• 제목/요약/키워드: Opimal Feeder Routing

검색결과 2건 처리시간 0.015초

적응 유전알고리즘을 이용한 배전계통 계획의 급전선 최적경로 선정 (An Adaptive Genetic Algorithm Based Optimal Feeder Routing for Distribution System Planning)

  • 김병섭;김민수;신중린
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제50권2호
    • /
    • pp.58-66
    • /
    • 2001
  • This paper presents an application of a newly designed Adaptive Genetic Algorithm (AGA) to solve the Optimal Feeder Routing (OFR) problem for distribution system planning. The main objective of the OFR problem usually is to minimize the total cost that is the sum of investment costs and system operation costs. We propose a properly designed AGA, in this paper, which can handle the horizon-year expansion planning problem of power distribution network in which the location of substation candidates, the location and amount of forecasted demands are given. In the proposed AGA, we applied adaptive operators using specially designed adaptive probabilities. we also a Simplified Load Flow (SLF) technique for radial networks to improve a searching efficiency of AGA. The proposed algorithm has been evaluated with the practical 32, 69 bus test system to show favorable performance. It is also shown that the proposed method for the OFR can also be used for the network reconfiguration problem in distribution system.

  • PDF

휴리스틱 탐색전략을 이용한 배전계통 계획의 급전선 최적 경로 선정 (Optimal Feeder Routing for Distribution System Planning Using a Heuristic Strategy)

  • 최남진;김병섭;신중린
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제49권11호
    • /
    • pp.566-574
    • /
    • 2000
  • This paper propose a heuristic algorithm based on the Branch-Exchange (BE) method to solve Optimal feeder Routing(OFR) problem for the distribution system planning. The cost function of the OFR problem is consisted of the investment cost representing the feeder installation and the system operation cost representing the system power loss. We propose a properly designed heuristic strategy, which can handle the horizon-year expansion planning problem of power distribution network. We also used the loop selection method which can define the maximum loss reduction in the network to reduce calculation time, and proposed a new index of power loss which is designed to estimate the power loss reduction in the BE. The proposed index, can be considered with both sides, the low voltage side and voltage side branch connected with tie one. The performances of the proposed algorithms and loss index were shown with 32, 69 example bus system.

  • PDF