• Title/Summary/Keyword: K-FNET

Search Result 7, Processing Time 0.033 seconds

Digital Frequency Estimation Algorithm for Frequency Monitoring (주파수 모니터링을 위한 디지털 주파수 추정 알고리즘)

  • Park, Chul-Won;Kim, Ye-Ji
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.89_90
    • /
    • 2009
  • 근래 주파수 편이를 모니터링 함으로서 광역정전 예방을 도모하려는 GPS 기반 FNET에 대한 연구가 시도되고 있다. 본 연구에서는 PMUs와 FNET에 대하여 살펴본 후, FNET에 적용 가능한 주파수 추정 알고리즘을 비교하였다.

  • PDF

Wide-area Frequency-based Tripped Generator Locating Method for Interconnected Power Systems

  • Kook, Kyung-Soo;Liu, Yilu
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.6
    • /
    • pp.776-785
    • /
    • 2011
  • Since the Internet-based real-time Global Positioning System(GPS) synchronized widearea power system frequency monitoring network (FNET) was proposed in 2001, it has been monitoring the power system frequency in interconnected United States power systems and numerous interesting behaviors have been observed, including frequency excursion propagation. We address the consistency of a frequency excursion detection order of frequency disturbance recorders in FNET in relation to the same generation trip, as well as the ability to recreate by power systems dynamic simulation. We also propose a new method, as an application of FNET measurement, to locate a tripped generator using power systems dynamic simulation and wide-area frequency measurement. The simulation database of all the possible trips of generators in the interconnected power systems is created using the off-line power systems dynamic simulation. When FNET detects a sudden drop in the monitoring frequency, which is most likely due to a generation trip in power systems, the proposed algorithm locates a tripped generator by finding the best matching case of the measured frequency excursion in the simulation database in terms of the frequency drop detection order and the time of monitoring points.

Measurement and Simulation of Wide-area Frequency in US Eastern Interconnected Power System

  • Kook, Kyung Soo;Liu, Yilu
    • Journal of Electrical Engineering and Technology
    • /
    • v.8 no.3
    • /
    • pp.472-477
    • /
    • 2013
  • An internet-based, real-time GPS synchronized wide-area power system frequency monitoring network(FNET) has been monitoring wide-area power system frequency in continuous time in the United States. This paper analyzes the FNET measurement to the verified disturbances in the US eastern interconnected power system and simulates it using the dynamic system model. By comparing the frequency measurements with its simulation results to the same disturbances in detail, this paper finds that the sequence of monitoring points to detect the frequency fluctuation caused by the disturbances is matched well in the measured data and the simulation results. The similarity comparison index is also proposed to quantify the similarity of the compared cases. The dynamic model based simulation result is expected to compensate for the lack of FNET measurement in its applications.

Study on the Propagation Speed of the wide-area power system frequency for the application of FNET (광역 전력계통 주파수 감시망 적용을 위한 광역계통주파수의 전파속도에 관한 연구)

  • Kook, Kyung-Soo;Rho, Dae-Seok
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.10 no.8
    • /
    • pp.1824-1831
    • /
    • 2009
  • This paper analyzes the propagation speed of the wide-area power system frequency. When a generator supplying the electric power to the grid is accidently tripped due to a disturbance on the systems, power system frequency suddenly drops during the transient period and this propagates from the location of the tripped generator to the other part of the systems like a wave. Since the propagation speed of the power system frequency depends on the own characteristics of power systems, its understanding from the perspective of the wide-area can help us in understanding power systems more correctly. In addition, the propagation speed of the power system frequency is used as a key parameter in the application study of IT based on the internet-based GPS synchronized frequency monitoring network (FENT) which has been recently implemented and operated in U.S. power systems. This paper simulates the generation trip on various locations in U.S. power systems deploying its latest dynamic model and calculates the propagation speed of the power system frequency for the application of FNET.

