• Title/Summary/Keyword: On-voltage power cable

Search Result 266, Processing Time 0.041 seconds

Medium Voltage HTS Cable Thermal Simulation using PSCAD/EMTDC

  • Jung, Chaekyun;Kang, Yeonwoog;Kang, Jiwon
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.1 no.1
    • /
    • pp.145-150
    • /
    • 2015
  • This paper described the medium voltage high temperature superconducting cable thermal simulation and its application. New simulation method for HTS cable modeling using PSCAD/EMTDC is introduced in this paper. The developed simulation method consists of electrical model part and thermal model part. In electrical model part, power loss and thermal capacitance can be calculated in each layer, then the temperature of each layer can be calculated by power loss and thermal capacitance in thermal model part. This paper also analyzes the electrical and thermal characteristic in the case of normal operating condition and transient including single line to ground fault and line to line ground fault using new simulation method.

Examination of Conductor and Sheath Temperatures Dependent on the Load Currents through High-Power Live Cables at a Power Station (발전소에서 활선 고전력 케이블의 운전 부하전류에 따른 도체 및 피복표면의 온도 분석)

  • Um, Kee-Hong
    • The Journal of the Institute of Internet, Broadcasting and Communication
    • /
    • v.17 no.1
    • /
    • pp.213-218
    • /
    • 2017
  • High-voltage power systems operate in order to generate and transmit electric power at power stations. Compared to low-power systems, high-power systems are complex in structure, large-scale, and expensive. When high-power cable accidents occur, most facilities are incapacitated-including low-power systems-causing huge economic losses. Great care must therefore be taken in designing, installing and managing power systems. Although dependent on installation circumstances and usage conditions, in some cases the cross-sectional areas of cables fall short of the critical area due to the expansion of and improper design and installation of power facilities. In this situation, the exceeded ampacity (allowable current) above the critical value caused by the operating current initiates the deterioration processes of power cables. In order to systematically monitor power cables operating at power stations, we have developed the first device of its kind in Korea. In this paper, we present the analyzed characteristics of expected temperatures of cables based on the load current of high-voltage cables operating at Korean Western Power Co. Ltd. We can predict the lifetime of cables by analyzing the temperature obtained from our device.

Review of the Conceptual Design for the Use of HTS Power Transmission Cable for a Metropolitan Area

  • Park, Sang-Bong
    • KIEE International Transactions on Power Engineering
    • /
    • v.3A no.2
    • /
    • pp.63-69
    • /
    • 2003
  • The necessity of compact high temperature superconducting cables is more keenly felt in densely populated metropolitan areas. Because the compact high-temperature superconducting cables can be installed in ducts and tunnels, thereby reducing construction costs and making the use of underground space more effective, the effect of introducing it to the power system will be huge. Seoul, Korea, is selected as a review model for this paper. The loads are estimated by scenario based on a survey and analysis of 345kV and 154kV power supply networks in this area. Based on this, the following elements for an urban transmission system are examined. (1) A method of constructing a model system to introduce high-temperature superconducting cables to metropolitan areas is presented. (2) A case study is conducted through the analysis of power demand scenarios, and the amount of high-temperature superconducting cable to be introduced by scenario is examined. (3) The economy involved in expanding existing cables and introducing high-temperature superconducting cables(ducts or tunnels) following load increase in urban areas is examined and compared., and standards for current cable ducts are calculated. (4) The voltage level that can be accommodated by existing ducts is examined.

Analysis of Switching Overvoltage in 345kV Underground and Combined Transmission Systems (345kV 지중 및 혼합 송전계통에서의 개폐 과전압 해석)

  • 정채균;이종범;강지원
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.12
    • /
    • pp.713-721
    • /
    • 2003
  • This paper analyzes the switching overvoltage occurred on 345kV underground power cable system as well as combined transmission system using EMTP. Cable length and closing time, preinsertion resistance have effect on switching overvoltage. Therefore, this paper analyzes the switching overvoltage occurred on conductor and sheath with change of those parameters. Specially, the cross bonding position becomes discontinuity point because of the difference between surge impedance of metal sheath and that of lead cable. Thus, the transmission and the reflection of traveling wave complexly occur at this connection point. According to these influences, voltage between sheath and earth as well as voltage between joint boxes rise. Time to crest point of switching overvoltage is longer than lightning overvoltage. Even though the voltage induced by switching surge is smaller than lightning surge, that voltage may have serious effect on the metal sheath. Therefore, this paper also analyses the reduction effect of switching overvoltage when the preinsertion resistance of circuit breaker is considered.

Analysis of the Induced Voltage on the 154kV Underground Cable (154kV 지중케이블에서 유기전압의 해석)

  • Choi, Suk-Young;Yoo, Myeong-Ho;Bai, Doo-Han;Oh, Jung-Hwan;Rim, Seong-Jeong;Kim, Jae-Chul
    • Proceedings of the KIEE Conference
    • /
    • 1997.07c
    • /
    • pp.1184-1186
    • /
    • 1997
  • In this paper, we analyze the induced voltage and current in the underground transmission cable. To analyze it, we select the 154[kV] underground transmission system which is located in the city. In the case of the steady state, the single phase fault, and three phase fault in the underground cable, we analyze the induced voltage and current for an equivalent model through EMTP simulation. Also, the components of an equivalent model and the computer simulation using EMTP is described.

