• 제목/요약/키워드: Intermittent heating system

검색결과 15건 처리시간 0.021초

간헐난방주택에 대한 외기온도 예측제어 적용 연구 (Application of the Outdoor Air Temperature Prediction Control for Intermittent Heating Residences)

  • 태춘섭;조성환;이충구
    • 설비공학논문집
    • /
    • 제13권8호
    • /
    • pp.682-691
    • /
    • 2001
  • Most of radiant floor heating systems are operated in the intermittent heating mode in Korea. The application possibility of predictive suboptimal control for Koran residential house was investigated by computer simulation and experiment. For this study, TRNSYS program was used and an experimental facility consisting of tow rooms ($3\times4.4\times2.8 m$) identical in construction was built. The facility enabled simultaneous comparison of two different control method. And real multi residential hose was investigated. Results showed that outdoor air temperature prediction control was superior to the conventional control for radiant floor heating system operated in the intermittent heating mode. New control system resulted in good thermal environment and les energy consumption.

  • PDF

공동주택 간헐난방시스템의 에너지 절감 및 열환경 개선방안 연구 (Strategy of Energy Saving and Thermal Environment Improvement for Intermittent Heating System in Apartment Buildings)

  • 안병천;이태원
    • 설비공학논문집
    • /
    • 제17권1호
    • /
    • pp.88-93
    • /
    • 2005
  • In this study, the operational characteristics on heating performance and energy consumption for intermittent hot water heating system in apartment buildings were research by simulation. The effects of apartment inlet hot water temperature and operation time per day on energy consumption and indoor thermal environment are investigated. The strategy of energy saving and thermal environment improvement is suggested in comparison with the existing ones.

공동주택용 온수난방 시스템의 에너지해석 및 제어특성 (The Energy Analysis and Control Characteristics of a Hot Water Heating System for Apartment Houses)

  • 장효환;안병천
    • 설비공학논문집
    • /
    • 제8권1호
    • /
    • pp.76-87
    • /
    • 1996
  • Energy analysis for the hot water heating control system of apartment house complex is accomplished by computer simulation. Mathematical model of a boiler, pipe network and a unit-house is developed. The effects of heating control methods on the heating performance and energy consumption of the system are investigated. The heating control methods considered in this study are a continuous heating control, and on-off heating control and an intermittent heating control methods. For each control method, the effects of an outdoor temperature, indoor temperature sensing position and the capacities of the boilers and circulating pumps on the heating performance and energy consumption are obtained and "the best" control method is recommended.commended.

  • PDF

주거용건물의 바닥복사 난방방식에 대한 실태조사 연구 (Research on the actual condition of 'Under Floor Radiant Heating for Apartment Housing')

  • 우병관;이성;김삼열
    • KIEAE Journal
    • /
    • 제7권5호
    • /
    • pp.81-86
    • /
    • 2007
  • The research analyzes the arrangement of boiler and hot water header, the method of radiator pipe setting, hot water supply control, hourly heating situation of each room for underfloor radiant heating systems in Korea and suggests an alternative to improve to efficient heating method. One of the best options for install position of hot water distributor is under kitchen sink which is center point of all rooms, according to previous research of the energy saving strategies. When the radiator pipes are arranged to each individual room instead of bedrooms through livingroom and kitchen, it has energy saving effects. For rooms without occupancy according to a time period, hot water supply method should be intermittent heating rather than continuous heating. For this intermittent heating method, individual control of hot water supply is more practical, and it can lead to massive energy savings. The intermittent heating system has time-lag, so it is more effective in energy saving with mild and comfort condition if the spaces are preheated by automatic control equipment prior to required time.

SERI-RES를 이용한 Radiant Floor Heating System의 열 성능 분석 (A Thermal Performance Analysis on the Operation Modes of Radiant Floor Heating System Using SERI-RES)

  • 천원기;전명석;오정무
    • 태양에너지
    • /
    • 제11권2호
    • /
    • pp.29-33
    • /
    • 1991
  • 본 연구는 일차원 열 성능 분석 프로그램인 SERI-RES를 이용하여 우리 고유의 난방 방식이라 할 수 있는 Radiant Floor Heating System의 운전 모드(Operation Modes)에 대한 시뮬레이션을 수행하였다. SERI-RES는 원래 공기 가열식 시스템을 주요 난방 방식으로 작성된 프로그램이라 본 연구의 시뮬레이션을 수행하기 위하여 Source Code에 대한 약간의 수정을 가하였다. 얻은 결과를 분석하여 보면 Radiant Floor Heating System은 그 운용 방법(Operation Modes)에 따라 건물의 동적 열 성능에 상당한 영향을 미치는 것으로 나타났으며 이는 Test Cell에 대한 간단한 실측 실험을 통해서도 확인되었다. SERI-RES는 비록 HVAC 시스템등에 대한 구체적인 시뮬레이션은 불가하나, 비록 일차원적이기는 하지만 Radiant Floor Heating 시스템과 건물의 동적 열 성능에 대한 분석에는 상당히 효율적인 Simulation Model을 제공하였다.

