본 연구의 목적은 간접식 증발냉각 장치의 성능을 예측하고, 장치를 공기조화기의 배기열 회수에 적용하였을 경우의 에너지 절약효과를 분석하는 것이다. 플라스틱 열교환기를 사용한 간접식 증발냉각장치의 성능 상관식을 여러가지 조건에서 얻어진 실험 데이터로부터 구하였으며, 이 상관식을 이용하여 환기와 외기의 조건을 변화시켜가면서 장치의 성능변화를 예측하였다. 또한 간접식 증발냉각장치의 배기열 회수에 의한 에너지 절약효과를 우리나라 몇개 도시의 표준기상데이터를 사용하여 분석하였다. 여름철 배기열 회수를 위한 현열냉각장치의 사용율은 평균 44.3%이며 증발냉각장치의 사용율은 96.7% 이다. 증발냉각장치의 배기열 회수에 의한 에너지 절약은 현열냉각장치에 비해서 훨씬 높으며, 서울의 경우 약 3.89 배로 나타났다.
In order to investigate the effects of PAG oil concentration on heat transfer performance and pressure drop during gas cooling process of $CO_2$, the experiments on fin-tube heat exchanger of $CO_2$ heat pump were performed. The experimental apparatus consists of a gas cooler, a heater, a chiller, a mass flow meter, a pump and measurement system. Experiments were conducted in various experimental conditions, which were inlet temperature($110^{\circ}C$), mass flow rates (50, 55, 60, 65, 70 g/s) and PAG oil concentration(0 to 2.6 wt%). Heat transfer rate decreased with the increase of the oil concentration and the decrease of inlet pressure. And pressure drop increased with the increase of the oil concentration and mass flow rate of refrigerant. The COP reduction by deterioration of gas cooler performance with oil concentration was analyzed. When inlet pressure of gas cooler is 100 bar, the COP reduction was estimated by 6% under 1 wt% of oil concentration.
The peak demand of electricity in summer season mainly comes from the day time cooling loads. Ice thermal Storage System (ITSS) uses off-peak electricity at night time to make ice for the day time cooling. In order to maximize the use of cold storage in ITSS, the estimation of day time cooling load for the building is necessary. In this study, we present a method of cooling load estimation using 5 years of normalized outdoor temperature, relative humidity, and the building construction data. We applied the hourly-based estimation to a general hospital building with relatively less sudden heat exchange and the results are compared with the measured cooling load of the building. The results show that the cooling loads estimation depends on the indoor cooling design temperature of the building.
This paper presents the heating performance of a water-to-refrigerant type ground source heat pump system (GSHP) installed in a school building. The evaluation of the heating performance has been conducted under the actual operating conditions of GSHP system in the winter. Ten units with the capacity of 10 HP each were installed in the building. Also, a closed vertical typed-ground heat exchanger with 24 boreholes of 175 m in depth was constructed for the GSHP system. For analyzing the heating performance of the GSHP system, we monitored various operating conditions, including the outdoor temperature, the ground temperature, and the water temperature of inlet and outlet of the ground heat exchanger. Simultaneously, the heating capacity and the input power were evaluated for determining the heating performance of the GSHP system. The average heating coefficient of performance (COP) of the heat pump was found to be 5.1 at partial load of 46.9%, while the overall system COP was found to be 4.2.
This paper presents the heating performance of a water-to-refrigerant type ground source heat pump system (GSHP) installed in a school building. The evaluation of the heating performance has been conducted under the actual operating conditions of GSHP system in the winter. Ten units with the capacity of 10 HP each were installed in the building. Also, a closed vertical typed-ground heat exchanger with 24 boreholes of 175 m in depth was constructed for the GSHP system. For analyzing the heating performance of the GSHP system, we monitored various operating conditions, including the outdoor temperature, the ground temperature, and the water temperature of inlet and outlet of the ground heat exchanger. Simultaneously, the heating capacity and the input power were evaluated for determining the heating performance of the GSHP system. The average heating coefficient of performance (COP) of the heat pump was found to be 5.1 at partial load of 46.9%, while the overall system COP was found to be 4.2.