  • PDF

Study on Crack Resistance Improvement of Epoxy Insulation (Epoxy 절연물의 내크랙성 향상에 관한 연구)

  • Ha, Young-Kil;Kim, Su-Yon;Lee, Sang-Jin;Kim, Young-Seong;Park, Wan-Ki
    • Proceedings of the KIEE Conference
    • /
    • 1999.07d
    • /
    • pp.1581-1583
    • /
    • 1999
  • Epoxy Compound has been used as insulation material in cable accessories. During the applying voltage to cable, heat shock is induced to accessory by the temperature difference between atmosphere and conductor. In this study, crack resistance, thermal and mechanical properties were evaluated about conventional epoxy compound and rubber toughened epoxy compound. Because rubber absorbs the stress caused by heat shock, crack resistance of rubber toughened epoxy compound is high. In the case of low thermal expansion coefficient, the compound shows high crack resistance because of low volumetric change.

  • PDF

Power System Security Control Method for Quench Characteristic of High-Temperature Superconducting Cable (초전도 케이블의 퀜치 특성에 대한 계통안전성 제어방식)

  • Lee, Geun-Joon;Hwang, Si-Dol;Lee, Jeong-Phil;Kim, Chang-Hyun;Park, Hye-Chul
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.375-380
    • /
    • 2004
  • This paper presents the basic quench protection idea for the HTS(High-Temperature Superconducting) cable. In Korea power system, the transfer capability of transmission line is limited by the voltage stability, and HTS cable could be one of the countermeasure to solve the transfer limit as its higher current capacity and lower impedance[1]. However, the quench characteristic of HTS cable makes HTS cable to loss its superconductivity, and therefore change the impedance of the line and power system operating condition dramatically. This pheonominum threats not only HTS cable safety but also power system security, therefore a proper protection scheme and security control counterplan have to be established before HTS cable implementation. In this paper, the quench characteristics of HTS cable for the fault current based on heat balance equation was established and a proper protection method by FCL(Fault Current Limiter) was suggested.

  • PDF

Analysis of induced voltage of CCPU with unbalanced current from Distribution Line on Underground Transmission Cable System (지중송전계통에서 배전선 불평형전류 유입에 따른 영향 검토)

  • Kang, J.W.;Jang, T.I.;Hong, D.S.;Jung, C.K.;Yoon, D.S.;Yoon, J.K.;Kim, H.H.
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.459-461
    • /
    • 2005
  • This paper analyses the induced voltage characteristic of CCPU with unbalanced current from distribution line on underground transmission power cable systems. In switching surge strokes, in order to obtain the data of induced voltage/current on CCPU, the actual proof test carried out. This paper is expected to contribute the establishment of proper protection methods of CCPU against the unbalanced current from distribution line on underground transmission power cable systems.

  • PDF

The investigation of tracking resistant sheath material for ADSS Optic cable (ADSS 광 케이블 시스용 내 트래킹 재료의 특성에 관한 연구)

  • Lee, Jung-Hee;Seo, Il-Gun;Whang, Sun-Ho;Lee, Gun-Joo;Bak, Seung-Yup;Kim, Kyeung-Min;Lee, Seung-Chan
    • Proceedings of the KIEE Conference
    • /
    • 2002.11a
    • /
    • pp.102-105
    • /
    • 2002
  • ADSS(All Dielectirc Self-Supporting) cable installed under high voltage power cable line suffers a variety of environmental influence, rain, wind, snow fall, chemical pollution, salt fog and electrical stress. Its lifetime is required to be at least 20 years with this harsh weathering condition. The electrical stress under high voltage power line gives rise to dry band arcing and tracking, the severest damage, on the outer sheath of cable. Finally tracking might penetrate sheath and cause the break-down of ADSS cable. Tracking resistant sheath material, therefore, should be used to protect the core of ADSS from dry band arcing and to be sure long lifetime. In this work, we discuss various commercial tracking resistant material to investigate the way of track resistance and compare their mechanical, electrical, weathering and tracking properties through serial experiments. We found track resistant material is categorized into two main type : polyethylene with metal hydroxide and polyethylene with reduced carbon black. The Liquid contaminant, Inclined plane Tracking and Erosion test says the time to track of tracking resistant material with metal hydroxide has a little longer time to track in the high applied voltage than that with carbon black, but mechanical and weathering properties were inferior to.

  • PDF

A Study on Energy Characteristics in Transient States of OF Cable Systems (OF 케이블 계통에서 과도상태시 에너지 특성 검토)

  • Jung, Chae-Kyun;Lee, Jong-Beom;Kang, Ji-Won;Lee, Dong-Il;Seo, Je-Ho
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.11
    • /
    • pp.468-475
    • /
    • 2006
  • This paper reviews the energy characteristics of oil filled cables in transient state such as grounding fault and lightning surge. Artificial grounding fault test was firstly performed in 2003 for the analysis of arc voltage and breakdown energy according to the fault current. In this paper, energy of OF cable is variously analysed at joint box based on the actual test. Then more various conditions such as installation types, section lengths and CCPU(Cable Covering Protection Unit) connection types are applied for the simulation using EMTP when the single line to ground fault and direct lightning stroke are occurred on actual underground power cable systems and combined power cable systems, respectively. Finally, the energy by the length of crossbonded lead and grounding lead as well as fault lasting time is also calculated using EMTP simulation.