• Title/Summary/Keyword: Lightning protection system

Search Result 134, Processing Time 0.029 seconds

Lightning Risk Assessment for Structures Lower than 20m High (높이 20미터 미만인 구조물의 낙뢰리스크 평가)

  • Lee, Ju-Chul;Kim, Gi-Hyun;Lee, Young-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.12
    • /
    • pp.21-27
    • /
    • 2012
  • Korean Industrial Standards for lightning protection system complies with IEC standards. However, the standards are applicable only to buildings and structures more than 20 meters in high. Therefore, it is necessary to determine whether lightning protection system should be installed on structures lower than 20 meters high. This paper proposes an efficient method of assessing risk against lightning of structures lower than 20 meters high. The method suggests simplified lightning protection system and provides selecting an appropriate protection level. The suggested method assumes that structure under assessment has no lightning protection system and there is no person around the structure at the moment of lightning stroke. A simplified method of assessing the risk to human within the structure is developed by adopting the general assessment factor. The selection of a protection level is possible by comparing tolerable risk with physical damage risk caused by a direct lightning. Finally, this paper gives ways to establish surge protection measures when a structure with lightning risk is within a radius of 2km from the assessed structure even if this structure requires no lightning protection system.

Construction of Lightning Protection System for Railway Signaling Equipments (철도신호설비용 낙뢰방호장치의 건설)

  • Choi Kyu-Hyoung;Seo Seok-Chul;Choi Se-Wan
    • Proceedings of the KSR Conference
    • /
    • 2004.10a
    • /
    • pp.1193-1198
    • /
    • 2004
  • This paper describes the lightning protection system for railway signaling equipments installed at subway car depots in Seoul metropolitan Rapid Transit Cooperation. Several measures for improving lightning protection performance are adopted; newly organized grounding system for neutral line of power system, rolling method to minimize damages induced by direct lightning strike, new measures to reduce voltage differences between the signaling equipments and the ground, and improvement of grounding system. The proposed system has greatly reduced the grounding resistance and also the voltage difference between the signaling equipments and the ground, and has prevented the accident related with lightning surges since it was installed. The proposed approach can be viewed as a useful alternative of dealing with lightning protection for railway signaling equipments.

  • PDF

Statistics on the Present Status of Installations of Non-conventional Lightning Rods (일반형이 아닌 피뢰침의 설치 실태에 대한 통계적 조사)

  • Lee, Bok-Hee;Lee, Seok-Yeon;Lee, Su-Bong;Baek, Young-Hwan;Lee, Kyu-Sun;Kim, Dong-Sung
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2006.05a
    • /
    • pp.347-350
    • /
    • 2006
  • The conception of early streamers is in sufficient and inadequate as a parameter for the determination of any advantage of early streamer emission(ESE) lightning rods versus ordinary lightning rods. Thus, standards for many other national and international lightning protection as well as KS C IEC 61024-1 do not take ESE lightning rods, charge dissipation systems or non-conventional lightning rods. Unfortunately, many non-conventional lightning rods such as ESE lightning rods and charge dissipation systems in Korea are increasingly used in lightning protection of structures including explosive manufacturing buildings, electric generating, transmission and distribution systems. This study attempts to make aware of no advantage of ESE rods and other non-conventional lightning protection systems and to investigate the present status of installations of ESE lightning rods.

  • PDF

Review about the Lightning Protection System for Ground Facilities of Anti-aircraft Weapons System (뇌 보호시스템의 대공무기체계 지상시설 적용에 대한 고찰)

  • Jung, Kyoungwook;Shim, Donghyouk;Son, Donghyeop
    • Journal of the Korea Institute of Military Science and Technology
    • /
    • v.24 no.3
    • /
    • pp.339-347
    • /
    • 2021
  • Recently, the incidence of lightning in Korea has been increasing more and more. The damage caused by lightning is also getting worse. Lightning protection system is a prerequisite, not a sufficient condition. Considering the characteristics of lightning, there is a high frequency of lightning strikes in highlands. So, high grades of LPS should be applied to ground facilities of anti-aircraft weapons systems. 4-Level LPS was applied on groung facilities of anti-aircraft weapons system based on lightning incidence rate in past. There are some possibilities of damage from lightning in anti-aircraft weapons system. So, we have to readjust the LPS level with grounding, lightning rods and surge protect device based on lightning incidence rate in now days. Propose 2-level LPS and design with lightning rods, surge protector, separated grounding in this paper.

Protection Design and Lightning Zone Analysis for Unmanned Aerial Vehicle with Composite Wings (복합재 주익 무인항공기의 낙뢰보호 설계와 피격영역 해석)

  • Hee-chae Woo;Yong-Tae Kim
    • Journal of the Korea Institute of Military Science and Technology
    • /
    • v.26 no.3
    • /
    • pp.302-312
    • /
    • 2023
  • This paper describes the analysis of lightning strike zoning, the indirect lightning data simulation and the protection design for lightning indirect effects of equipment by lightning strike for unmanned aircraft consisting of composite wings. Through the analysis of lightning strike zoning according to the external shape of unmanned aerial vehicles, the structure areas that should be protected during lightning strike is derived, and the protection requirements of lightning indirect effects for flight critical equipments and equipment that must be operated upon lightning strike was derived. Lightning protection levels according to the location of mounting equipment and surrounding structure materials for each equipment was derived, and the protection design of the unmanned aerial vehicle with composite structures was also proposed from direct effect of lightning. Later, the lightning protection technology will be verified by the ground test of lightning direct and indirect effects.

