• 제목/요약/키워드: Large blackouts

검색결과 8건 처리시간 0.025초

Sequential Outage Checkers for Analyzing Cascading Outages and Preventing Large Blackouts

  • Hur, Jin;Joung, Man-Ho;Baldick, Ross
    • Journal of Electrical Engineering and Technology
    • /
    • 제6권5호
    • /
    • pp.585-594
    • /
    • 2011
  • This paper presents the use of sequential outage checkers to identify the potential cascading processes that might lead to large blackouts. In order to analyze cascading outages caused by a combination of thermal overloads, low voltages, and under-frequencies following an initial disturbance, sequential outage checkers are proposed. The proposed sequential outage checkers are verified using the AEP 9-bus system, New England 39-bus system, and IEEE 118-bus system.

확률론적 연쇄사고 분석을 위한 시각화 모형 개발 (Development of Visualization Model for Probabilistic Analysis of Cascading Failure Risks)

  • 최영도;백자현;김태균;전동훈;윤기갑;박상호;구보경;허진
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제4권1호
    • /
    • pp.13-17
    • /
    • 2018
  • According to the recent blackouts, large blackouts can be described by cascading outages. Cascading outage is defined by sequential outages from an initial disturbance. Sequential and probabilistic approach are necessary to minimize the blackout damage caused by cascading outages. In addition, conventional cascading outage analysis models are computationally complex and have time constraints, it is necessary to develop the new analytical techniques. In this paper, we propose the advance visualization model for probabilistic analysis of cascading failure risks. We introduce the visualization model for identifying size of cascading and potential outages and estimate the propagation rate of sequential outage simulation. The proposed model is applied to Korean power systems.

A Framework for Wide-area Monitoring of Tree-related High Impedance Faults in Medium-voltage Networks

  • Bahador, Nooshin;Matinfar, Hamid Reza;Namdari, Farhad
    • Journal of Electrical Engineering and Technology
    • /
    • 제13권1호
    • /
    • pp.1-10
    • /
    • 2018
  • Wide-area monitoring of tree-related high impedance fault (THIF) efficiently contributes to increase reliability of large-scaled network, since the failure to early location of them may results in critical lines tripping and consequently large blackouts. In the first place, this wide-area monitoring of THIF requires managing the placement of sensors across large power grid network according to THIF detection objective. For this purpose, current paper presents a framework in which sensors are distributed according to a predetermined risk map. The proposed risk map determines the possibility of THIF occurrence on every branch in a power network, based on electrical conductivity of trees and their positions to power lines which extracted from spectral data. The obtained possibility value can be considered as a weight coefficient assigned to each branch in sensor placement problem. The next step after sensors deployment is to on-line monitor based on moving data window. In this on-line process, the received data window is evaluated for obtaining a correlation between low frequency and high frequency components of signal. If obtained correlation follows a specified pattern, received signal is considered as a THIF. Thereafter, if several faulted section candidates are found by deployed sensors, the most likely location is chosen from the list of candidates based on predetermined THIF risk map.

고장전류를 고려한 수도권 BTB HVDC 위치선정 연구 (A study on BTB HVDC location in metropolitan area considering fault current analysis)

  • 윤민한;장길수;박정수;장병훈
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.274-275
    • /
    • 2011
  • Fault current problems is considered a serious issue in the power system because large fault currents not only cause many side effects to the equipments of power system but also lead to severe problems, such as blackouts. This paper deals with the structural analysis and 3-phase fault current stability of the future Seoul metropolitan power system. The simulation composition and analysis are performed with the 4th KEPCO power supply planning data using PSS/e. Through the results of the simulations, it can be observed that the future Seoul metropolitan system results in a fault current which exceeds the circuit breaker (CB) rate. This unremovable fault current can cause critical damage to power system. To resolve the problem, the algorithm for the application of Voltage Sourced Converter Back-to-Back High Voltage Direct Current (VSC BTB HVDC) is being proposed. where the most suitable location for solving fault current problem in Seoul metropolitan area is being implemented.

