGR causes voltage increase by L-C resonance and line-to-ground fault in an unearthed system results in voltage increase at healthy phases. So Over Voltage Ground Relay(OVGR) is used for tripping M.Tr. Also, buses at second phases of M.Trs are all connected with section circuit breakers closed for the purpose of parallel operation and load shedding. In case of speciality buses are comprised of power cable in part for GIS connection. When no-load charged cable or bus is open by a section CB, unbalanced voltage charged on the bus is induced. Also discrepant opening time for circuit breakers on different phases gives rise to unbalanced zero sequence voltage. It was observed that this zero sequence voltage detected in the 22.9kV P.T (Potential Transformer for bus) mal-operated 59GT and tripped M.Tr. The zero sequence voltage of which vanishing time is longer than relay operating time came out by EMTDC simulation. Also, it was shown that the voltage waves of actual test are similar to those of simulation. On the basis of above results, R-C circuit complement on the relay without any effect on a power system made operating time of the relay longer than vanishing time of distorted waves. Consequently, operating time of the relay was delayed and magnitude of distorted waves was decreased by increasing time constant of the relay.

  • PDF

배전계통 내 고장발생시 운전모드가 과전류계전기에 미치는 영향 분석 (Analysis of effects of OCR in operation mode during fault ocuurs in Distribution System)

  • 김용환;이상봉;김철환
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.563-564
    • /
    • 2015
  • Recently, distributed generation using renewable energy resources have increased due to the limitation of conventional energy. To utilize these energy source effectively, a method of applying the energy storage system(ESS) in distribution system has been considered. In this paper, we simulated the one line-to-ground fault in power system with ESS. Based on these simulations, we analyzed the effect on Over Current Relay(OCR) operation. As a result, ESS operation modes result fault current fluctuation. Thus, OCR need to reset the pick up current. This paper analyze effect of ESS in distribution system according to OCR setting by using ElectroMagnetic Transient Program(EMTP).

  • PDF

분산전원이 연계된 배전계통에서 보호협조기기의 운용특성에 관한 연구 (Operating Characteristics of Protection Coordination Devices in Distribution System interconnected with Distributed Generation)

  • 김소희;지성호;김선영;노대석
    • 한국융합학회논문지
    • /
    • 제2권2호
    • /
    • pp.35-45
    • /
    • 2011
  • 최근 정부의 녹색성장 정책에 의해 배전계통에 태양광, 풍력발전 등과 같은 분산전원의 보급률이 지속적으로 증가되고 있는 실정이다. 이러한 분산전원의 설치가 급증함에 따라 기존 배전계통의 조류흐름은 단방향(One-direction)에서 양방향(Bi-direction)으로 변화되고 고장전류의 증 감이 발생하는 등, 다양한 변화가 생겨 배전계통의 운용상에 여러 가지 문제점들이 발생할 가능성이 커지고 있다. 따라서 본 논문에서는 분산전원의 배전계통 연계에 따른 보호기기의 정정 및 양방향 보호협조검토가 가능한 보호협조 평가알고리즘을 제안하고, 그 알고리즘을 바탕으로 양방향 보호협조 평가시스템을 제작하였다. 또한 평가시스템을 이용하여 배전계통을 모델링하고 분산전원 연계 시 보호기기들 사이의 보호협조를 검토하여, 분산전원이 연계된 경우 배전계통에 발생할 수 있는 기술적인 문제점들을 분석하여 그 방안을 제시하였다.

분산전원이 연계된 배전계통에 보호협조기기 평가시스템의 최적운용에 관한 연구 (A study on Optimal Operation of Protection Coordination Devices Evaluation System in Distribution System with Distributed Sources)

  • 지성호;송방운;김병기;노대석
    • 한국산학기술학회논문지
    • /
    • 제14권6호
    • /
    • pp.2971-2978
    • /
    • 2013
  • 최근 배전계통은 정부의 녹색성장 정책으로 태양광, 풍력발전 등과 같은 분산전원의 보급률이 지속적으로 증가되고 있는 실정이다. 이러한 분산전원의 연계로 기존 배전계통의 조류흐름은 단방향(One-direction)에서 양방향(Bi-direction)으로 변화되고, 고장전류의 증 감이 발생하는 등, 다양한 변화가 생겨 배전계통의 운용상에 여러 가지 문제점들이 발생할 가능성이 커지고 있다. 따라서 본 논문에서는 분산전원의 배전계통 연계에 따른 보호기기의 정정 및 양방향 보호협조 검토가 가능한 보호협조 평가알고리즘과 실제의 사고전류 값을 이용한 개선된 T-C곡선 알고리즘을 제안하고, 이 알고리즘을 바탕으로 양방향 보호협조 평가시스템을 개선하였다. 또한 평가시스템을 이용하여 배전계통을 모델링하고, 분산전원 연계 시 보호기기들 간의 보호협조를 검토하여, 분산전원이 연계된 경우 배전계통에 발생할 수 있는 기술적인 문제점들을 분석하여 그 방안을 제시하였다.