• Title/Summary/Keyword: Lightning performance

Search Result 154, Processing Time 0.027 seconds

A study on the Unbalanced Insulation of the Double Circuit 154 kV Transmission Lines to Reduce Lightning Failure Rate (뇌사고율 저감을 위한 154 kV 송전선의 차등절연 적용 방안 연구)

  • Kwak, J.S.;Kang, Y.W.;Woo, J.W.;Shim, E.B.;Kim, W.G.
    • Proceedings of the KIEE Conference
    • /
    • 2003.10a
    • /
    • pp.151-159
    • /
    • 2003
  • According to the records, approximately 50 percent of power failure were caused by lightning. Conventional fault preventive measures against lightning include reduction of the footing resistance of the tower, multiplication of overhead ground wires and unbalanced insulation of the double circuit transmission tower. In addition to these, transmission line arresters have been recently appeared as an alternatives. In this paper an unbalanced insulation method with transmission line arrester was assumed as another countermeasure against simultaneous double circuit trip of 154 kV transmission line by lightning strike. The lightning performance of line arrester was compared with conventional insulation concept using different numbers of porcelain and glass insulator. Larger numbers of insulator simply increase flashover current level by lightning but the lightning performance doesn't proportional to it. EMTP simulation and predictive calculation of lightning failure rate were carried out to evaluate the performance.

  • PDF

Performance Evaluation of Early Streamer Emission Lightning Air Terminal

  • Choi, Sang-Won;Her, Yong
    • International Journal of Safety
    • /
    • v.5 no.2
    • /
    • pp.18-23
    • /
    • 2006
  • Studies have claimed that ESE (Early Streamer Emission) air terminals offer a vastly increased zone of protection over that of traditional lightning rods (Franklin rods) by causing the emission of an upward streamer/leader: The upward streamer/leader will propagate towards the tip of the downward leader at an early stage in the attachment process.. This paper shows the results of a performance evaluation test of a particular type of the ESE air terminal (called "ElecHippo") with a simple rod tested at the Korea Electrotechnology Research Institute (KERI). The corona emission current of the ElecHippo made by Yong-Jin Enterprise Corp. has also been measured at the Occupational Safety & Health Research Institute (OSHRI). The results show that the ElecHippo meets the French standard of NFC 17-102-1995. The results also verify the ESE performance by measuring the ion emission current generated in the discharge electrode gap as a function of the capacitance and inductance of the equipped devices. Finally, we propose a new method for grounding the system to reduce the lightning damage by combining the ESE air terminal, the early discharge earth plate, the lightning strike recorder and the surge protection device.

Study on Enhancing Lightning Protection Scheme of Catenary in Subway Viaduct Section

  • Li, Rui-Fang;Chen, Kui;Chen, Li-Sheng;Cao, Xiao-Bin;Wu, Guang-Ning;Zhang, Xue-Qin
    • Journal of Electrical Engineering and Technology
    • /
    • v.12 no.2
    • /
    • pp.950-958
    • /
    • 2017
  • Viaduct increases the height of subway catenary, namely magnifies lightning attraction scope that lead to higher possibility of suffering lightning stroke. Therefore, it is necessary to analyze performance of lightning striking to catenary of subway in viaduct section and propose an improving lightning protection scheme. In this paper, using ATP-EMTP simulation software to establish an associated model to evaluate lightning withstand level of catenary with existing lightning protection schemes including arrester and grounding point, an improving lightning protection scheme is proposed - every pillar ground earth and arresters are installed with some installing spacing between 200m to 400m based on lightning damage degree and reliability requirements - according to analyzing results: while lightning withstand level is lowest for lightning striking to the neutral pillar, lightning withstand level is greatest for lightning striking to the both-ends pillar that arrester and grounding point are both installed; grounding point could obviously improve lightning withstand level for lightning striking to ground wire while arrester could obviously improve the lightning withstand level for lightning striking to catenary; every pillar ground earth could enhance the lowest lightning withstanding level up to 2.5 times than of that pillar ground earth across every 200m.

Analysis on Lightning Overvoltage According to Lead Length of Surge Arrester for Underground Cable Outdoor Termination Protection at C/H Tower (C/H 철탑 종단접속함 보호용 피뢰기 리드선 길이에 따른 뇌과전압 분석)

  • Jung, Chae-Kyun;Kang, Ji-Won
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.2
    • /
    • pp.257-263
    • /
    • 2016
  • This paper describes the lightning arrester transients in cable head termination. The installation references of cable head tower and lightning arresters are firstly reviewed, then the performance of lightning arrester operation is also evaluated based on lightning overvoltage analysis by the change of grounding lead cable length. This paper finally proposes the optimal length of grounding lead cable at the cable head termination. The limited lightning current is also proposed according to the change of grounding lead cable length. The results will contribute to protecting insulation breakdown failure against lightning surge at the terminations and joints.

