A Study on the Effects of Various Disk Shape of Hydrant on the Pressure Drop (옥외소화전의 디스크 형상을 고려한 압력손실에 관한 연구)

  • You, Woo Jun;Shim, Myoung Gyu;Sung, Kun Hyuk;Yu, Jae Bum;Youm, Moon Cheon;Ryou, Hong-Sun
    • Fire Science and Engineering
    • /
    • v.27 no.6
    • /
    • pp.1-7
    • /
    • 2013
  • In this study, the effects of various disk shapes of hydrant on the pressure drop are experimentally and numerically analyzed. The test methods for measuring pressure drop of hydrant are comply with standard of Underwriters Laboratory (UL). The hydrant as used in this study has one inlet, diameter 150 mm, and three outlet, 114.3 mm diameter for one outlet and 63.5 mm diameter for the others. The pressure of the hydrant are measured in the range 760 L/min~2,270 L/min for 63.5 mm outlet and 3,030 L/min~6,060 L/min for 114.3 mm outlet. Also, the numerical results of pressure drop are compared with the experiments to verify the accuracy and to analyze the of various valve shape of hydrant on the pressure drop. The engineering parameters, flow coefficients, are reduced from 181.57 to 136.35 ($L/min/kPa^{0.5}$) with inclined angle of disk from $0^{\circ}$ to $45^{\circ}$. These results are able to practical use for design hydrant to minimize pressure drop.