• Title/Summary/Keyword: On-line PD monitoring

Search Result 48, Processing Time 0.022 seconds

Asymmetric Capacitive Sensor for On-line and Real-time Partial Discharge Detection in Power Cables

  • Changhee Son;Hyewon Cheon;Hakson Lee;Daekyung Kang;Jonghoo Park
    • Journal of Sensor Science and Technology
    • /
    • v.32 no.4
    • /
    • pp.219-222
    • /
    • 2023
  • Partial discharges (PD) have long been recognized as a major contributing factor to catastrophic failures in high-power equipment. As the demand for high voltage direct current (HVDC) facilities continues to rise, the significance of on-line and real-time monitoring of PD becomes increasingly prominent. In this study, we have designed, fabricated, and characterized a highly sensitive and cost-effective PD sensor comprising a pair of copper electrodes with different arc lengths. The key advantage of our sensor is its non-invasive nature, as it can be installed at any location along the entire power cable without requiring structural modifications. In contrast, conventional PD sensors are typically limited to installation at cable terminals or insulation joint boxes, often necessitating invasive alterations. Our PD sensor demonstrates exceptional accuracy in estimating PD location, with a success rate exceeding 95% in the straight sections of the power cable and surpassing 89% in curved sections. These remarkable characteristics indicate its high potential for realtime and on-line detection of PD.

Development of Insulation Diagnosis System by On-Line Partial Discharge Measurement of Generator Stator Windings (발전기 고정자 권선의 운전중 부분방전 측정에 의한 절연진단 시스템 개발)

  • Shin, Byoung-Chol;Hwang, Don-Ha;Kim, Yong-Joo;Kim, Jeong-Woo
    • Proceedings of the KIEE Conference
    • /
    • 1999.11d
    • /
    • pp.1025-1027
    • /
    • 1999
  • Recently, many researches on a diagnosis of stator winding insulation of large generators are reported. They mostly utilize a trend analysis of Partial Discharge (PD). In this paper, a novel on-line monitoring system for an insulation diagnosis is proposed. This system obtains the parameters such as Maximum Partial Discharge Magnitude (QM), Normalized Quantity Number (NQN) and Dynamic Stagnation Voltage (DSV) by continuous on-line monitoring of winding insulation. It is capable of diagnosing the insulation condition by analyzing the trend of PD and utilizing the database built by the system.

  • PDF

Development of On-line PD Monitoring System for High Voltage Power Cable System (초고압 선로 부분방전 On-line 모니터링 시스템 개발)

  • Kim, Choong-Sik;Lee, Chang-Young;Kim, Won-Nyeon
    • Proceedings of the KIEE Conference
    • /
    • 2005.07e
    • /
    • pp.58-60
    • /
    • 2005
  • 초고압 선로에 대한 풍부한 진단 경험과 축적된 Know-how를 바탕으로 선로의 이상유무를 원격으로 진단, 감시하는 On-line PD Monitoring System을 개발하였다. 초고압 선로의 이상 유무를 활선상태에서 정밀하게 진단할 수 있는 전기적인 측정방법으로 부분방전이 유일하다. 그러나 부분방전 신호는 미약하고 주위 노이즈와 구분이 어렵기 때문에 측정 뿐만 아니라 분석하기가 어렵다. 부분방전 측정 장비는 이러한 노이즈를 효과적으로 제거하고 측정된 신호를 의미있는 정보로 가공하여 사용자에게 제공해 주어야 한다. 본 논문에서는 이러한 조건들을 충족하는 고성능의 원격 진단시스템에 관하여 서술하였다.

  • PDF

Assessment of Insulation Condition in Operating Large Turbine Generator (운전중인 대형 터빈발전기에서 절연상태 평가)

  • 김희동
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.6
    • /
    • pp.324-329
    • /
    • 2004
  • Six stator slot couplers(SSC) and a flux probe sensor installed on the stator winding slots of large turbine generator. Assessment of insulation condition has been based upon the measurements of partial discharge(PD) of stator windings and shorted-turn of rotor windings in operating large turbine generator. The maximum PD magnitude(Qm), normalized quantify number(NQN), PD pattern and shorted-turn were measured using on-line insulation condition monitoring system. The NQN and Qm of slot PD side in the phase A are indicated the highest value in six SSC sensors. Monitoring system results showed that discharge at conductor surface and internal discharge were detected at the surface of stator winding and in voids of the groundwall insulation. Insulation of stator and rotor windings in large turbine generator was judged to be in good condition.

Development of On-tine Partial Discharge Monitoring System for High-Voltage Motor Stator Windings (고압 전동기 고정자 권선의 운전중 절연감시 시스템 개발)

  • Hwang, D.H.;Sim, W.Y.;Park, D.Y.;Gang, Dong-Sik;Kim, Y.J.;Song, S.O.;Kim, H.D.
    • Proceedings of the KIEE Conference
    • /
    • 2001.11a
    • /
    • pp.224-226
    • /
    • 2001
  • In this paper, a novel high-voltage motor monitoring system (HVMMS) is proposed. This system monitors the insulation condition of the stator winding by on-line measurements of partial discharge (PD). Sensor, EMC (Epoxy-Mica Coupler) is used for PD measurement PD signals are continuously measured and digitized with a peak-hold A/D converter to build the database of the high-voltage motor's insulation condition. Also, this system can communicate with the central monitoring system via RS-485. This helps more efficient operation and maintenance of the generator.

