• Title/Summary/Keyword: Novel wet/dry type cooling tower

Search Result 1, Processing Time 0.016 seconds

A Numerical Study on the Performance Analysis of the Plume Abatement NWD Cooling Tower (백연 방지를 위한 NWD냉각탑의 성능해석에 관한 수치해석적 연구)

  • 최창혁;최영기;소헌영
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.11
    • /
    • pp.1049-1058
    • /
    • 2001
  • The performance and design analysis for a NWD cooling tower using a combined wet and dry type fill are numerically investigated and compared with the experimental results. The Stoecker's method is applied to the wet section and LMTD or NTU-Effectiveness method to the wet and dry sections. The efficiency ratio of the NWD cooling tower to a wet type crossflow cooling tower is 59.34%. The predicted result shows a good agreement with the experimental data within 1.4% error. Plume abatement is far better with a NWD cooling tower than a counterflow cooling tower. It costs less than a conventional wet/dry tower because the finned exchanger is eliminated. This method also leaves out complexity in structure and Intricacy in operation.

  • PDF