Wilson Plot을 이용한 만액식 증발기의 열전달계수 측정 (Measurement of Heat Transfer Coefficient in a Flooded Evaporator through Wilson Plot Method)

  • 윤필현;강용태;정진희
    • 설비공학논문집
    • /
    • 제16권8호
    • /
    • pp.698-706
    • /
    • 2004
  • Heat transfer coefficients of enhanced tubes in a flooded evaporator are measured through Wilson Plot method. And the correlations are proposed to design a flooded evaporators. Overall heat transfer coefficients are composed of the heat transfer coefficients both inside and outside tubes. Usually the experiments have been conducted separately. But there have been many difficulties like setting up the equipments and measuring the wall temperature. Wilson Plot method makes it possible to measure the separated transfer coefficients at the same equipment through experimental skills. So the cost and time can be reduced. And the results are reliable enough to use for design. Heat transfer coefficients inside the tube were able to be correlated uniquely in spite of various outside conditions. Boiling heat transfer of R134a is more dependent on the saturation temperature and much higher than that of R123.

외표면 형상이 원관의 응축열전달에 미치는 영향 (Experiments on the Condensation Heat Transfer Enhancement of Horizontal Circular Tube with Threaded Outside Surface)

  • 이진호;남임우
    • 대한설비공학회지:설비저널
    • /
    • 제17권3호
    • /
    • pp.230-237
    • /
    • 1988
  • An experiment was carried out to study the condensation heat transfer enhancement of horizontal circular cylinders with varying outside surface configurations. The refrigerant used is Freon-22 and the test condensing temperature is 34.1C. Pin-finned tube shows about 2.5-3.5 times higher overall heat transfer coefficient compared to that of smooth surface tube, thus has larger encomic benifit for condenser design. The condensation heat transfer coefficient was shown to increase as the fin-pitch of the pin-finned tube decreases for film Reynolds number larger than 100.

  • PDF

절삭유 냉각용 낮은 핀관의 응축 및 비등 열전달 성능에 관한 연구 (A Study on the Performance of the Condensation and the Boiling Heat Transfer of Low Fin Tubes Used in Cooling of the Cutting Oil)

  • 이종선
    • 한국생산제조학회지
    • /
    • 제8권4호
    • /
    • pp.68-78
    • /
    • 1999
  • Heat transfer performance is studied for boiling and condensation of R-11 on integral-fin tubes. Nine tubes with trapezoidal integral-fins having fin densities from 748 to 1654fpm and 10,30 grooves and finned tubes with caves of 0.55 and 0.64 mm height respectively are tested. in case of condensation CFC-11 condensates at saturation stat of 32$^{\circ}C$ on the outside surface cooled by inside cooling water flows. And in case of boiling the refrigerant evaporates at a saturation state of 1 bar on the outside tube surface and heat is supplied by hot water which circulates inside of the tube,. The tube having fin transfer coefficient concerns fin tubes with caves show higher valve than low fin tube having find density of 1299fpm and 30grooves. The overall heat transfer coefficient of fin tube with caves is about 5155 W/mK at 2.8m/s of water velocity, The value is abuot 2.7 times higher than plain tube and 1.3 times higher than low fin tube having fin density of 1299fpm and 30 grooves.

  • PDF

절삭유 냉각용 낮은 핀관의 응축 및 비등 열전달 성능에 관한 연구 (A Study on the Performance of the Condensation and the Boiling Heat Transfer of Low Fin Tubes Used in Cooling of the Cutting Oil)

  • 조동현;이종선
    • 한국생산제조학회지
    • /
    • 제8권4호
    • /
    • pp.65-65
    • /
    • 1999
  • Heat transfer performance is studied for boiling and condensation of R-11 on integral-fin tubes. Nine tubes with trapezoidal integral-fins having fin densities from 748 to 1654fpm and 10,30 grooves and finned tubes with caves of 0.55 and 0.64 mm height respectively are tested. in case of condensation CFC-11 condensates at saturation stat of 32℃ on the outside surface cooled by inside cooling water flows. And in case of boiling the refrigerant evaporates at a saturation state of 1 bar on the outside tube surface and heat is supplied by hot water which circulates inside of the tube,. The tube having fin transfer coefficient concerns fin tubes with caves show higher valve than low fin tube having find density of 1299fpm and 30grooves. The overall heat transfer coefficient of fin tube with caves is about 5155 W/mK at 2.8m/s of water velocity, The value is abuot 2.7 times higher than plain tube and 1.3 times higher than low fin tube having fin density of 1299fpm and 30 grooves.

