• 제목/요약/키워드: Multiple-tube heat exchanger

검색결과 13건 처리시간 0.02초

증기압축식 냉동장치에서 다증관 열교환기의 성능특성에 관한 실험적 연구 (An Experimental Study of the Performance Characteristics on Multiple-tube Heat Exchanger in the Vapor Compression Refrigeration System)

  • 김재돌
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제33권1호
    • /
    • pp.37-43
    • /
    • 2009
  • This paper is performed to develop a tripple-tube exchanger which can improve the system efficiency. Three different tube diameters are compacted by one body(tripple-tube) to recover waste heat from heat exchanging among the fluids. With this, the tripple-tube shows higher cooling capacity than the double-tube after comparing between those two systems. The results of this paper are basic data to design the optimum tripple-tube heat exchanger.

공기압축기의 인터쿨러 선정을 위한 열교환기의 형상별 성능해석 (Comparison of Various Heat Exchanger Performances in order for Air Compressor Intercooler Application)

  • 유상훈;박상구;윤정필;정지환
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제32권1호
    • /
    • pp.73-81
    • /
    • 2008
  • Intercooling and aftercooling are required in order to operate air compressor, these are conducted through air-cooled or water-cooled heat exchangers. This study aims to find more suitable type of heat exchanger as a water-cooled intercooler of air compressor. Comparative performance evaluation among fin-tube heat exchanger and shell-and-tube (S&T) heat exchanger having various tubes such as circular tube, spiral tube, and internally finned tube was conducted. Thermal-hydraulic performance of each heat exchanger type is evaluated in terms of temperature drop and pressure drop. The comparisons show that shell-and-tube heat exchangers may have similar and larger heat transfer capacity to the fin-tube heat exchanger if tube diameter is reduced and multiple pass is adopted. For these cases, however, compressed air pressure drop in shell-and-tube heat exchanger become much larger than that in fin-tube heat exchanger.

다관형 순환유동층 열교환기의 유동 및 전열성능 예측모델 연구 (A Study on Prediction Model of Flow and Heat Transfer in the Circulating Fluidized Bed Heat Exchanger with Multiple Vertical Tubes)

  • 박상일
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.1199-1204
    • /
    • 2006
  • The pressure drop and heat transfer coefficient were measured at room temperature in CFB heat exchanger with multiple vertical tubes. Also the circulation rate of solid particles was measured. The theoretical model for predicting heat transfer coefficient using the solid flowrate was developed in this study. The model predictions were compared with the measured heat transfer coefficient to show relatively good agreement.

  • PDF

에어컨 실외기용 휜-관 직교형 열교환기의 열, 유동 해석 및 휜 성능 개선을 위한 연구 (Flow and heat transfer analysis for the performance improvement of cross-flow fin-tube heat exchangers)

  • 안진수;최도형
    • 한국전산유체공학회:학술대회논문집
    • /
    • 한국전산유체공학회 2004년도 춘계 학술대회논문집
    • /
    • pp.183-189
    • /
    • 2004
  • The flow and the heat transfer about the cross-flow fin-tube heat exchanger in an out-door unit of a heat pump system has been numerically Investigated. Using the general purpose analysis code, FLUENT, the Navier-Stokes equations and the energy equation are solved for the three dimensional computation domain that encompasses multiple rows of the fin-tube. The temperature on the fin and tube surface is assumed constant but compensated later through the fin efficiency when predicting the heat-transfer rate. The contact resistance is also taken into consideration. The flow and temperature fields for a wide range of inlet velocity and fin-tube arrangements are examined and the results are presented in the paper. The details of the flow are very well captured and the heat transfer rate for a range of inlet velocity is in excellent agreement with the measured data. The flow solution provides the effective permeability and the inertial resistance factor of the heat exchanger if the exchanger were to be approximated by the porous medium. This information is essential in carrying out the global flow field calculation which, in turn, provides the inlet velocity lot the microscopic temperature-field calculation of the heat exchanger unit.

