• Title/Summary/Keyword: Insulation diagnostic

Search Result 111, Processing Time 0.024 seconds

Analysis of Insulation Diagnostic Test for High Voltage motor (II) (고압전동기 절연진단 해석 (II))

  • Lee, Young-Jun
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2107-2109
    • /
    • 1999
  • The insulation diagnostic tests was performed at local thermal power plants high voltage motor. The insulation diagnostic tests include measurements of insulation resistance, polarization index, AC current, $tan{\delta}$, partial discharges. This paper describes Insulation characteristics for high voltage motor which located by inside and outside.

  • PDF

Analysis of Insulation Characteristic for Small Hydro Generator (소수력발전기 절연특성분석)

  • Oh, Bong-Keun;Chang, Jeong-Ho;Lee, Kwang-Ho;Kang, Dong-Sik
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2008.05a
    • /
    • pp.142-145
    • /
    • 2008
  • Electrical insulation of small hydro generator stator winding is one of the most important parts in generator facilities. Some stator winding insulation problems can be identified through analysis of insulation diagnostic test. So, Diagnosis of stator winding insulation is an important measure of ensuring the safe operation and extending the remaining life of small hydro generator. This paper presents case studies of insulation failure in generator stator windings and the results of insulation diagnostic test for small hydro generator stator windings. Especially, Conducting the insulation diagnostic test before the generator installed in site is very important process to keep the good insulation condition in service.

  • PDF

Analysis of Insulation Diagnostic Test for High Voltage Motor(I) (고압전동기 절연진단 해석(I))

  • Lee, Young-Jun;Ju, Young-Ho
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2104-2106
    • /
    • 1999
  • The insulation diagnostic tests was performed at local thermal power plants high voltage motor. The insulation diagnostic tests include measurements of insulation resistance, polarization index, AC current, $tan{\delta}$, partial discharges. This paper describes the difference of insulation characteristics for high voltage motor makers.

  • PDF

Analysis of Insulation Condition in Traction Motor Stator Windings (견인전동기 고정자 권선의 절연상태 분석)

  • Kim, Hee-Dong;Park, Young
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.20 no.7
    • /
    • pp.631-635
    • /
    • 2007
  • Diagnostic, surge and ac breakdown tests are widely used to evaluate the insulation condition of stator winding in traction motor. Diagnostic test included ac current, tan delta and maximum partial discharge. The result of diagnostic test indicates that five kinds of stator windings are good condition. Surge test was peformed to confirm the healthy of turn insulation in stator windings. This test is very easy to detect the turn insulation failure between normal and defect stator windings. After completing the diagnostic test, ac breakdown test has conducted gradually increasing ac voltage, until the stator winding punctured. No. 5 stator windings failed near rated voltage of 18.9 kV The breakdown voltage of No. 1 stator windings was 13.0 kV The ac breakdown voltage of normal winding is about 1.45 times higher than that of defect windings. The failure was located in a line-end coil at the exit from the core slot.

Analysis of Insulation Characteristics for High-voltage Motor Stator Winding using Insulation Diagnostic Test (절연진단법을 이용한 고전압전동기 고정자권선의 절연특성분석)

  • Oh, Bong-Keun;Kang, Hyun-Goo;Kim, Hyun-Il;Lim, Kee-Joe
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.06a
    • /
    • pp.404-405
    • /
    • 2009
  • Insulation diagnostic tests for high voltage motor stator winding were conducted to analyze the insulation characteristics. Test motors were manufactured same factory and year(1996). Insulation characteristics of moisture winding are different from those of deteriorative winding. Insulation resistance and disscipation factor test results are sensitive to moisture winding. AC current, disscipation factor tip-up and PD test results are sensitive to deteriorative winding. Also, Capacitance value for stator winding insulation material has characteristic of increasing in moisture winding.

  • PDF

Evaluation of Insulation Diagnostic Test Reliability for Stator Winding of High Voltage Induction Motor (고압유도전동기 절연특성시험의 신뢰도 평가)

  • Lee, Kwang-Ho;Kim, Hyun-Il;Kwak, Hee-Jin;Oh, Bong-Keun
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1838-1841
    • /
    • 2004
  • This test was performed to assess the correlation between insulation diagnostic tests and breakdown voltage strength of the stator winding of 6.6kV class induction motor in insulation deterioration condition which have been in service for 5 years after being installed in 1998. The insulation diagnostic tests include resistance, polarization index(P.I), dissipation factor(${\triangle}tan{\delta}$), maximum partial discharges(Qmax) and AC breakdown test. we evaluated the correlation between insulation diagnostic test and AC breakdown test for stator winding of high voltage induction motor.