친수성 표면처리가 수평관 외벽의 증발열전달에 미치는 영향 (Effects of Hydrophilic Surface Treatment on Evaporation Heat Transfer at the Outside Wall of Horizontal Tubes)

  • 박노성;황규대;강병하;정진택
    • 설비공학논문집
    • /
    • 제12권5호
    • /
    • pp.525-532
    • /
    • 2000
  • Evaporation heat transfer characteristics have been investigated experimentally when distilled water is sprayed on the outside wall of horizontal tubes in a evaporator. This problem is of particular interest in the design of evaporator of an absorption system. Hydrophilic surface treatment was employed to increase the wettability on copper tubes. The results indicate that evaporation heat transfer with hydrophilic tubes is shown to be 25-44% higher than that with bare tubes at evaporation pressure of 31.8 Torr(evaporation temperature$ 30^{\circ}C). Evaporation heat transfer rates of hydrophilic treatment tubes are improved substantially, comparing with those of conventional copper tubes in the wide range of operating parameters, such as water inlet temperatures, water mass flow rates and evaporation pressures.

  • PDF

공작기계 절삭유 냉각용 낮은 핀관의 열전달 성능에 관한 연구 (A Study on the Performance of Heat Transfer of Low Fin Tubes Used in Cooling of the Cutting Oil of the Machine Tool)

  • 조동현
    • 한국공작기계학회:학술대회논문집
    • /
    • 한국공작기계학회 1998년도 추계학술대회 논문집
    • /
    • pp.125-133
    • /
    • 1998
  • Nine tubes with trapezoidal integral-fins having fin densities from 748 to 1654fpm and 10,30 grooves and finned tubes with caves of 0.55 and 0.64mm height respectively are tested. A plain tube having same diameter as the finned tubes is also tested for comparison. In case of condensation CFC-11 condensates at saturation state of 32$^{\circ}C$ on the outside surface cooled by inside cooling water flows. And in case of boiling the refrigerant evaporates at a saturation state of 1bar on the outside tube surface and heat is supplied by hot water which circulates inside of the tube. The tube having fin density of 1299fpm and 30grooves has the best condensation overall heat transfer coefficient. However, as far as boiling heat transfer coefficient concerns, fin tubes with cave show higher value than low fin tube having fin density of 1299fpm and 30 grooves.

  • PDF

프로필렌 냉매의 증발열전달 특성에 관한 실험적 연구 (Experimental Study on Heat Transfer Characteristics of Evaporation using Propylene Refrigerant)

  • 이호생;김재돌;정석권;윤정인
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제28권5호
    • /
    • pp.754-761
    • /
    • 2004
  • In this paper, evaporating heat transfer characteristics in the refrigeration and air-conditioning facilities were studied using the environmentally friendly refrigerants R-1270 (Propylene). R-290 (Propane). R-600a (Iso-butane) and HCFC refrigerant R-22 The test tube was surrounded by an annulus with water flowing counter to the refrigerant. The tube is copper. with an outside diameter of 12.7mm and the wall thickness of 1.315mm. The test results showed that the local evaporating heat transfer coefficients of hydrocarbon refrigerants were superior to that of R-22 and the maximum increasing rate of heat transfer coefficient was found in R-1270. The average evaporating heat transfer coefficient increased with the increase of the mass velocity and it showed the higher values in hydrocarbon refrigerants than R-22 Comparing the heat transfer coefficient of experimental results with that of other correlations. the presented results had agood agreement with the Kandlikar's correlation. This results form the investigation can be used in the design of heat transfer exchangers using hydrocarbons as the refrigerant for the air-conditioning systems.

