• 제목/요약/키워드: LV PLC

검색결과 8건 처리시간 0.025초

Characterization and Field Measurements of NB-PLC for LV Network

  • Masood, Bilal;Ellahi, Manzoor;Khan, Waheed Aftab;Akram, Waqar;Usman, Muhamad;Gul, Muhammad Talha
    • Journal of Electrical Engineering and Technology
    • /
    • 제13권1호
    • /
    • pp.521-531
    • /
    • 2018
  • This paper presents a procedure for field measurements which provides a generalized Narrowband Power Line Communications (NB-PLC) channel model for low voltage (LV) access network in order to deploy advanced metering infrastructure (AMI) within Lahore, Pakistan. The measurements of allocated sites were performed in the residential (urban and rural), industrial and commercial electricity consumers for the NB-PLC channel modeling of overhead transmission lines (TLs). On the basis of extensive field measurement results, the average attenuation profile and transfer functions are presented. The results obtained from field measurements are validated by comparing them with a proposed Simulink model. A close agreement in the measured and simulated transfer function (TF) results is observed. The proposed Simulink model is an effort to model the NB-PLC channels in an effective way, especially in South Asian countries.

지중 저압 전력선의 협대역 전력선통신 채널특성 및 적용성에 대한 연구 (Study on Channel Characteristics and Feasibility of Narrowband Power Line Communication over Underground Low Voltage Power Lines)

  • 유현우;윤경섭;강수경;최인지;박병석;김일한;김원수
    • 한국통신학회논문지
    • /
    • 제38A권10호
    • /
    • pp.874-884
    • /
    • 2013
  • 본 논문은 국내 지중 저압선에 대한 협대역 PLC 기술의 통신 채널 특성과 이를 기반으로 한 적용성 연구결과에 대해 기술한다. 지중 저압선이 매설된 실제 거주지역에 협대역 PLC 채널 측정을 위한 시스템을 구성하였으며, 이를 통해 채널 응답, 잡음 PSD, 선 임피던스를 포함하는 채널 특성을 측정하였다. 측정된 채널 특성을 분석하여 국내 지중 저압선의 채널 특성이 협대역 PLC 적용에 적합한 특성을 띠며, 250kHz 이후 주파수 대역이 특히 양호한 특성을 나타내는 것을 보였다. 이를 기반으로 IEEE P1901.2 규격을 채택, FCC High 대역을 이용하여 네트워크 테스트를 수행하였으며 이를 통해 국내 지중 저압선에 협대역 PLC 기술의 적용이 가능함을 확인하였다.

고속전력선통신과 무선통신간의 간섭 회피 방법에 대한 연구 (A Study on Methods of Interference Avoidance between Power Line Communications and Radio Communications)

  • 장동원;이영환
    • 한국정보통신설비학회:학술대회논문집
    • /
    • 한국정보통신설비학회 2007년도 학술대회
    • /
    • pp.223-226
    • /
    • 2007
  • This paper first outlines the technology used in Power Line Communications(PLC) systems, and the political support being offered to the technology, from the point of view of its effect on electromagnetic compatibility (EMC). The radio spectrum needs protection from other interferers, and there is a regime in place to provide this interference avoidance/mitigation. Nevertheless, PLC has several features that mean that it is capable of creating such interference. These features are discussed, and some published field trial results are reviewed. Difficulties in achieving compatibility between the requirements for radio protection and the requirements for operation of the PLC system mean that there is no consensus as yet as to how PLC system components can be made compliant with EMC requirements. It is concluded that there is little prospect of an accommodation between the competing demands, so that if PLC is to become widespread it will be at the expense of the radio environment.