  • PDF

Tow in 와류발생기에 의한 핀-관 열교환기의 성능실험 (Performance Evaluation in Fin-Tube Heat Exchanger by Tow-In Winglet Pairs)

  • 곽경민;;배철호
    • 설비공학논문집
    • /
    • 제15권2호
    • /
    • pp.87-94
    • /
    • 2003
  • To reduce the air side pressure drop in air-cooled heat exchanger, tow-in type winglet vortex generators are applied. A specially designed multiple-channel test core was used in the experiments for the various geometry of winglet vortex generators. The proposed tow-in type vortex generator gives significant separation delay, reduces form drag, and removes the zone of poor heat transfer from near-wake of the tubes. The results show the significant pressure drop reduction for the tow-in win91e1 vortex generators with the similar enhancement of the heat transfer as other vortex generator applications in heat exchanger. In the range of Reynolds number of 350 to 2100 the pressure drop decrease 8∼15% and 34∼55% for the in-line and staggered tube banks, respectively, compared to those without vortex generators.

다관형 고밀도 순환유동층 열교환기의 열전달계수에 대한 예측모델 연구 (A Study on Prediction Model of Heat Transfer Coefficient in the Circulating Fluidized Bed Heat Exchanger with Multiple Vertical Tubes)

  • 박상일
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.288-293
    • /
    • 2005
  • The pressure distribution and heat transfer coefficient were measured at room temperature in the high suspension density CFB heat exchanger with multiple vertical tubes and the effective density of CFB was determined. The theoretical model for predicting heat transfer coefficient was developed in this study. The model predictions were compared with the measured heat transfer coefficient to show relatively good agreement between them.

  • PDF

다관형 순환유동층 열교환기의 유동 및 전열성능 예측모텔 연구 (A Study on Prediction Model of Flow and Heat Transfer in the Circulating Fluidized Bed Heat Exchanger with Multiple Vertical Tubes)

  • 박상일
    • 설비공학논문집
    • /
    • 제19권3호
    • /
    • pp.263-268
    • /
    • 2007
  • The pressure drop and heat transfer coefficient were measured at room temperature in a CFB heat exchanger with multiple vertical tubes. The circulation rate of solid particles was also measured. The theoretical model for predicting heat transfer coefficient using the solid flowrate was developed in this study. The model predictions were compared with the measured heat transfer coefficient to show relatively good agreement.

다공성 모델링을 이용한 평행류 열교환기의 열.유동 해석 (Heat and Flow Analysis of a Parallel Flow Heat Exchanger Using Porous Modeling)

  • 정길완;이관수
    • 대한기계학회논문집B
    • /
    • 제25권12호
    • /
    • pp.1784-1792
    • /
    • 2001
  • Numerical analysis on a parallel flow heat exchanger(PFHE) is performed using 2 dimensional turbulent porous modeling. This modeling can consider three-dimensional configuration of passage (flat tube with micro-channels), and the stability and accuracy of numerical results are improved. The geometrical parameters(e.g., the position of separators, inlet/outlet, and porosity of passages of a PFHE) are varied in order to examine the flow and thermal characteristics and flow distribution of the single phase multiple passages system. The flow non-uniformities along the paths of the PFHE are observed to evaluate the thermal performance of the heat exchanger. The location of inlet affects the heat transfer, and the location of outlet affects the pressure drop. The porosity with the optimum thermal performance is around 0.53.