In the perspective of saving energy in buildings, the high performance of insulation and air tightness for improving the heating and the cooling efficiency, has brought economically positive effects. However, these building energy saving technologies cause the lack of ventilation, which is the direct cause of increasing the indoor contaminants, and is also very harmful to the residents, because they spend over 90% of their time indoors. Therefore, the ventilation is important to keep the indoor environment clean and it can also save the energy consumption. In this study, a HEPA type nano ceramic filter is designed as a passive ventilation system to collect airborne particles and to supply fresh outdoor air. The double layer filter, which has $30{\mu}m$ in diameter at the conditions of 10wt% of concentration and 3kV/cm of the electric intensity, is produced by electrospinning. The filtration coating technology is confirmed in the solution with $SiO_2$ nano particles using polymer nano fibers. Also double layer filters are coated with $SiO_2$ nano particles and finally the porous construction materials are made by sintering in the electric furnace at $200{\sim}1400^{\circ}C$. The efficiency is measured 96.67% at the particle size of $0.31{\mu}m$, which is slightly lower than HEPA filter. However the efficiency is turned out to be sufficient.
The annual mean temperature of South Korea has risen by $1.3^{\circ}C$ for last 100 years by urbanization and industrialization. Especially, the frequency of unusual hot weather in summer increases for a long time and the frequency of unusual cold weather in winter clearly decreases. In recently, The considerable portion of curtain wall system is appled to building skin in domestic. As related to this, the Korea Institute of Construction Technology devised the box typed double skin facade(It is occasionally called as FDFS : Functional Double Facade System) as an alternative that reflects the distinctive local climate and saves cooling energy. Two mock-ups($49m^*4.9m$) applied to single skin(curtain wall) and double skin each were monitored under the outdoor condition. Therefore, the characteristics of natural ventilation and cooling energy consumption of each window had been analyzed in real time. The results of this study are summarized as follow, Analysis of the experiment on an air conditioner: the indoor temperature of the chamber with FDFS is lower than that of the chamber with single skin facades by $3{\sim}6$ degrees(C). A temperature variation of about $1{\sim}2$ degrees between the 0.2m and 1.7m height of the mock-up occurs in FDFS, while that of about maximum 7 degrees occurs in single skin facade at noon with abundant intensity of solar accident. Also, 67 percent of energy consumption for air conditioning has been saved.
The cooling load in winter is significant in many commercial buildings and hotels because of the usage of office equipments and the high efficiency of wall insulation. The development of a multi-heat pump that can cover heating and cooling simultaneously for each indoor unit is required. In this study, the performance of a multi-heat pump with 3-piping system was investigated as a function of refrigerant charge and its performance was analyzed in cooling mode, heating mode, and heat recovery mode. COP in the heating or cooling mode showed little dependence on refrigerant charge at overcharge conditions, while those were strongly dependent on refrigerant charge at undercharge conditions and outdoor inlet temperature. In the heat recovery mode, the performance of the system was very sensitive to charge amount at all conditions. Optimum charge amount in the heat recovery mode was 14% lower than that in the cooling mode at the standard condition because the refrigerant only passed the indoor units. It is required to store the excessive refrigerant charge in a storage tank to optimize the system performance at operating modes.
본 연구의 목적은 열대 지방에서 사용되는 특수목적 자동차용 에어컨 시스템의 냉방성능 특성을 고찰하는 것이다. 이를 위하여 R-134a를 사용하는 듀얼 냉동사이클을 구성하였고 냉매량 및 실내온도를 변화시켜가면서 냉방성능을 비교하였다. 외기온도 $40.0^{\circ}C$에서 듀얼 냉동사이클의 실내 냉각속도 및 압축비(토출압력) 등을 고려하여 최적 냉매량을 1.5kg으로 선정하였다. 실내온도가 증가할수록 냉방부하가 증가하여 $25.0^{\circ}C$에서 $32.5^{\circ}C$로 실내온도를 높일 경우 $15.0^{\circ}C$에 도달하는데 걸리는 시간은 86.5% 증가하였고, $32.5^{\circ}C$에서 $40.0^{\circ}C$로 증가할 경우 38.1% 증가하였다. 또한, 실내온도가 $25.0^{\circ}C$에서 $40.0^{\circ}C$로 증가할수록 냉방용량은 19.1 kW에서 20.5 kW로 7.3% 증가했으나 냉방성능(COP)는 4.67에서 5.1로 7.0%감소하였다.