Development of Dynamic Frequency Monitoring Software for Wide-Area Protection Relaying Intelligence (광역 보호계전 지능화를 위한 동적 주파수 모니터링 S/W 개발)

  • Kim, Yoon-Sang;Park, Chul-Won
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.61 no.4
    • /
    • pp.174-179
    • /
    • 2012
  • The social and economic level of damages might be highly increased in the case of wide-area black-outages, because of heavy dependence of electricity. Therefore, the development of a wide-area protection relay intelligence techniques is required to prevent massive power outages and minimize the impact strength at failure. The frequency monitoring and prediction for wide-area protection relaying intelligence has been considered as an important technology. In this paper, a network-based frequency monitoring system developed for wide-area protection relay intelligence is presented. In addition, conventional techniques for frequency estimation are compared, and a method for advanced frequency estimation and measurement to improve the precision is proposed. Finally, an integrated monitoring system called K-FNET(Korea-Frequency Monitoring Network) is implemented based on the GPS and various energy monitoring cases are studied.

Frequency Estimation Method using Recursive Discrete Wavelet Transform for Fault Disturbance Recorder (FDR를 위한 RDWT에 의한 주파수 추정 기법)

  • Park, Chul-Won;Ban, Yu-Hyeon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.8
    • /
    • pp.1492-1501
    • /
    • 2011
  • A wide-area protection intelligent technique has been used to improve a reliability in power systems and to prevent a blackout. Nowadays, voltage and current phasor estimation has been executed by GPS-based synchronized PMU, which has become an important way of wide-area blackout protection for the prevention of expending faults in power systems. As this technique has the difficulties in collecting and sharing of information, there have been used a FNET method for the wide-area intelligent protection. This technique is very useful for the prediction of the inception fault and for the prevention of fault propagation with accurate monitoring frequency and frequency deviation. It consists of FDRs and IMS. It is well known that FNET can detect the dynamic behavior of system and obtain the real-time frequency information. Therefore, FDRs must adopt a optimal frequency estimation method that is robust to noise and fault. In this paper, we present comparative studies for the frequency estimation method using IRDWT(improved recursive discrete wavelet transform), for the frequency estimation method using FRDWT(fast recursive discrete wavelet transform). we used the Republic of Korea 345kV power system modeling data by EMTP-RV. The user-defined arbitrary waveforms were used in order to evaluate the performance of the proposed two kinds of RDWT. Also, the frequency variation data in various range, both large range and small range, were used for simulation. The simulation results showed that the proposed frequency estimation technique using FRDWT can be the optimal frequency measurement method applied to FDRs.

Comparative Studies of Frequency Estimation Method for Fault Disturbance Recorder (고장 왜란 기록기를 위한 주파수 추정 기법의 비교 연구)

  • Park, Chul-Won
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.61 no.2
    • /
    • pp.87-92
    • /
    • 2012
  • Voltage and current phasor estimation has been executed by GPS-based synchronized PMU, which has become an important way of wide-area blackout protection for the prevention of expending faults in a power system. The PMU technique can not easily get the field data and it is impossible to share information, so that there has been used a FNET(Frequency Monitoring Network) method for the wide-area intelligent protection in USA. It consists of FDR(Fault Disturbance Recorder) and IMS(Information Management System). Therefore, FDR must provide an optimal frequency estimation method that is robust to noise and failure. In this paper, we present comparative studies for the frequency estimation method using IRDWT(Improved Recursive Discrete Wavelet Transform), FRDWT(Fast Recursive Discrete Wavelet Transform), and DFT(Discrete Fourier Transform). The Republic of Korea345[kV] power system modeling data by EMTP-RV are used to evaluate the performance of the proposed two kinds of RDWT(Recursive Discrete Wavelet Transform) and DFT. The simulation results show that the proposed frequency estimation technique using FRDWT could be the optimal frequency measurement method, and thus be applied to FDR.