회전수 상승폭 변화에 따른 인버터열펌프의 비정상 운전특성 (A study on the transient characteristics during speed up of inverter heat pump)

  • 황윤제;김호영
    • 설비공학논문집
    • /
    • 제10권4호
    • /
    • pp.495-507
    • /
    • 1998
  • The transient characteristics of a 4.0㎾ inverter driven heat pump was investigated by theoretical and experimental studies. The heat pump used in this study consists of a high side scroll compressor and $\Phi$7 compact heat exchangers with two capillary tubes. A series of tests was peformed to examine the transient characteristics of heat pump in heating and cooling mode when the operating speed was varied from 30Hz to 102Hz. One of the major issues that has not been addressed so far is transient characteristics during speed modulation. A cycle simulation model has been developed to predict the cycle performance under frequency rise-up conditions, and the results of theoretical study were compared with the results of experimental study. The theoretical model was driven from mass conservation and energy conservation equations to predict the operation points of refrigerant cycle and the performances at various operating speeds. For transient conditions, the simulated results are in good agreement with the experimental results within 10%. The transient cycle migration of the liquid state refrigerant causes a significant dynamic change in system. Thus, the migration of refrigerant is the most important factor whenever An experimental analysis is performed or A simulation model is developed.

  • PDF

Capacity Modulation of an Inverter Driven Heat Pump with Expansion Devices

  • Lee, Yong-Taek;Kim, Yong-Chan;Park, Youn-Cheol;Kim, Min-Soo
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제8권2호
    • /
    • pp.60-68
    • /
    • 2000
  • An experimental study was peformed to investigate characteristics of an inverter driven heat pump system with a variation of compressor frequency and expansion device. The compressor frequency varied from 30Hz to 75Hz, and the performance of the system ap-plying three different expansion devices such as capillary tube, thermostatic expansion valve(TXV), and electronic expansion valve (EEV) was measured. The load conditions were altered by varying the temperatures of the secondary fluid entering condenser and evaporator with a constant flow rate. When the test condition was deviated from the standard value(rated value), TXV and EEV showed better performance than capillary tube due to optimal control of mass flow rate and superheat. In the present study, it was observed that the variable area expansion device had better performance than constant area expansion device in the inverter heat pump system due to active control of flow area with a change of com-pressor frequency and load conditions.

  • PDF

인버터 열펌프의 주파수 및 냉매봉입량 변화에 따른 시스템 성능특성의 실험적 연구 (An Experimental Study on the Performance of an Inverter Heat Pump with a Variation of Frequency and Refrigerant Charging Amount)

  • 최득관;김경천;김주상
    • 설비공학논문집
    • /
    • 제13권1호
    • /
    • pp.66-71
    • /
    • 2001
  • In the air-conditioning industry, the refrigerant charging amount is one of the most important parameters affecting the energy efficiency ratio of heat pumps. An experimental study was performed on the characteristics of an inverter driven air-to-air heat pump system with a variation of compressor frequency and charging amount of refrigerant. The frequency was altered from 40Hz to 70Hz and the charging amount was changed from 1.6kg to 2.8kg in tests. The variation of performance was measured with switching of the expansion valve on each frequency and charging amount. All the tests were performed at the Korean Standard and test conditions of the air conditioners. As results, it was found that there existed the charging amount and the level of the suction gas superheat which provided the highest energy efficiency ratio at all the frequency bands.

  • PDF

동특성을 고려한 열펌프의 엑서지 해석 (Exergy analysis of heat pump in consideration of its dynamic response)

  • 장기태;남관우;정상권
    • 설비공학논문집
    • /
    • 제10권2호
    • /
    • pp.155-164
    • /
    • 1998
  • A multi-type heat pump controls the mass flow rate of the working fluid to cope with variable heat loads when it is under dynamic load condition. This paper describes the exergy analysis associated with the dynamic response of heat pump. First, a basic heat pump cycle is examined at steady state to show the general trends of exergy changes in each process of the cycle. Entropy generation issue in the exchangers is discussed to optimize the heat pump cycle. Second, the performance of the inverter-driven heat pump is compared to that of the conventional one when the heat load is variable. Third, the exergy destruction rate associated with the ON/OFF operations of the heat pump is calculated by simulating the thermodynamic states of the condenser and the evaporator. The inefficiency of the ON/OFF operation during the transient period is quantitatively revealed by the exergy analysis.

  • PDF

Experimental Study on Characteristics of Two-Phase Flow through a Bypass Orifice Expansion Device

  • Choi, Jong-Min;Kim, Yong-Chan
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제9권1호
    • /
    • pp.11-19
    • /
    • 2001
  • To establish optimum cycle of the inverter-driven heat pump with a variation of frequency, the bypass orifice, which was a short tube haying a bypass hole in the middle, was designed and tested. Flow characteristics of the bypass orifice were measured as a function of orifice geometry and operating conditions. Flow trends with respect to frequency were compared with those of short tube orifices and capillary tubes. Generally, the bypass orifice showed the best flow trends among them. and it would enhance the seasonal energy efficiency ratio of an inverter heat pump system, Based on experimental data, a semi-empirical flow model was developed to predict mass flow rate through bypass orifices. The maximum difference between measured data and model`s prediction was within $\pm$5%.