헬리컬관외 침전 및 적하 열전달 특성에 관한 연구 (Study on the Heat Transfer Characteristics of Immerged and Falling Flows on Helical Tubes)

  • 황승기;윤상국;김동혁;이승갑
    • 설비공학논문집
    • /
    • 제13권4호
    • /
    • pp.225-232
    • /
    • 2001
  • An experimental study is carried out to investigate the characteristics of heat transfer of outside helical tubes. The main heat exchanger consists of twelve curved columns with each 300mm diameter and the total length of 1.2m copper tube having an outer diameter of 19.05mm with 1.5mm thickness. Water flows down the outside of helical tube, where flow patterns are the vertical film falling flow, immerged flow, and mixed-flow which is the combination of film falling flow and immerged flow. Refrigerant 11 flow the inside of the tube countercurrently. The experimental range of inside flow rate is 1.7~3.2$\ell$/min and outside flow rate is 21-33$\ell$/min. The results are presented as Nusselt number with corresponding Reynolds number for variety of outside and inside flow rates. The heat transfer rates of the mixed flow are 8 to 56% higher than those of film falling flow or immerged flow only. Interpretation of the results is given on the basis of physical reasoning and the correlation equations.

  • PDF

내면 핀관을 사용하는 열교환기에서 R-22 대체 탄화수소계 냉매의 증발 열전달 특성 (Evaporating heat transfer characteristics of R-22 alternative hydrocarbon refrigerants at heat exchanger using grooved inner tube)

  • 홍진우;박승준;노건상;구학근;오후규
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제24권4호
    • /
    • pp.414-420
    • /
    • 2000
  • In this paper, evaporation heat transfer characteristics at a inner grooved tube were studied using a new natural refrigerants R-290, R-600a and HCFC refrigerant R-22. Experiments were performed in the inner tube with outside diameter of 12.70mm, having 75 fins with a fin height of 0.25mm. The following results were obtained from this research. On the evaporating heat transfer characteristics, the maximum increment of heat transfer coefficient was found in R-290. Average heat transfer coefficient was obtained the maximum value in R-290 and the minimum value in R-22. It reveals that the natural refrigerant can be used as a substitute for R-22. In the grooved inner tube, 70% of the increment of the heat transfer coefficient was obtained compared to the smooth tube. Comparing the heat transfer coefficient between experimental results and simulation data of other's, the Kandlikar's correlated equation was closely approximated to the author's experimental results in the smooth tube or grooved inner one.

  • PDF

유동층 연소로 내에서 수평 휜 전열관의 열전달 특성에 관한 실험적 연구 (An Experimental study on Heat Characteristics of Horizontal Tubes with Fin in Fluidized Bed Combustor)

  • 강형수;정태용
    • 한국연소학회지
    • /
    • 제1권1호
    • /
    • pp.19-29
    • /
    • 1996
  • This study is to investigate the characteristics of heat transfer of a horizontal tube, with radial fins of various configuration, immersed in a high temperature fluidized bed. The experimental heat transfer variation is compared with that of a smooth tube. The finned tubes and smooth tube, with outside and inside diameter of 48.6mm and 30.6mm, are made of steel tubes. The depth of the fin is 5mm, the rake angles of fin are $25^{\circ},\;35^{\circ},\;45^{\circ}$ and the widthes of fin for each rake angle are 0mm, 1mm, 2mm and 3mm. A bed temperature is fixed at $880\;{\pm}\;10^{\circ}C$. A granular refractory(silica sand) is used as a bed material with mean particle diameters of 1.22mm and 1.54mm. The maximum heat transfer coefficient is achieved with the rake angle of $25^{\circ}$ and the width of 0mm for the mean particle size 1.22mm. The coefficient is 2.14 times larger than that for a smooth tube. The rake angle for the maximum heat transfer coefficient depends on the particle size of bed material. Also the transfer coefficient decreases as the width of fin increases.

  • PDF