  • PDF

Modeling and Characterization of Low Voltage Access Network for Narrowband Powerline Communications

  • Masood, Bilal;Haider, Arsalan;Baig, Sobia
    • Journal of Electrical Engineering and Technology
    • /
    • 제12권1호
    • /
    • pp.443-450
    • /
    • 2017
  • Nowadays, Power Line Communication (PLC) is gaining high attention from industry and electric supply companies for the services like demand response, demand side management and Advanced Metering Infrastructure (AMI). The reliable services to consumers using PLC can be provided by utilizing an efficient PLC channel for which sophisticated channel modeling is very important. This paper presents characterization of a Low Voltage (LV) access network for Narrowband Power Line Communications (NB-PLC) using transmission line (TL) theory and a Simulink model. The TL theory analysis not only includes the constant parameters but frequency selectivity is also introduced in these parameters such as resistance, conductance and impedances. However, the proposed Simulink channel model offers an analysis and characterization of capacitive coupler, network impedance and channel transfer function for NB-PLC. Analysis of analytical and simulated results shows a close agreement of the channel transfer function. In the absence of a standardized NBPLC channel model, this research work can prove significant in improving the efficiency and accuracy of NB-PLC communication transceivers for Smart Grid communications.

저압 PLC 배전 네트워크를 위한 두가지 전송 주파수 대역 비교 (Comparison of two different frequency bands on LV distribution network for PLC)

  • 김용성;김재철;권영목;이양진
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.322-324
    • /
    • 2005
  • This paper describes the comparison of Two frequency ranges for power line communication. The first one is that the frequency range from 100 to 400 KHz is supported by the Federal Communication Committee(FCC). The other one is that the frequency range from 1MHz to 30MHz is based on the European-supported EN5006A band. In this paper, the advantages and disadvantages of their frequency ranges are discussed for PLC. By ATP/EMTP software, the signal attenuation is simulated both the frequency ranges. It shows that the signal attenuation is bigger at high frequency than at low frequency.

  • PDF

전력선 통신을 위한 저압 배전 시스템의 임피던스 연구 (Study on Characteristic Impedance in LV Distribution System for PLC)

  • 김용성;김재철;이양진;조성민
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2006년도 춘계학술대회 논문집
    • /
    • pp.78-81
    • /
    • 2006
  • In this paper, the investigation of characteristic impedance on low voltage distribution system is described The residential area of LV distribution systems is researched for the modeling. At frequency range from 1MHz to 30Mhz, the input characteristic impedances of low-voltage distribution network are obtained with experiments. The low-voltage distribution system based on the model is built at the laboratory building. S parameters are measured by performing experiments. Finally, the characteristic impedances are reported.

  • PDF

전력선 통신용 접촉식 커플러의 제조와 통신 특성 향상 (Manufacturing and Communication properties of Capacitive Coupler for the low Voltage Power Line Communication)

  • 김현식;이해연;이진;김춘배;오영우
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2009년도 하계학술대회 논문집
    • /
    • pp.369-370
    • /
    • 2009
  • 전력선 통신용 접촉식 커플러의 제조 방법 확립과 응용 가능성을 파악하기 위해 440V이하의 저압용 3상 4선식 접촉식 커플러를 설계 및 제조하였다. 60Hz의 교류 전압 신호를 차단하는 캐패시터의 용량이 증가할수록 삽입 손실의 증가하였으며, 68nF의 캐패시터를 적용하여 90~450kHz, 2~30MHz의 전력선통신 주파수 대역에서 최소 삽입 손실 특성을 얻었다. 커플링 트랜스의 권선수 증가는 전자계 결합계수의 상승으로 자기유도 효율이 증가하여 삽입 손실 특성이 증가하였으며. 6턴 이상의 권선수에서는 거의 일정한 삽입 손실 특성을 나타내었다. 설계 완료된 접촉식 커플러를 이용하여 전력선 통신 주파수인 90~450kHz, 2~30MHz 대역에서 $-2\pm1dB$의 삽입 손실 특성을 얻었다.

  • PDF

저압 배전선 반송 방식의 원격검침 실증 연구 (The Study on the Automated Meter Reading using Low Voltage Power)

  • 박상만;하복남;이중호;조남훈;김명수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 D
    • /
    • pp.985-987
    • /
    • 1997
  • AMR(Automated Meter Reading) has been considered to solve the lack of meter mem caused by the rise of cost, inefficiency of manual meter reading. Demand forecasting and efficient management of facilities can be accomplished by increasing meter reading efficiency and correcting various data. In this paper, we introduce AMR system using LV PLC in KANG-DONG blanch office of KEPCO.

  • PDF