• Title/Summary/Keyword: Lightening arrester

Search Result 6, Processing Time 0.022 seconds

A Study on the Dielectric Properties of Lightening Arrester used for Distribution Line (배전용 피뢰기의 유전특성에 관한 연구)

  • Kim, Chan-Young;Kim, Ju-Yong;Song, Il-Keun;Lee, Byoung-Sun;Han, Yong-Heui
    • Proceedings of the KIEE Conference
    • /
    • 1999.07d
    • /
    • pp.1642-1644
    • /
    • 1999
  • This paper provides the results of dielectric properties for aged or controlled lightening arresters. The aged lightening arresters were used for five years in distribution line. The leakage current of lightening arresters and elements was measured to confirm whether the lightening arrester was deteriorated or not. The microstructure was also investigated to determine the size of grain and grain boundary. The dielectric properties of aged lightening arresters were compared to those of controlled lightening arresters. The dielectric constant and the tan${\delta}$ of aged lightening arrester were larger than those of controlled one, resulting from accelerated aging due to the thin grain boundary.

  • PDF

Characteristic Analysis of Distribution Lighten ins Arrester Failed in the Field (현장 고장난 배전용 피뢰기의 특성분석)

  • 김찬영;김주용;송일근;이병성;한재홍;윤태상
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.07a
    • /
    • pp.687-690
    • /
    • 2000
  • This paper provides the result of the analysis of the lightening arresters which were disconnected from the power line due to the overvoltage having high current. The effect of thermal runaway on the microstructures of lightening arrester's block was intensively investigated. The chance of the microstructures of the blocks was limited only on the breakdown paths and near them. Also even though a disconnector was disconnected from the arrester, some of the lightening arrester were showed normal characteristics.

  • PDF

The Study on the Aging Characteristics of the Arrester Block(ZnO) (피뢰기 소자(ZnO)의 열화특성에 관한 연구)

  • Kim, Chan-Young;Song, Il-Keun;Kim, Ju-Yong;Jeoung, Nyeon-Ho
    • Proceedings of the KIEE Conference
    • /
    • 1998.07d
    • /
    • pp.1459-1461
    • /
    • 1998
  • This paper provides the results of analysis of lightening arrester failed in the field. XRD was used for qualitative analysis and SEM for microstructure analysis of zinc oxide (ZnO) block. The failure of lightening arrester might occur due to the following reasons: the uneven size of zinc oxide grains and cement layers. the re-crystallization of zinc oxide grains resulting from electrical stress around impurities, and the presence of too large pores($\simeq$ 50 ${\mu}m$).

  • PDF

Development of Lightning Arrester Degradation Monitoring System Using ZCT (ZCT틀 이용한 피뢰기 열화 감시 시스템 개발)

  • Park, J.N.;Lee, Y.H.;Jang, S.H.;Kim, P.S.;Shin, Y.S.;Kim, Y.G.;Seo, J.M.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1626-1628
    • /
    • 2003
  • The lightning arrester is a very important overvoltage protection device in the electric power system. Therefore, the inspection of lightning arrester whether it keeps its performance or not properly has close related to verifying the safety confidence of the electric power system. But the development of the deterioration measuring method and on-line detecting system, is necessary to monitor the deterioration of the lightening arrestor. In this paper, we developed the lightning arrester degradation monitoring system. This system detected leakage current of lightning arrester by using the ZCT, and analyze the third harmonics ingredient of leakage current using DFT method in the Data Acquisition Unit(DAU). The analyzed current signal is transmit to the Human-Machine Interface(HMI), and HMI alarmed when accident are occurred and informed with the amplitude of leakage current to the operator.

  • PDF

Study on insulation coordination of 154KV solidly grounded system (154KV계 직접접지시의 절연협조)

  • 신대승
    • 전기의세계
    • /
    • v.17 no.3
    • /
    • pp.57-61
    • /
    • 1968
  • Limitation to Peterson coil grounded operation of 154KV system began to develop with the growth of system as to voltage and system cost. Therefore, 154KV system is going to be grounded solidly from November this year. This study shows the insulation coordination of solidly ground system, such as the selection of a suitable lightening arrester, determination of transmission line insulation and Basic Insulation Level of station equipment.

  • PDF

Impulse Characteristics of MOV Elements for Railroad Vehicle Arrester (전철 탑재 피뢰기용 MOV 소자 임펄스 특성)

  • Han, S.W.;Cho, H.G.;Lee, H.G.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07d
    • /
    • pp.1529-1531
    • /
    • 1999
  • The main functions of AC railroad vehicles arresters is to protect the main transformer from lightening impulse or switching impulse surge, then the MOV(metal oxide varistor) elements rated of 10kA is applied. The residual voltage and surge energy absorption are important parameters in designing arrester, these must be carefully decided with considering protecting level of impulse environment of system. The purpose of this study is to discuss the residual voltages and the energy absorption capability by impulse currents on MOV elements for railroad vehicles, and to introduce design factors which act as optimal protecting condition against impulse currents.

  • PDF