• 제목/요약/키워드: Limiting MCCB

검색결과 5건 처리시간 0.024초

전자기력의 영향을 포함한 MCCB 기구부의 동역학적 모델링 방법 연구 (Study on the Dynamic Modeling of a MCCB Mechanism Including Electro-Magnetic Force Effect)

  • 강경록;유홍희
    • 대한기계학회논문집A
    • /
    • 제25권3호
    • /
    • pp.362-368
    • /
    • 2001
  • To design a limiting MCCB (Molded Case Circuit Breaker) mechanism, a dynamic modeling of the mechanism in which the electro-magnetic force effects are incorporated needs to be developed. Conventionally, electro-magnetic effects were considered separately for the design of the mechanism. In this paper, an electro-magnetic force that is induced by limited current is identified and included in the dynamic modeling of the mechanism. Thus, the electro-magnetic which is defined as a external force and the mechanical effects are simultaneously considered for the design of the mechanism which is composed of contactor, spring , link, latch and so on.

차단성능 평가해석기법을 적용한 강자계 구동방식의 460[V]/225[A]/50[kA]급 한류형 MCCB 소호부 개발 (Development of 460[V]/225[A]/50[kA] Contact System in Current Limiting MCCB using an estimation and analysis method for the interrupting capability)

  • 최영길;박찬교
    • 조명전기설비학회논문지
    • /
    • 제18권1호
    • /
    • pp.78-84
    • /
    • 2004
  • 배선용 차단기(MCCB)는 신속한 고장전류 차단과 전원시스템의 안정성을 확보하기 위해 배선시스템에 폭넓게 사용되고 있다. 본 논문에서는 MCCB의 소호부 형상에 따른 차단성능을 파악하고 이를 통해 성능향상을 꾀하고자 3차원 자계해석을 이용한 차단성능 평가해석기법을 개발하고, 개발한 평가해석기법을 각 모델 차단기에 적용한 바를 기술하였다. 또한, 소호부내 아크런너의 형상을 불연속 통전경로로 구성하여 차단성능에 미치는 영향을 살펴보았다. 이상의 연구내용을 토대로 새로운 소호부 형상을 고안하여 국내 최초로 460 [V]/225 [A]/50 [kA] 대전력 단락시험에 성공한 결과를 제시하였다.

2중 한류 구조를 갖는 배선용 차단기의 차단성능 평가 연구 (A Study on Estimation of Interrupting capability on Molded Case Circuit Breaker including Current Limiting Unit)

  • 김용기;송중천;서정민
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 추계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.144-146
    • /
    • 2002
  • The latest development flow of MCCB(Molded Case Circuit Breaker) is largely separated from which are high capability of interrupting compact of size and multi-ability in functions. As follow of development of industrial system. MCCB which are including communication function and having a ultimate interrupting capability is required in electrical system. to attain an effective limitation of the peak let-through current and the let-through energy, the arc has to move rapidly off the contacts and has to increase the arc voltage which mainly effect to interrupt. In this paper. we made high performance circuit breaker which including current limiting unit which is attached to the main which is simulated by CAE tool that are repulsion force and mechanical dynamics after that we tested and finally selected optimized for circuit breaker.

  • PDF

Development of 460V/225A/50㎄ Contact System in Current Limiting Molded Case Circuit Breakers

  • Park, Young-Kil;Park, Chan-Kyo
    • KIEE International Transaction on Electrical Machinery and Energy Conversion Systems
    • /
    • 제3B권4호
    • /
    • pp.165-172
    • /
    • 2003
  • Low voltage circuit breakers are widely used in power distribution systems to interrupt fault current rapidly and to assure the reliability of the power supply. This paper is focused on understanding the interrupting capability, more specifically of the contacts and the arc runner, based on the shape of the contact system in the current molded case circuit breaker (hereafter MCCB). Moreover, in order to improve the interrupting capability of the circuit breaker, the estimation and analysis of the interrupting capability, based on the 3-D magnetic flux analysis, were developed. Furthermore, this paper also presents results of the estimation and analysis of the interrupting capability when applied to different model breakers. In addition, this paper analyzes the efficiency of the interrupting tests by forming false current paths consisting of a three-division cascade arc runner in the contact system. With regards to the interrupting test, there is a need to assure that the optimum design required to analyze the electromagnetic forces of the contact system generated by the current and flux density be present. Based on the results of this study, this paper presents both computational analysis and test results for the newly developed MCCB 460V/225A/50㎄ contact system.

3D FEM해석을 통한 배선용 차단기의 가동자 거동해석 (Dynamic Motion Analysis of a Moving Contact by Electromagnetic Repulsion Force in MCCB)

  • 송중천;김용기;유만종;서정민
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 B
    • /
    • pp.786-789
    • /
    • 2002
  • The behaviour of contactors protected by arcs under short-circuit currents is analysed using a simple model to represent the electric circuit and the contactor. In most cases, the protection of contactors against short-circuit currents is entrusted to fuses. Fuses are suitable for preventing excessive damage to the contactor, or parts of the contactor, under short-circuit conditions. In particular, they are capable of limiting the thermal and electrodynamic stresses which can lead to arcing or welding together of the contacts of a contactor. This paper is the Dynamic Motion Analysis of a Moving Contact by Electromagnetic Repulsion Force in Molded Case Circuit Breaker(MCCB)

  • PDF