통풍과 차양이 하절기 옥외공간에서 인간이 느끼는 온열쾌적성에 어떤 영향을 미치는지를 객관적으로 검증하기 위하여 통풍과 차양을 달리한 실험구를 조성하고 흑구온도와 기온 및 풍속을 측정하여 평균복사온도를 환산하여 비교 분석하였다. 미기후 측정을 위하여 개방된 잔디밭에 철제 각관을 이용하여 가로${\times}$세로${\times}$높이가 각각 $3m{\times}3m{\times}1.5m$인 프레임을 구성하고, 투명 폴리에틸렌 필름과 농업용 차광막을 이용하여 통풍과 차양의 조건을 달리한 네 가지의 실험구를 조성하였다. 각 실험구 내 중심부 지면으로부터 1.2m 높이에서 베인형 풍속계와 흑구, 측온저항체(PT-100)를 이용하여 2011년 5월 1일부터 동년 9월 30일까지 풍속과 기온, 흑구온도를 매 분 단위로 계측하였다. 기상조건과 계측자료의 유효성 등을 고려하여 총 44일 동안의 13,262건의 자료를 바탕으로 실험구별 일중 시계열적 변화를 분석하였으며, 낮 시간에 해당되는 오전 7시부터 오후 8시까지의 7,172건의 자료를 바탕으로 실험구에 따른 통계적 차이를 해석하였다. 아울러 햇볕이 가장 강렬한 시간대인 오전 11시부터 오후 4시까지의 자료를 바탕으로 평균복사온도와 풍속 및 일사량과의 관계를 분석하였다. 평균복사온도를 기준으로 해석했을 때, 통풍이 차단된 노지에서의 측정기간 중 최고값이 $58.84^{\circ}C$까지 상승한 반면, 차양이 적용되고 통풍이 원할한 실험구의 최고값은 $42.94^{\circ}C$였다. 시험결과를 종합하면, 하절기 옥외공간에서 낮 동안의 평균복사온도에 있어서 차양에 의해서는 최대 $13^{\circ}C$, 평균 $9^{\circ}C$의 냉각효과가 발생한 반면, 방풍에 의해서는 반대로 평균 약 $3^{\circ}C$의 가열효과가 있는 것으로 정리되어, 통풍이 되지 않는 태양직사광 지역은 바람이 원활하게 통하는 그림자 지역 보다 최대 $16^{\circ}C$까지 높은 것으로 나타났다. 결론적으로 본 연구를 통해서 하절기 옥외공간의 열쾌적성을 개선하는데 차양이 가장 중요하며, 그 다음이 통풍이라는 사실을 파악할 수 있었다. 따라서 옥외공간에 더 많은 녹음수와 숲을 조성하여 그림자 지역을 증가시킴으로써 인간의 하절기 옥외활동에 많은 제약을 주고 있는 불필요한 열에너지를 현격하게 저감시켜 쾌적한 미기후를 효과적으로 조성할 수 있으며, 나아가 정교하게 조성된 바람길이나 통풍 시스템을 적용한다면 도시 전체의 열환경도 효과적으로 개선할 수 있을 것이다.
본 웹사이트에 게시된 이메일 주소가 전자우편 수집 프로그램이나
그 밖의 기술적 장치를 이용하여 무단으로 수집되는 것을 거부하며,
이를 위반시 정보통신망법에 의해 형사 처벌됨을 유념하시기 바랍니다.
[게시일 2004년 10월 1일]
이용약관
제 1 장 총칙
제 1 조 (목적)
이 이용약관은 KoreaScience 홈페이지(이하 “당 사이트”)에서 제공하는 인터넷 서비스(이하 '서비스')의 가입조건 및 이용에 관한 제반 사항과 기타 필요한 사항을 구체적으로 규정함을 목적으로 합니다.
제 2 조 (용어의 정의)
① "이용자"라 함은 당 사이트에 접속하여 이 약관에 따라 당 사이트가 제공하는 서비스를 받는 회원 및 비회원을
말합니다.
② "회원"이라 함은 서비스를 이용하기 위하여 당 사이트에 개인정보를 제공하여 아이디(ID)와 비밀번호를 부여
받은 자를 말합니다.
