Development of System and Measured Results for Measuring Insulation Resistance of High-Power Cables in Operation (활선 고전력 케이블의 절연저항을 측정하기 위한 시스템 설계 및 측정결과)

  • Um, Kee-Hong;Kim, Bo-Kyeong
    • The Journal of the Institute of Internet, Broadcasting and Communication
    • /
    • v.16 no.4
    • /
    • pp.165-170
    • /
    • 2016
  • The XLPE(or CV) cables installed to deliver high electric power from generator at the power station have operating for the last 40 years in Korea. In 6-8 years from the time of initial operation, the cables in operation start a deteriorating process, depending on the installation and usage conditions. Some cables, even before 6-8 years from the installation, can cause accidents due to the faulty construction or other inadequate environments. In order to prevent cable accident in advance, the regular auditing of power cables are required. For a systematic realization of surveillance and prevention of accidents, we have invented a measuring device. In this paper, we present the device installed at Korean Western Power Co. Ltd., in order to detect the deterioration status of insulation resistances of dielectrics in the cables. We present that the measured results by the device we developed show the deteriorating processes in the cables in operation.

Relationship Between Humidity and Insulation Status of XLPE 6.6kV Cables for the Load of Electric Turbine Generator (터빈 발전기 부하용 XLPE 6.6kV 케이블의 절연층 절연상태와 습도의 상관관계)

  • Um, Kee-Hong
    • The Journal of the Institute of Internet, Broadcasting and Communication
    • /
    • v.16 no.5
    • /
    • pp.185-190
    • /
    • 2016
  • The high-power 6.6 kV XLPE (or CV) cables at Korean electric power stations have been in operation for the last 40 years. Most of the XLPE cables starts deteriorating in 6-8 years from the operating instant of time, some cables may be breakdown at any moment even though they were installed in recent years, causing, huge socioeconomic losses. In order to prevent unexpected cable accident, the operating status of power cables should be monitored in regularly, timely bases. We have invented a device in order to systematically monitor and prevent an abrupt accidents of high-power cables in operation at power station. It has been installed at Korean Western Power Co. Ltd. at Taean, and operating normally for the last 4 years. In this paper, we introduce the functions and operating principles of the measuring device, and present the relationship between humidity and insulation status of XLPE cables for the load of electric turbine generator.

Design of Measuring System for Insulation Resistance and Humidity in High-Power XLPE Cables in Operation and the Relationship Between Insulation Resistance and Humidity in the Oversheath (운전 중인 고전력 XLPE 케이블의 절연저항과 습도의 측정 시스템 설계 및 방식층 절연저항과 습도의 상관관계)

  • Um, Kee-Hong
    • The Journal of the Institute of Internet, Broadcasting and Communication
    • /
    • v.16 no.5
    • /
    • pp.179-184
    • /
    • 2016
  • The usual way used by electric power stations to deliver high levels of generated power is via 6.6kV XLPE (or CV) cables. Depending on the manufacturing technique, installation environment, and usage conditions, the deterioration processes of the power cables start from the instant of operation. Cable junctions may break down in three years from the start of operation due to the manufacturing or construction defects. Otherwise they should be in good working order for 20-30 years. When the cable system (the cable itself and cable junctions combined) deteriorates, fire accidents happen due to the dielectric breakdowns. We have invented a device to monitor the deteriorating status of cables at Korean Western Power Co. Ltd. located in Taean, Chungcheongnam-do province. In this paper, we introduce the device hardware. Using the device, we have measured the insulation resistance and humidity in the sheath of the cables. We present, in analysed results, the effect of humidity on insulation resistance in cable sheaths.

Calculation of the Harmonic Emission Limit for low-Voltage Electrical Equipment (국내 저압 전기기기의 고조파 유출 제한값 산정)

  • Kang, Moon-Ho;Song, Yang-Hoi;Lee, Heung-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.10
    • /
    • pp.56-61
    • /
    • 2008
  • Because the harmonic disturbance characteristic which makes voltage drop and the deterioration of instantaneous power quality in electrical power system overheats the NGR and the customer capacitor and malfunctions the OCGR and AMR, it is necessary for electric power company to take active measures to reduce this disturbance. International Electrotechnical Commission(IEC) 61000-3-2 specifies limits for harmonic current emissions generated by low voltage(LV) electrical equipment whose input current $\leq$ 16(A) per phase. Analysis shows that limits for Class A equipment in IEC are calculated using the reference impedance of LV system and maximum permissible voltage and limits for other Classes are also calculated based on limits for Class A. Therefore we have calculated four(4) internal limits for LV electrical equipment using the korea reference impedance and maximum permissible voltage in this paper.