  • PDF

A Study of On-line Monitoring System for a KEPCO Pumped Storage Generator/Motor

  • Kim Hee-Dong;Ju Young-Ho;Kim Yong-Joo;Cho Kyu-Bock
    • Transactions on Electrical and Electronic Materials
    • /
    • v.7 no.2
    • /
    • pp.90-95
    • /
    • 2006
  • An on-line diagnostic test has been studied and performed for the pumped storage generator/motor. This study aims at reducing the diagnostic cost, minimizing the technical dependency on third party manufactures. Further design of on-line diagnostic system such as shorted-turn of rotor winding, partial discharge (PD) of stator winding and air-gap between stator and rotor for pumped storage generator/motor has been verified. In addition, it needs to be validated on site performance of the developed continuous on-line monitoring system for corresponding tasks for the improvement of the availability & reliability during operation.

Implementation of an Inductively Coupled EM Probe System for PD Diagnosis

  • Kim, Hee-Dong;Park, Noh-Joon;Park, Dae-Hee
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.1
    • /
    • pp.111-118
    • /
    • 2011
  • In recent years, various types of partial discharge (PD) methods such as capacitive, inductive, electromagnetic, and acoustic coupling techniques have been developed for diagnosing rotating machines. An electromagnetic (EM) probe, which is an inductively coupled type of sensor, is required for detecting corona and internal discharges during off-line tests. In this study, a new technique for enhancing the measurement sensitivities for corona and internal discharge based on an EM inductive position sensor is proposed. An EM probe that winds wires around horseshoe-shaped and cylindershaped ferrites as helices is designed and optimized for the implementation of off-line PD monitoring of the stator winding of a rotating machine. The measurement system based on this design is implemented, and it is verified from the results of the experiment performed in this study that the probe provides similar performance as existing commercial products.

Flashover Prediction of Polymeric Insulators Using PD Signal Time-Frequency Analysis and BPA Neural Network Technique

  • Narayanan, V. Jayaprakash;Karthik, B.;Chandrasekar, S.
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.4
    • /
    • pp.1375-1384
    • /
    • 2014
  • Flashover of power transmission line insulators is a major threat to the reliable operation of power system. This paper deals with the flashover prediction of polymeric insulators used in power transmission line applications using the novel condition monitoring technique developed by PD signal time-frequency map and neural network technique. Laboratory experiments on polymeric insulators were carried out as per IEC 60507 under AC voltage, at different humidity and contamination levels using NaCl as a contaminant. Partial discharge signals were acquired using advanced ultra wide band detection system. Salient features from the Time-Frequency map and PRPD pattern at different pollution levels were extracted. The flashover prediction of polymeric insulators was automated using artificial neural network (ANN) with back propagation algorithm (BPA). From the results, it can be speculated that PD signal feature extraction along with back propagation classification is a well suited technique to predict flashover of polymeric insulators.

Assessment of Insulation Condition in Gas Turbine Generator Stator Windings (가스터빈 발전기 고정자 권선의 절연상태 평가)

  • Kim, Hee-Dong;Yang, Gyu-Hyun;Ju, Young-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.8
    • /
    • pp.1423-1428
    • /
    • 2010
  • The results of off-line and on-line diagnostic tests performed on the stator winding of an air-cooled gas turbine(G/T) generator are reported in this paper. Off-line diagnostic tests included measurements of the ac current, dissipation factor(tan${\delta}$), and partial discharge(PD). Six epoxy-mica capacitors were installed in the three phases of G/T generator for performing on-line diagnostic testing with the turbine generator analyzer(TGA). The TGA showed that the normalized quantity number(NQN) and the PD magnitude($Q_m$) were high in phase A of the stator winding. Internal discharges were generated in phases B and C, and slot discharge occurred in phase A. According to the trend analyses of the NQN and $Q_m$ values available for insulation condition assessment for G/T generator stator windings, it was concluded that phases B and C were in good condition, whereas phase A has been significantly deteriorated.

Application of SA-SVM Incremental Algorithm in GIS PD Pattern Recognition

  • Tang, Ju;Zhuo, Ran;Wang, DiBo;Wu, JianRong;Zhang, XiaoXing
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.1
    • /
    • pp.192-199
    • /
    • 2016
  • With changes in insulated defects, the environment, and so on, new partial discharge (PD) data are highly different from the original samples. It leads to a decrease in on-line recognition rate. The UHF signal and pulse current signal of four kinds of typical artificial defect models in gas insulated switchgear (GIS) are obtained simultaneously by experiment. The relationship map of ultra-high frequency (UHF) cumulative energy and its corresponding apparent discharge of four kinds of typical artificial defect models are plotted. UHF cumulative energy and its corresponding apparent discharge are used as inputs. The support vector machine (SVM) incremental method is constructed. Examples show that the PD SVM incremental method based on simulated annealing (SA) effectively speeds up the data update rate and improves the adaptability of the classifier compared with the original method, in that the total sample is constituted by the old and new data. The PD SVM incremental method is a better pattern recognition technology for PD on-line monitoring.