③ "회원 아이디(ID)"라 함은 회원의 식별 및 서비스 이용을 위하여 자신이 선정한 문자 및 숫자의 조합을
말합니다.
④ "비밀번호(패스워드)"라 함은 회원이 자신의 비밀보호를 위하여 선정한 문자 및 숫자의 조합을 말합니다.
제 3 조 (이용약관의 효력 및 변경)
① 이 약관은 당 사이트에 게시하거나 기타의 방법으로 회원에게 공지함으로써 효력이 발생합니다.
② 당 사이트는 이 약관을 개정할 경우에 적용일자 및 개정사유를 명시하여 현행 약관과 함께 당 사이트의
초기화면에 그 적용일자 7일 이전부터 적용일자 전일까지 공지합니다. 다만, 회원에게 불리하게 약관내용을
변경하는 경우에는 최소한 30일 이상의 사전 유예기간을 두고 공지합니다. 이 경우 당 사이트는 개정 전
내용과 개정 후 내용을 명확하게 비교하여 이용자가 알기 쉽도록 표시합니다.
제 4 조(약관 외 준칙)
① 이 약관은 당 사이트가 제공하는 서비스에 관한 이용안내와 함께 적용됩니다.
② 이 약관에 명시되지 아니한 사항은 관계법령의 규정이 적용됩니다.
제 2 장 이용계약의 체결
제 5 조 (이용계약의 성립 등)
① 이용계약은 이용고객이 당 사이트가 정한 약관에 「동의합니다」를 선택하고, 당 사이트가 정한
온라인신청양식을 작성하여 서비스 이용을 신청한 후, 당 사이트가 이를 승낙함으로써 성립합니다.
② 제1항의 승낙은 당 사이트가 제공하는 과학기술정보검색, 맞춤정보, 서지정보 등 다른 서비스의 이용승낙을
포함합니다.
제 6 조 (회원가입)
서비스를 이용하고자 하는 고객은 당 사이트에서 정한 회원가입양식에 개인정보를 기재하여 가입을 하여야 합니다.
제 7 조 (개인정보의 보호 및 사용)
당 사이트는 관계법령이 정하는 바에 따라 회원 등록정보를 포함한 회원의 개인정보를 보호하기 위해 노력합니다. 회원 개인정보의 보호 및 사용에 대해서는 관련법령 및 당 사이트의 개인정보 보호정책이 적용됩니다.
제 8 조 (이용 신청의 승낙과 제한)
① 당 사이트는 제6조의 규정에 의한 이용신청고객에 대하여 서비스 이용을 승낙합니다.
② 당 사이트는 아래사항에 해당하는 경우에 대해서 승낙하지 아니 합니다.
- 이용계약 신청서의 내용을 허위로 기재한 경우
- 기타 규정한 제반사항을 위반하며 신청하는 경우
제 9 조 (회원 ID 부여 및 변경 등)
① 당 사이트는 이용고객에 대하여 약관에 정하는 바에 따라 자신이 선정한 회원 ID를 부여합니다.
② 회원 ID는 원칙적으로 변경이 불가하며 부득이한 사유로 인하여 변경 하고자 하는 경우에는 해당 ID를
해지하고 재가입해야 합니다.
③ 기타 회원 개인정보 관리 및 변경 등에 관한 사항은 서비스별 안내에 정하는 바에 의합니다.
제 3 장 계약 당사자의 의무
제 10 조 (KISTI의 의무)
① 당 사이트는 이용고객이 희망한 서비스 제공 개시일에 특별한 사정이 없는 한 서비스를 이용할 수 있도록
하여야 합니다.
② 당 사이트는 개인정보 보호를 위해 보안시스템을 구축하며 개인정보 보호정책을 공시하고 준수합니다.
③ 당 사이트는 회원으로부터 제기되는 의견이나 불만이 정당하다고 객관적으로 인정될 경우에는 적절한 절차를
거쳐 즉시 처리하여야 합니다. 다만, 즉시 처리가 곤란한 경우는 회원에게 그 사유와 처리일정을 통보하여야
합니다.
제 11 조 (회원의 의무)
① 이용자는 회원가입 신청 또는 회원정보 변경 시 실명으로 모든 사항을 사실에 근거하여 작성하여야 하며,
허위 또는 타인의 정보를 등록할 경우 일체의 권리를 주장할 수 없습니다.
