• Title/Summary/Keyword: Liquid desiccant system

Search Result 22, Processing Time 0.029 seconds

Study Characteristics in Packed Tower of Liquid Desiccant Solar Cooling System Using Counter Flow Configuration

  • Rahmanto, R. Hengki;Choi, K.H.;Agung, B.;Sukmaji, I.C.
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2009.11a
    • /
    • pp.168-174
    • /
    • 2009
  • High water vapour content in air can cause a number of problems as for human or surrounding materials. For human a high water vapour can create physiological stress, discomfort, and also can encourage ill health. While, the cause for the environment is can accelerate the corrosion of metals, accelerate the growth of spores and mould, can reduce the electrical resistance of insulators and etc. Desiccant systems have been proposed as energy saving alternatives to vapor compression air conditioning for handling especially the latent load and also sensible load. Use of liquid desiccants offers several design and performance advantages over solid desiccants, especially when solar energy is used for regeneration. The liquid desiccants contact the gas inside the packed tower of liquid desiccant solar cooling system and the heat transfer and mass transfer will occur. This thesis is trying to study the characteristics inside the packed tower of dehumidifier systems. This characteristics consist of mass transfer rate, heat transfers rate, human comfort and energy that consume by the system. Those characteristics were affected by air flow rates, air temperature and humidity, and desiccant temperature and all that variation will influence the performance of the systems. The results of this thesis later on can be used to determine the best performance of the systems.

  • PDF

Experimental Study on Mass Transfer Rate at the Packed Column of Solar Cooling Liquid Desiccant System Using Counter Flow Configuration

  • Hengki R, R.;Choi, K.H.;Yohana, Eflita;Sukmaji, I.C.;Kim, J.R.
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2009.04a
    • /
    • pp.155-161
    • /
    • 2009
  • Desiccant systems have been proposed as energy saving alternatives to vapor compression air conditioning for handling the latent load. Use of liquid desiccants offers several design and performance advantages over solid desiccants, especially when solar energy is used for regeneration. The liquid desiccants contact the gas inside the packed column and the heat transfer and mass transfer will occur. This proposal is try study the mass transfer and heat transfer inside the packed column of dehumidifier and regenerator systems. And later on, the rates of dehumidification and regeneration that were affected by desiccant flow rates, air temperature and humidity, and desiccant temperature and all that variation will influence the performance of the systems.

  • PDF

Study on the Regenerating Performance of Liquid Desiccant in the Cooling/Dehumidification System able to use a Solar Water Heater in Summer(On the Analysis of Source Effect by the Design of Experiments) (여름철 냉방/제습시스템 중 태양열 온수기를 적용할 수 있는 액체흡수제의 재생성능에 관한 연구(실험계획법에 의한 요인효과 분석에 관하여))

  • Choi, K.H.;Kim, B.C.;Kim, B.J.
    • Journal of the Korean Solar Energy Society
    • /
    • v.22 no.1
    • /
    • pp.1-8
    • /
    • 2002
  • With the possibility of hot water being able to be used as a heating source in a liquid desiccant system, an experimental apparatus for regeneration of the liquid desiccant was set up and series of experiments were conducted in a climate-controlled chamber. This study was performed to ascertain the influences of experimental factors on regenerating performance and to suggest the optimal combination of factors affecting regeneration rate. Furthermore. in order to figure out the contribution ratio of the factors on regenerating performance, a multi-way factorial design among the design of experiments was adopted. According to experimental results, the most influential factor on regenerating performance was temperature of the liquid desiccant and its contribution ratio was about 79.4%. In addition. the optimal operating combination was as follows; $60^{\circ}C$ of solution temperature, $14\ell$/min of solution flow rate, and 190m3/h of air volume.

Optimization Design of Liquid Desiccant Cooling System (액체 제습식 냉방 시스템의 최적 설계)

  • Jeon, Dong-Soon;Lee, Sang-Jae;Kim, Seon-Chang;Kim, Young-Lyoul;Lee, Chang-Jun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.22 no.7
    • /
    • pp.419-428
    • /
    • 2010
  • This paper presents the optimization process of liquid desiccant cooling system using LiCl aqueous solution as a working fluid. Operating conditions(mass flow rate, conditioner outlet concentration, difference concentration) and design factors for heat exchangers(difference temperature of the district heating water, leaving temperature difference of the conditioner, leaving temperature difference of the regenerator, air temperature difference of the conditioner, air temperature difference of the regenerator) were optimized by response surface method. As a result, we obtained the 7.297 kW of cooling capacity and 0.788 of COP at optimized condition. Effect of difference temperature of hot water on system performances was also examined. As difference temperature of the district heating water increases, the cooling capacity increases and COP decreases.

Optimization of Liquid Desiccant Cooling Cycle (액체 제습식 냉방 사이클의 최적화)

  • Kim, Seon-Chang;Kim, Young-Lyoul;Lee, Sang-Jae;Jeon, Dong-Soon;Choi, Jaug-Hyeon;Kwon, Hyeok-Min;Lee, Chang-Jun
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.673-678
    • /
    • 2009
  • This paper presents the optimization process of liquid desiccant cooling cycle using LiCl aqueous solution as a working fluid. Operating conditions and design factors for heat exchangers were optimized by response surface method. As a result, we obtained the 7.297 kW of cooling capacity and 0.788 of COP at optimized condition. Effect of $dT_{hw}$ on system performances was also examined. As $dT_{hw}$ increases, the cooling capacity increases and COP decreases.