  • PDF

공동주택의 에너지소비량 및 난방운전 실태에 관한 조사연구 (An investigation on the heating energy consumption and operating condition in apartment houses)

  • 신용태
    • 한국주거학회:학술대회논문집
    • /
    • 한국주거학회 1994년도 학술발표대회논문집 상
    • /
    • pp.45-50
    • /
    • 1994
  • The energy consumption in apartment houses is investigated according to the heating systems, that is, district, central, and individual heating systems. And, operating conditions of intermittent heating are surveryed and analysed in the central heating systems. As a result, each annual energy consumption of district, central and individual heating system is 143.56 Mcal/m2year, 216.78 Mcal/m2year and 150.68 Mcal/m2year, Also, the heating is generlly started at 04:00 and 17:00 of each day, and the heating system is operated for 2~3 hours per each time.

  • PDF

지중온도회복을 고려한 지열 히트펌프 시스템의 운전방법 검토 (Study on the Operation Method of Ground Source Heat Pump System Considering Recovery of Ground Temperature)

  • 배상무;전재영;권영식;남유진
    • 한국지열·수열에너지학회논문집
    • /
    • 제16권4호
    • /
    • pp.24-30
    • /
    • 2020
  • Ground source heat pump (GSHP) systems are actively introduced as cooling and heating conditioning systems of buildings due to annual stable performance and easily maintenance. However, ground temperature imbalance is occurred when the GSHP is used for a long period. Therefore, in this study, we proposed the operation method of the system that considered the recovery time of heat source temperature. The entering water temperature (EWT) and heat exchange rate (HER) were comparatively analyzed according to the continuous and intermittent operation. Furthermore, the underground thermal environment was evaluated by numerical analysis model. As the result, the intermittent operation was a maximum of 12.3% higher HER during the heating period than the continuous operation. In addition, the overall ground heat source temperature at the intermittent operation was higher than it at the continuous operation.

보일러 운전조건 및 마감층 두께 변화에 따른 온돌난방공간의 열특성에 관한 실험연구 (An experimental study on the heat transfer characteristics of a Ondol-heated space by varying pipe embedding depths and hot water supply conditions)

  • 박병윤
    • 한국주거학회:학술대회논문집
    • /
    • 한국주거학회 1991년도 학술발표대회논문집
    • /
    • pp.41-47
    • /
    • 1991
  • This study reports the results of the transient temperature response of a floor heating panel according to variation of the hot water supply temperature and the pipe embedding depth. Also, this experiment compares the temperature responses of floor heating panels under the continuous and intermittent heating system. Furtthermore, this study presents some details of the thermal response of Ondol-heated buildings to varying loads and patterns of heat input. The analysis of the thermal performance fo Ondol heating system have been presented.

  • PDF

바닥난방용 자동온도조절기의 난방방식에 따른 에너지성능 해석용 프로그램에 관한 연구 (Energy Performance Analysis Program with Heating methods of Automatic Thermostatic Valves in Floor Radiant Heating System)

  • 안병천;송재엽;이태원;김용기
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 동계학술발표대회 논문집
    • /
    • pp.381-386
    • /
    • 2008
  • In this study, the energy characteristic of automatic thermostatic valves according to each heating method in floor radiant heating system were researched by computer simulation. For the analysis of unsteady heat transfer phenomena in household, the method of using electrical equivalent R-C circuit is applied, and radiation heat transfer between panel, ceiling and walls in household is calculated by enclosure analysis method. The parametric study on heating method, valve's control method, outdoor air condition, supply heating water temperature, supply flow rate are performed to compare energy characteristic, respectively.

  • PDF

An Experimental Study on Two Parameter Control for Radiant Floor Heating System

  • Cho, Sung-Hwan;Tae, Choon-Seob;Jang, Chel-Yong
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제6권
    • /
    • pp.136-147
    • /
    • 1998
  • An experimental facility consisting of two 3$\times$4.4$\times$2.8m rooms identical in construction is built. Each room has a control system and storage tank supplying hot water to the radiant floor heating system. The facility enables simultaneous comparison of two different control strategies each implemented in a separate room. The operating performance of three kinds of flow control scheme is tested and compared in this study: (ⅰ) conventional on-off control based on feedback from room air temperature (ⅱ) TPSC(two parameter switching control )(ⅲ) TPOC(two parameter on-off control). Results show that TPSC and TPOC using room air and surface temperature sequentially as feedback signal to control hot water supply is the better temperature regulation scheme than conventional control based on feedback from only room air temperature. They are good candidates for the room with radiant floor heating system under continuous and intermittent heating mode.

  • PDF