  • PDF

Characteristics of Insulation Diagnostic in Traction Motor Stator Windings (견인전동기 고정자 권선의 절연진단 특성)

  • Kim, Hee-Dong;Kim, Chung-Hyo;Park, Young;Park, Hyun-June
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2006.11a
    • /
    • pp.336-338
    • /
    • 2006
  • Diagnostic tests are used to evaluate the insulation condition of stator windings in traction motor. These tests included ac current, tan delta and maximum partial discharge. The insulation condition of stator windings was assessed by three test items. The stator windings of traction motor were m good condition. After completing the diagnostic tests, the stator windings of traction motors were subjected to gradually increasing ac voltage, until the insulation punctured. No.5 stator windings failed near rated voltage of 18.9 kV. The breakdown voltage of No.1 stator windings was 13.0. The failure was located m a line-end coil at the exit from the core slot.

  • PDF

Evaluation of Insulation Diagnostic Test Reliability for Stator Winding of High Voltage Induction Motor (고압유도전동기 절연특성시험의 신뢰도 평가)

  • Lee, Kwang-Ho;Kim, Hyun-Il;Kwak, Hee-Jin;Oh, Bong-Keun
    • Proceedings of the KIEE Conference
    • /
    • 2004.11d
    • /
    • pp.46-49
    • /
    • 2004
  • This test was performed to assess the correlation between insulation diagnostic tests and breakdown voltage strength of the stator winding of 6.6kV class induction motor in insulation deterioration condition which have been in service for 5 years after being installed in 1998. The insulation diagnostic tests include resistance, polarization index(P.I), dissipation factor(${\Delta}tan{\delta}$). maximum partial discharges(Qmax) and AC breakdown test. we evaluated the correlation between insulation diagnostic test and AC breakdown test for stator winding of high voltage induction motor.

  • PDF

Analysis of Aging Insulation Characteristics of 3.3[kV] Class Induction Motor with AC Breakdown Test (절연파괴시험법을 이용한 3.3[kV] 유도전동기의 절연물 열화특성 분석)

  • Lee, Ju;Kim, Hyun-Il;Kim, Youn-Hyun;Son, Yeoung-Gyu
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.10
    • /
    • pp.141-149
    • /
    • 2007
  • This paper introduce to improve the reliability of the expected service life and the insulation condition evaluation of the high voltage induction motors by assessing, comparing and analyzing the correlation between the dielectric properties of the off-line insulation diagnostic test and dielectric strength on the insulation breakdown test. The insulation diagnostic tests include insulation resistance, polarization index(P.I.), dissipation factor($tan{\delta}$), maximum partial discharges($Q_{max}$) and AC breakdown test. This study evaluated the correlation between insulation diagnostic test and AC breakdown test for stator winding of high voltage induction motor. On the basis of these test results, we expect that this study can be used for effectively assessing the results of insulation diagnostic tests for similar class induction motors in service at industrial field.

Correlation between Insulation Diagnostic Test and AC Breakdown Test for 3.3 kV Class Induction Motor

  • Byun, Doo-Gyoon;Hong, Jin-Woong
    • Transactions on Electrical and Electronic Materials
    • /
    • v.7 no.5
    • /
    • pp.262-266
    • /
    • 2006
  • The insulation diagnostic test and the AC breakdown test were performed under off-line using the 3.3 kV class induction motor which have been served for 10 years. These tests were conducted in means of nondestructive and destructive test. In this paper, we compared the correlation between the nondestructive and destructive test. Furthermore we setup an experimental condition with moisture and compared the insulation characteristics between moist and dry sample. From the results of the nondestructive and destructive test, it was found that the second AC current, which is the previous step of insulation breakdown, suddenly increased at a point of around 8.5 kV. The insulation breakdown of moist sample occurred at 12-14 kV, which is 4-5 kV lower than dry sample.