  • PDF

Research on the Performance of a Solar Air Conditioning System using a Liquid Desiccant in Summer (액체흡수제 이용 태양열 공조시스템의 하계 능력에 관한 연구)

  • Choi, K.H.;Yoon, J.I.;Kim, B.C.
    • Journal of the Korean Solar Energy Society
    • /
    • v.22 no.2
    • /
    • pp.33-38
    • /
    • 2002
  • In order to find out whether solar air conditioning system could be applied to building or not, the performance and evaluation on thermal environment of the system suggested was done during summer. A solar model house was constructed to find out the performance and thermal environment evaluation when it actually operated outside. As a result, regeneration rate increased rapidly when LiCl solution temperature was over $50^{\circ}C$ and the regeneration rate was $13\sim15kg$ during 9 hours operation. Furthermore the dehumidification rate was 12kg at maximum during 10 hours operating of a dehumidifier and indoor temperature and relative humidity was $28.4^{\circ}C$ and 39.1% in average respectively. On evaluation of thermal environment during summer, PMV value was slightly high, but thermal sensation vote was 71% within the comfort zone.

Experimental Study for Estimation of Air Heating Performance and Improvement of Thermal Performance of Hybrid Solar Air-water Heater (태양열 공기-물 가열기의 공기 가열 성능 평가 및 열적 성능 개선을 위한 실험적 연구)

  • Choi, Hwi-Ung;Kim, Young-Bok;Yoon, Jung-In;Son, Chang-Hyo;Choi, Kwang-Hwan
    • Journal of the Korean Solar Energy Society
    • /
    • v.37 no.1
    • /
    • pp.47-57
    • /
    • 2017
  • Solar energy is one of the important renewable energy resources. It can be used for air heating, hot water supply, heat source of desiccant cooling system and so on. And many researches for enhancing efficiency have been conducted because of these various uses of solar thermal energy. This study was performed to investigate the air heating performance of hybrid solar air-water heater that can heat air and liquid respectively or simultaneously and finding method for improving thermal performance of this collector. This collector has both liquid pipe and air channel different with the traditional solar water and air heater. Fins were installed in the air channel for enhancing the air heating performance of collector. Also air inlet & outlet temperature, ambient temperature and solar collector's inner part temperature were confirmed with different air velocity on similar solar irradiance. As a result, temperature of heated air was shown about $43^{\circ}C$ to $60^{\circ}C$ on the $30^{\circ}C$ of ambient temperature and thermal efficiency of solar collector was shown 28% to 73% with respect to air velocity. Also, possibility of improvement of thermal performance of this collector could be ascertained from the heat transfer coefficient calculated from this experiment. Thus, it is considered that the research for finding optimal structure of hybrid solar air-water heater for enhancing thermal performance might be needed to conduct as further study based on the method for improving air heating performance confirmed in this study.

Development on the Sub-Cooled Hybrid Condenser in Automotive Air-Conditioning System (자동차 냉방시스템에서 건조기 일체형 응축기 개발)

  • 김경훈;장주섭;박종일
    • Transactions of the Korean Society of Automotive Engineers
    • /
    • v.11 no.5
    • /
    • pp.70-76
    • /
    • 2003
  • An experimental study was performed to understand the heat transfer and fluid dynamic characteristics of Sub-Cooled Hybrid Condenser (SCHC), which conventional condenser and receiver dryer are integrated into. SCHC also employs a sub-cooled refrigerant passages at the end of the condenser in order to supply perfect liquid refrigerant to the expansion unit. Throughout the present study, it was found that the developed SCHC increases in the degree of sub-cooling by 10~100% compared to conventional condenser. The excessive sub-cooling has improved the cooling performance by 10%, and that leads reduction in evaporator outlet air temperature by $1.5^{\circ}C$. Also found through the study is that the refrigerant pressure drop across SCHC is fairly increased due to insertion of the desiccant cartridge in the receiver tank which is composed of zeolite, filter and supporter plate.

Experimental Study on Heat and Mass transfer Coefficient Comparison Between Counterflow Types and Parallel in Packed Tower of Dehumidification System

  • Sukmaji, I.C.;Choi, K.H.;Yohana, Eflita;Hengki R, R.;Kim, J.R.
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2009.04a
    • /
    • pp.162-169
    • /
    • 2009
  • In summer electrical energy is consumed in very high rate. It is used to operate conventional air conditioning system. Hot and humid air can germinate mould spores, encourage ill health, and create physiological stress (discomfort). Dehumidifier solar cooling effect is the one alternative solution saving electrical energy. We use surplus heat energy in the summer, to get cooling effect and then to get human reach to comfort condition. These devices have two system, dehumidifier and regeneration system. This paper will be focus in dehumidifier system. Dehumidifier system use for absorbing moisture in the air and decreasing air temperature. When the liquid desiccant as strong solution contact with the vapor air in the packed tower, it works. The heat and mass transfer performances of flow pattern in the packed tower of dehumidifier are analyzed and compared in detail. In this experiment was introduced, the flow patterns are parallel flow and counter flow. The performance of these flow patterns will calculate from air side. Which is the best flow pattern that gave huge mass transfer rate? The proposed dehumidifier flow pattern will be helpful in the design and optimization of the dehumidifier solar cooling system.

  • PDF