설비공학 분야의 최근 연구 동향 : 2012년 학회지 논문에 대한 종합적 고찰 (Recent Progress in Air-Conditioning and Refrigeration Research : A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2012)

  • 한화택;이대영;김사량;김현정;최종민;박준석;김수민
    • 설비공학논문집
    • /
    • 제25권6호
    • /
    • pp.346-361
    • /
    • 2013
  • This article reviews the papers published in the Korean Journal of Air-Conditioning and Refrigeration Engineering during 2012. It is intended to understand the status of current research in the areas of heating, cooling, ventilation, sanitation, and indoor environments of buildings and plant facilities. The conclusions are as follows : (1) The research works on thermal and fluid engineering have been reviewed as groups of fluid machinery, pipes and valves, fuel cells and power plants, ground-coupled heat pumps, and general heat and mass transfer systems. Research issues are mainly focused on new and renewable energy systems, such as fuel cells, ocean thermal energy conversion power plants, and ground-coupled heat pump systems. (2) Research works on the heat transfer area have been reviewed in the categories of heat transfer characteristics, pool boiling and condensing heat transfer, and industrial heat exchangers. Researches on heat transfer characteristics included the results for natural convection in a square enclosure with two hot circular cylinders, non-uniform grooved tube considering tube expansion, single-tube annular baffle system, broadcasting LED light with ion wind generator, mechanical property and microstructure of SA213 P92 boiler pipe steel, and flat plate using multiple tripping wires. In the area of pool boiling and condensing heat transfer, researches on the design of a micro-channel heat exchanger for a heat pump, numerical simulation of a heat pump evaporator considering the pressure drop in the distributor and capillary tubes, critical heat flux on a thermoexcel-E enhanced surface, and the performance of a fin-and-tube condenser with non-uniform air distribution and different tube types were actively carried out. In the area of industrial heat exchangers, researches on a plate heat exchanger type dehumidifier, fin-tube heat exchanger, an electric circuit transient analogy model in a vertical closed loop ground heat exchanger, heat transfer characteristics of a double skin window for plant factory, a regenerative heat exchanger depending on its porous structure, and various types of plate heat exchangers were performed. (3) In the field of refrigeration, various studies were executed to improve refrigeration system performance, and to evaluate the applicability of alternative refrigerants and new components. Various topics were presented in the area of refrigeration cycle. Research issues mainly focused on the enhancement of the system performance. In the alternative refrigerant area, studies on CO2, R32/R152a mixture, and R1234yf were performed. Studies on the design and performance analysis of various compressors and evaporator were executed. (4) In building mechanical system research fields, twenty-nine studies were conducted to achieve effective design of mechanical systems, and also to maximize the energy efficiency of buildings. The topics of the studies included heating and cooling, HVAC system, ventilation, renewable energy systems, and lighting systems in buildings. New designs and performance tests using numerical methods and experiments provide useful information and key data, which can improve the energy efficiency of buildings. (5) In the fields of the architectural environment, studies for various purposes, such as indoor environment, building energy, and renewable energy were performed. In particular, building energy-related researches and renewable energy systems have been mainly studied, reflecting interests in global climate change, and efforts to reduce building energy consumption by government and architectural specialists. In addition, many researches have been conducted regarding indoor environments.

Effective modelling of borehole solar thermal energy storage systems in high latitudes

  • Janiszewski, Mateusz;Siren, Topias;Uotinen, Lauri;Oosterbaan, Harm;Rinne, Mikael
    • Geomechanics and Engineering
    • /
    • 제16권5호
    • /
    • pp.503-512
    • /
    • 2018
  • Globally there is an increasing need to reduce the greenhouse gas emissions and increase the use of renewable sources of energy. The storage of solar thermal energy is a crucial aspect for implementing the solar energy for space heating in high latitudes, where solar insolation is high in summer and almost negligible in winter when the domestic heating demand is high. To use the solar heating during winter thermal energy storage is required. In this paper, equations representing the single U-tube heat exchanger are implemented in weak form edge elements in COMSOL Multiphysics(R) to speed up the calculation process for modelling of a borehole storage layout. Multiple borehole seasonal solar thermal energy storage scenarios are successfully simulated. After 5 years of operation, the most efficient simulated borehole pattern containing 168 borehole heat exchangers recovers 69% of the stored seasonal thermal energy and provides 971 MWh of thermal energy for heating in winter.