② 당 사이트가 관계법령 및 개인정보 보호정책에 의거하여 그 책임을 지는 경우를 제외하고 회원에게 부여된
ID의 비밀번호 관리소홀, 부정사용에 의하여 발생하는 모든 결과에 대한 책임은 회원에게 있습니다.
③ 회원은 당 사이트 및 제 3자의 지적 재산권을 침해해서는 안 됩니다.
제 4 장 서비스의 이용
제 12 조 (서비스 이용 시간)
① 서비스 이용은 당 사이트의 업무상 또는 기술상 특별한 지장이 없는 한 연중무휴, 1일 24시간 운영을
원칙으로 합니다. 단, 당 사이트는 시스템 정기점검, 증설 및 교체를 위해 당 사이트가 정한 날이나 시간에
서비스를 일시 중단할 수 있으며, 예정되어 있는 작업으로 인한 서비스 일시중단은 당 사이트 홈페이지를
통해 사전에 공지합니다.
② 당 사이트는 서비스를 특정범위로 분할하여 각 범위별로 이용가능시간을 별도로 지정할 수 있습니다. 다만
이 경우 그 내용을 공지합니다.
제 13 조 (홈페이지 저작권)
① NDSL에서 제공하는 모든 저작물의 저작권은 원저작자에게 있으며, KISTI는 복제/배포/전송권을 확보하고
있습니다.
② NDSL에서 제공하는 콘텐츠를 상업적 및 기타 영리목적으로 복제/배포/전송할 경우 사전에 KISTI의 허락을
받아야 합니다.
③ NDSL에서 제공하는 콘텐츠를 보도, 비평, 교육, 연구 등을 위하여 정당한 범위 안에서 공정한 관행에
합치되게 인용할 수 있습니다.
④ NDSL에서 제공하는 콘텐츠를 무단 복제, 전송, 배포 기타 저작권법에 위반되는 방법으로 이용할 경우
저작권법 제136조에 따라 5년 이하의 징역 또는 5천만 원 이하의 벌금에 처해질 수 있습니다.
제 14 조 (유료서비스)
① 당 사이트 및 협력기관이 정한 유료서비스(원문복사 등)는 별도로 정해진 바에 따르며, 변경사항은 시행 전에
당 사이트 홈페이지를 통하여 회원에게 공지합니다.
② 유료서비스를 이용하려는 회원은 정해진 요금체계에 따라 요금을 납부해야 합니다.
제 5 장 계약 해지 및 이용 제한
제 15 조 (계약 해지)
회원이 이용계약을 해지하고자 하는 때에는 [가입해지] 메뉴를 이용해 직접 해지해야 합니다.
제 16 조 (서비스 이용제한)
① 당 사이트는 회원이 서비스 이용내용에 있어서 본 약관 제 11조 내용을 위반하거나, 다음 각 호에 해당하는
경우 서비스 이용을 제한할 수 있습니다.
- 2년 이상 서비스를 이용한 적이 없는 경우
- 기타 정상적인 서비스 운영에 방해가 될 경우
② 상기 이용제한 규정에 따라 서비스를 이용하는 회원에게 서비스 이용에 대하여 별도 공지 없이 서비스 이용의
일시정지, 이용계약 해지 할 수 있습니다.
제 17 조 (전자우편주소 수집 금지)
회원은 전자우편주소 추출기 등을 이용하여 전자우편주소를 수집 또는 제3자에게 제공할 수 없습니다.
제 6 장 손해배상 및 기타사항
제 18 조 (손해배상)
당 사이트는 무료로 제공되는 서비스와 관련하여 회원에게 어떠한 손해가 발생하더라도 당 사이트가 고의 또는 과실로 인한 손해발생을 제외하고는 이에 대하여 책임을 부담하지 아니합니다.
제 19 조 (관할 법원)
서비스 이용으로 발생한 분쟁에 대해 소송이 제기되는 경우 민사 소송법상의 관할 법원에 제기합니다.
[부 칙]
1. (시행일) 이 약관은 2016년 9월 5일부터 적용되며, 종전 약관은 본 약관으로 대체되며, 개정된 약관의 적용일 이전 가입자도 개정된 약관의 적용을 받습니다.