A Study on the Effective Surge Protection Method from Induced Lightning Surgeto Improve Isolate Grounding to Common Grounding (낙뢰 Surge 방호를 위한, 독립접지를 공통접지로 개선하는 효율적인 방법에 대한 연구)

  • Jeon, Hyung-Gu;Woo, Jea-Wook;Suh, Yong-Joon
    • Proceedings of the KSR Conference
    • /
    • 2011.10a
    • /
    • pp.1459-1467
    • /
    • 2011
  • This paper proposes the effective method to improve the protection from induced lightning Surge by making common grounding from individual grounding. Common grounding under equipotential principle is more effective than individual grounding for lightning Surge protection, and so common grounding is indicated as international technical standard under the AC power supply system with neutral line. So, this paper is to propose the effective way of induced lightning Surge protection method for currently installed power supply system which has no neutral grounded line and individual grounding which are weak for lightning Surge protection. This proposal can improve the power supply system as has neutral line, and improve the grounding system to common grounding system. And also this paper proposes to make effective equipotential system with voltage variable shunting devices for lightning Surge protection.

  • PDF

A Study on the Effective Surge Protection Method from Induced Lightning Surge to Improve Isolate Grounding to Common Grounding (낙뢰 Surge 방호를 위한, 독립접지를 공통접지로 개선하는 효율적인 방법에 대한 연구)

  • Woo, Jea-Wook
    • Proceedings of the Korean Institute of Navigation and Port Research Conference
    • /
    • 2013.10a
    • /
    • pp.215-218
    • /
    • 2013
  • This paper proposes the effective method to improve the protection from induced lightning surge by making common grounding from individual grounding. Common grounding under equipotential principle is more effective than individual grounding for lightning surge protection, and so common grounding is indicated as international technical standard under the AC power supply system with neutral line. So, this paper is to propose the effective way of induced lightning surge protection method for currently installed power supply system which has no neutral grounded line and individual grounding which are weak for lightning surge protection. This proposal can improve the power supply system as has neutral line, and improve the grounding system to common grounding system. And also this paper proposes to make effective equipotential system with voltage variable shunting devices for lightning surge protection.

  • PDF

An Application Method and Review of Lightning Protection for Wind Turbines (풍력발전기의 낙뢰피해 대책 검토 및 적용방안)

  • Han, Ji-Hoon;Ko, Kyung-Nam;Huh, Jong-Chul
    • Journal of Power System Engineering
    • /
    • v.19 no.2
    • /
    • pp.5-14
    • /
    • 2015
  • This investigation presents reviews of many research results on lightning damage to wind turbines and lightning protection strategies from IEC Standard, Europe, USA, Japan and Korea. There have been few studies on lightning protection of wind turbines in Korea, while various investigations have been performed in the other countries. It is necessary to apply some good lightning protection strategies of IEC Standard and the other countries to Korea. Those are as follows: The guideline for lightning protection of wind turbines should be established based on IEC Standards. It needs to be carried out both development of software and experimental studies for understanding the types of lightning damage to wind turbines and compiling the database. In order to minimize the lightning damage to wind turbines, it is a key factor for wind farm owners and researchers to provide the information about the damage cases and wind farm operation technique.

Applicability of Messenger Wire for Purpose of Lightning Protection

  • Seo, Hun Chul;Han, Joon;Choi, Sun Kyu;Lee, Byung Sung;Rhee, Sang Bong;Kim, Chul Hwan
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.1
    • /
    • pp.167-174
    • /
    • 2016
  • The Korean distribution line currently consists of overhead ground wires (OHGW), overhead distribution lines, neutral wires (NW), and messenger wires (MW). The MW is installed under the NW. The lightning protection system in Korea is focused on OHGW and lightning arrester and the MW are not considered. Therefore, this paper proposes the applicability of MW for purpose of lightning protection. For this, we analyzed the effects of lightning overvoltage according to the existence of OHGW and MW and the grounding conditions of the MW in the Korean distribution system. The grounding conditions of the MW that we took into consideration were the common or separate grounding of the MW and NW. The analysis based on the equivalent circuit of the distribution pole at each condition was performed. The distribution lines and lightning were modeled using the Electromagnetic Transients Program (EMTP). For each of the installation conditions of the OHGW and MW, the various lightning conditions were simulated and analyzed for both direct and indirect lightning. The simulation results showed that, if the OHGW was not installed in the Korean distribution system, the lightning overvoltage could be reduced by the common grounding of the MW and NW.

Design and Fabrication of High Frequency Ground Impedance Measuring System for Assessment of Grounding System for Lightning Protection (낙뢰 보호용 접지시스템 평가를 위한 고주파 접지임피던스 측정시스템의 설계 및 제작)

  • Gil, Hyoung-Jun;Shong, Kil-Mok;Kim, Young-Seok;Kim, Chong-Min;Kim, Young-Jin
    • Journal of the Korean Society of Safety
    • /
    • v.31 no.3
    • /
    • pp.47-52
    • /
    • 2016
  • This paper describes the design and fabrication of high frequency ground impedance measuring system for assessment of grounding system for Lightning protection. The ground impedance measuring system has been designed and fabricated which makes it possible to assess the ground impedance by frequency ranges from 100 Hz to 1 MHz. The effective grounding systems having a very low impedance to electromagnetic disturbance such as lightning surges and noises in microelectronics and high-technology branches are strongly required. In order to analyze the dynamic characteristic of grounding system impedances in lightning and surge protection grounding systems, it is highly desirable to assess the ground impedances as a measure of performance of grounding system in which lightning and switching surge currents with fast rise time and high frequency flow. The measuring system is based on the variable frequency power supply and consists of signal circuit part, main control part, data acquisition and processing unit, and voltage and current probe system. The ground impedance measuring system can be used to assess grounding system during occurrence of lightning.