An Analysis of Performance Testing for Metallic Connection Components of Lightning Protection System (피뢰시스템 구성부품 중 금속접속재의 성능시험 및 결과분석)

  • Lee, Ju-Cheol;Lee, An-Ki;Kim, Jae-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.7
    • /
    • pp.69-74
    • /
    • 2014
  • Recently, IEC published new standards about the requirements and tests for lightning protection system(LPS) components. If components are used for LPS, they should comply with the IEC standards. This paper, we collected six specimens for the metallic connection components using in domestic, and it tested for withstand lightning current which according to the IEC 62561-1. As a result, only one specimen meet this performance requirement. The specimen is the metallic connection component with four bolts fixed. Therefor, when designing of LPS in domestic, the metallic connection components shall be taken into account for the selection of the withstand lightning current. In addition, we need to develop for LPS components product and the national standards.

Construction of Lightning Protection System for Railway Signaling Equipments (철도신호설비용 낙뢰방호장치의 건설)

  • Choi Kyu-Hyoung;Seo Seok-Chul;Choi Se-Wan
    • Proceedings of the KSR Conference
    • /
    • 2004.10a
    • /
    • pp.1193-1198
    • /
    • 2004
  • This paper describes the lightning protection system for railway signaling equipments installed at subway car depots in Seoul metropolitan Rapid Transit Cooperation. Several measures for improving lightning protection performance are adopted; newly organized grounding system for neutral line of power system, rolling method to minimize damages induced by direct lightning strike, new measures to reduce voltage differences between the signaling equipments and the ground, and improvement of grounding system. The proposed system has greatly reduced the grounding resistance and also the voltage difference between the signaling equipments and the ground, and has prevented the accident related with lightning surges since it was installed. The proposed approach can be viewed as a useful alternative of dealing with lightning protection for railway signaling equipments.

  • PDF

Insulation Design of Distribution Systems in Case of the Stroke of Direct Lightning Surge (직격뢰 침입시 배전계통 절연설계)

  • 정채균;김상국;이종범;서재호
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.4
    • /
    • pp.238-247
    • /
    • 2004
  • This paper describes the insulation coordination scheme of line in distribution system when the direct lightning surge strikes. The BIL that is applied to distribution system is not properly considered the performance and operation of arresters. Because of that, the high BIL is being used at partial system. This paper variously analyses the lightning overvoltage of line and equipment with earth of overhead grounding wire and installation types of arrester. From these result. authors examine the rationality of BIL.

Insulation Design Standards for Protection of Power System against Lightning in Korea Electric Power Corporation (낙뢰로부터 전력설비 보호를 위한 한전의 절연설계 기준)

  • Woo, J.W.;Moon, J.D.
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.12
    • /
    • pp.555-560
    • /
    • 2006
  • As it has been reported that more than 60% of transmission line faults occurs due to lightning strokes, lighting is one of concerned issues in electric power utility company. Most of transmission line is double circuit in Korea. Double circuit outages account for 33.7 percent of total lightning faults from 1996 to 2004. Even though transmission fault might be cleared shortly by protective system, it could deteriorate the power quality accompanied with sag or flicker. Moreover, double circuit fault may lead to more aggravated situation, for instance, blackout. To Protect transmission lines from lightning stroke, reduction of tower footing resistance, multiple ground wires and unbalanced insulation in double circuit lines have been adopted. In this paper, we would like to introduce insulation design standards for lightning protection of Korea Electric Power Corporation.

A Protection Technique Against the Damages Caused by Lightning Surges on Information and Communication Facilities

  • Lee, Bok-Hee;Kang, Sung-Man;Ahn, Chang-Hwan
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.3C no.4
    • /
    • pp.117-122
    • /
    • 2003
  • The AC power lines and signal lines of info-communication networks are routed on overhead poles and are highly exposed to lightning strikes. Due to the potential difference between grounding points of AC power lines and signal lines, the electronic equipments connected to the signal lines can easily be damaged by lightning surges. In this work, in order to develop reliable methods of protecting information and communication facilities from lightning surges, the reliability and performance of SPDs (surge protective devices) were experimentally investigated in an actual-sized test circuit. The behaviors of SPDs against lightning surges from AC power lines and signal lines and the coordinated effects of SPD installation methods were evaluated. As a consequence, it was confirmed that the bypass arrester methods and common grounding system are both highly effective.

Development of Ground Impedance Measuring Instrument for Lightning Protection System (뇌보호 설비를 위한 접지임피던스 측정기 개발)

  • Lee, Tae-Hyung;Cha, Sung-Chul;Earn, Ju-Hang
    • Proceedings of the KIEE Conference
    • /
    • 2006.10a
    • /
    • pp.194-195
    • /
    • 2006
  • This study evaluated the impedance characteristics of earth termination system and developed a variable frequency-typed inverter (measuring tool) for the utilization in ground design for lightning protection. The variable-frequency-typed inverter were composed of rectification part, voltage adjuster, IGBT controller and measuring part. Meanwhile, the square wave signal of variable frequency converted its frequency up to lightning surge band by using an IGBT after rectifying an alternating current (AC). It conducted performance evaluation of ground impedance of actual earth termination system by using the developed measuring tool for ground impedance and confirmed that such impedance-oriented performance evaluation was effective in the design of lightning protection.

  • PDF