  • PDF

Preventing cascading failure of electric power protection systems in nuclear power plant

  • Moustafa, Moustafa Abdelrahman Mohamed Mohamed;Chang, Choong-koo
    • Nuclear Engineering and Technology
    • /
    • 제53권1호
    • /
    • pp.121-130
    • /
    • 2021
  • Cascading failure is the main cause of large blackouts in electrical power systems; this paper analyzes a cascading failure in Hanbit nuclear power plant unit two (2) caused by a circuit breaker (CB) operation failure. This malfunction has been expanded to the loss of offsite power (LOOP). In this study, current practices are reviewed and then the methodologies of how to prevent cascading failures in protection power systems are introduced. An overview on the implementation of IEC61850 GOOSE messaging-based zone selective interlocking (ZSI) scheme as key solution is proposed. In consideration of ZSI blocking time, all influencing factors such as circuit breaker opening time, relay I/O response time and messages travelling time in the communication network should be taken into account. The purpose of this paper is to elaborate on the effect of cascading failure in NPP electrical power protection system and propose preventive actions for this failures. Finally, the expected advantages and challenges are elaborated.

A Novel Online Multi-section Weighed Fault Matching and Detecting Algorithm Based on Wide-area Information

  • Tong, Xiaoyang;Lian, Wenchao;Wang, Hongbin
    • Journal of Electrical Engineering and Technology
    • /
    • 제12권6호
    • /
    • pp.2118-2126
    • /
    • 2017
  • The large-scale power system blackouts have indicated that conventional protection relays that based on local signals cannot fit for modern power grids with complicated setting or heavily loaded-flow transfer. In order to accurately detect various faulted lines and improve the fault-tolerance of wide-area protection, a novel multi-section weighed fault matching and detecting algorithm is proposed. The real protection vector (RPV) and expected section protection vectors (ESPVs) for five fault sections are constructed respectively. The function of multi-section weighed fault matching is established to calculate the section fault matching degrees between RPV and five ESPVs. Then the fault degree of protected line based on five section fault degrees can be obtained. Two fault detecting criterions are given to support the higher accuracy rate of detecting fault. With the enumerating method, the simulation tests illustrate the correctness and fault-tolerance of proposed algorithm. It can reach the target of 100% accuracy rate under 5 bits error of wide-area protections. The influence factors of fault-tolerance are analyzed, which include the choosing of wide-area protections, as well as the topological structures of power grid and fault threshold.

긴급복구용 자주조립식 철주 절연암 개발 (Development of Arm Insulator for Self-Build Based Emergency Tower)

  • 민병욱;위화복;박재웅;이철호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.107-108
    • /
    • 2007
  • Overhead transmission lines are completely exposed to the environment. This causes faults in transmission lines due to natural environmental conditions. In some cases, transmission towers are damaged by typhoons and snow, as well as sleet on the transmission lines. It takes a lot of time to repair the damaged towers. For emergency restoration purposes, steel poles are installed to temporarily supply power. Before 2003, emergency restoration steel poles were made of angled steel, which required a large number of beams, bolts, etc. In addition, the foundation of the steel pole and ground wire was constructed using excavation and burial methods, therefore it required a lot of manpower and time to construct temporary transmission lines. In September 2003, typhoon Maemi, whose maximum wind speed was 60m/s, hit Korea. 'Maemi' destroyed transmission lines in the Busan and Geojea area, causing long blackouts. To reduce the recovery time to the damaged transmission lines, self-build based emergency towers were developed. self-build based emergency towers reduced recovery time from 24 hours to 4 hours or less. However, the self-build based emergency tower had no arms, so the temporary transmission lines could only be constructed without curves in line routes. In this paper, solving these self-build based emergency tower limitations, using insulated arms(designed for use with the self-build based emergency tower), shall be explained.

  • PDF

XML을 이용한 이벤트 기반 분산 전력 정보 시스템 개발 (Development a Distributed Power Information System Based on Event using XML)

  • 김정숙
    • 한국컴퓨터정보학회논문지
    • /
    • 제14권8호
    • /
    • pp.89-96
    • /
    • 2009
  • 향후 에너지 환경에서 전력 관리 시스템은 예기치 못한 정전이나 과부하 같은 응급 상황 이벤트들이 발생하면 이를 실시간으로 대처할 수 있어야 하고, 원격 검침과 같은 소비자 서비스 이벤트들도 신속하게 제공되어야 한다. 뿐만 아니라, 시스템에서 발생되는 대용량의 정보들을 효과적으로 처리할 수 있는 기능도 필요하다. 이에 본 논문에서는 정보교환에 효율적인 XML(eXtensible Markup Language)을 이용하여 이벤트에 기반하며 대용량의 정보들을 부하 균형시키고, 핫 스폿(hot spot)을 줄일 수 있는 메타 데이터 처리 기법이 적용된 분산 전력 정보 관리 시스템을 개발하였다. 개발된 시스템을 실험하기 위해 무선통신으로 전력 단말기들을 제어할 수 있는 축소된 미래 전력 시스템을 제작한 후, 이를 통해 실험을 수행하였다.