  • PDF

바이패스 오리피스 팽창장치의 유동 특성에 관한 실험적 연구 (Experimental study on characteristics of two-phase flow through a bypass-orifice expansion device)

  • 최종민;김용찬
    • 설비공학논문집
    • /
    • 제11권1호
    • /
    • pp.109-116
    • /
    • 1999
  • To establish optimum cycle of the inverter-driven heat pump with a variation of frequency, the bypass orifice, which is a short tube having a bypass hole in the middle, was designed and tested. Flow characteristics of the bypass orifice were measured as a function of orifice geometry and operating conditions. Flow trends with respect to frequency were compared with those of short tube orifices and capillary tubes. Generally, the bypass orifice showed the best flow trends among them, that will enhance the seasonal energy efficiency ratio of an inverter heat pump system. Based on experimental data, the semi-empirical flow model was developed to predict mass flow rate through bypass orifices. The maximum difference between measured data and model's prediction was within ${\pm}5%$.

  • PDF

Exergy Analysis of On/Off Controlled Heat Pump

  • Jang, Ki-Tae;Nam, Kwan-Woo;Jeong, Sang-Kwon
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제7권
    • /
    • pp.22-32
    • /
    • 1999
  • A multi-type heat pump controls the mass flow rate of the working fluid to cope with variable heat loads when it is under dynamic load condition. This paper describes the exergy analysis associated with the unsteady response of a heat pump. First, a basic heat pump cycle is examined at a steady state to show the general trends of exergy variations in each process of the cycle. Entropy generation issue for the heat exchangers is discussed to optimize the heat pump cycle. Secondly, the performance of the inverter-driven heat pump is compared to that of the conventional one when the heat load is variable. Thirdly, the exergy destruction rate of the heat pump with On/Off operation is calculated by simulating the thermodynamic states of the working fluid in the condenser and the evaporator. The inefficiency of On/Off operation during the transient period is quantitatively described by the exergy analysis.

  • PDF

적분형 최적 레귤레이터 적용 시스템 히트펌프 제어 시뮬레이션 연구 (Numerical Simulation of a System Heat Pump Adopting an Integral Optimum Regulating Controller)

  • 김용찬;최종민
    • 설비공학논문집
    • /
    • 제25권7호
    • /
    • pp.398-405
    • /
    • 2013
  • Small and medium-size buildings employ a multi-distributed individual air-conditioning system that utilizes package air conditioners instead of centralized cooling systems, which can allow easier building management and maintenance, along with a diversification of facility use. Inverter driven system heat pumps have been developed to achieve not only an easy distribution control, allowing free combination of indoor units with different models and different capacities, but also wide applications to intelligent air conditioning. However, the control algorithms of the system heat pump are limited in the open literature, due to complicated operating conditions. In this paper, an inverter-driven system heat pump having two indoor units with electronic expansion valves (EEV) was simulated in the cooling mode. An integral optimum regulating controller employing the state space control method was also simulated, and applied to the system-heat pump system, to obtain efficient control of the MIMO (multi input multi output) system. The simulation model for the controller yielded satisfactory prediction results. The new control model can be successfully utilized as a basic tool in controller design.

전자식 팽창밸브를 적용한 3RT급 히트펌프 시스템의 냉방 성능 특성 (Cooling Performance Characteristics of 3RT Heat Pump System applied Electronic Expansion Valve)

  • 손창효;윤정인;최광환;하수정;전민주;박성현;이상봉
    • 동력기계공학회지
    • /
    • 제21권6호
    • /
    • pp.79-85
    • /
    • 2017
  • A heat pump system is a highly efficient, eco-friendly device which consumes a small amount of energy and supply a lot of energy for heat formation. In addition, it is a single device system that has low generation effect about carbon dioxide. There are many researches related to the electronic expansion valve and the heat pump, but the detailed data analysis of each influence is insufficient. In this study, the cooling capacity and COP of the heat pump system were investigated by varying frequency of the inverter connected to compressor, inlet temperature of chilled water into evaporator and inlet temperature of cooling water into condenser. The results are as follows : (1) The cooling capacity increased as the inverter frequency, inlet temperature of chilled water into evaporator increased, and inlet temperature of cooling water into condenser decreased. (2) The COP increased as the frequency of inverter, inlet temperature of cooling water into condenser decreased and the inlet temperature of chilled water into evaporator increased.

인버터 열펌프내 오일순환량에 관한 실험적 연구 (An Experimental Study on the Oil Circulation in an Inverter-Driven Heat Pump)

  • 민만기;홍기수;황윤제;황일남;김철민;조관식
    • 설비공학논문집
    • /
    • 제12권8호
    • /
    • pp.717-724
    • /
    • 2000
  • It is important to investigate characteristics of flow of refrigerant/oil mixture circulating in a refrigeration system. Therefore the oil concentration in refrigerant/oil mixture should be measured exactly by the adequate measuring instrument. In this paper, the oil concentration was measured by density monitoring system(DMS) in the liquid-line of a inverter-driven heat pump. Experimental result follows ; the main factor that have an effect on oil concentration refrigerant/oil mixture circulating in a refrigeration system is the momentum and kinematic viscosity of refrigerant/oil mixture compressed by scroll compressor.

  • PDF