• 제목/요약/키워드: Insulating transformer

검색결과 166건 처리시간 0.025초

변압기절연재료의 유동대전특성에 미치는 제인자 연구 (A STUDY ON THE FACTOR OF STATIC ELECTRIFICATION ON TRANSFORMER INSULATING-MATERIALS)

  • 이숭녕;허창수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1995년도 하계학술대회 논문집 C
    • /
    • pp.1143-1145
    • /
    • 1995
  • In this paper, we measured leakage current that produced by static electrification at pressboard and insulating paper. We found that the leakage current increased as temperature increased, as oil velocity increased. The leakage current at pressboard is higher than that of insulating paper.

  • PDF

3상 22.9/3.3kV 유입변압기의 소손패턴 해석 및 발화원인 판정에 관한 연구 (Study on the Damage Pattern Analysis of a 3 Phase 22.9/3.3kV Oil Immersed Transformer and Judgment of the Cause of Its Ignition)

  • 최충석
    • 전기학회논문지
    • /
    • 제60권6호
    • /
    • pp.1274-1279
    • /
    • 2011
  • The purpose of this paper is to present the manufacturing defect and damage pattern of a 3 phase 22.9/3.3kV oil immersed transformer, as well as to present an objective basis for the prevention of a similar accident and to secure data for the settlement of PL related disputes. It was found that in order to prevent the occurrence of accidents to transformers, insulating oil analysis, thermal image measurement, and corona discharge diagnosis, etc., were performed by establishing relevant regulation. The result of analysis performed on the external appearance of a transformer to which an accident occurred, the internal insulation resistance and protection system, etc., showed that most of the analysis items were judged to be acceptable. However, it was found that the insulation characteristics between the primary winding and the enclosure, those between the ground and the secondary winding, and those between the primary and secondary windings were inappropriate due to an insulating oil leak caused by damage to the pressure relief valve. From the analysis of the acidity values measured over the past 5 years, it is thought that an increase in carbon dioxide (CO2) caused an increase in the temperature inside the transformer and the increase in the ethylene gas increased the possibility of ignition. Even though 17 years have passed since the transformer was installed, it was found that the system's design, manufacture, maintenance and management have been performed well and the insulating paper was in good condition, and that there was no trace of public access or vandalism. However, in the case of transformers to which accidents have occurred, a melted area between the upper and the intermediate bobbins of the W-phase secondary winding as well as between its intermediate and lower bobbins. It can be seen that a V-pattern was formed at the carbonized area of the transformer and that the depth of the carbonization is deeper at the upper side than the lower side. In addition, it was found that physical bending and deformation occurred inside the secondary winding due to non-uniform pressure while performing transformer winding work. Therefore, since it is obvious that the accident occurred due to a manufacturing defect (winding work defect), it is thought that the manufacturer of the transformer is responsible for the accident and that it is lawful for the manufacture to investigate and prove the concrete cause of the accident according to the Product Liability Law (PLL).

퍼지 알고리즘을 이용한 유중 변압기의 안전진단 및 평가에 관한 연구 (A Study on the Safty Diagnosis and Evaluation of Oil-immersed Transformer using fuzzy Algorithm)

  • 김영일
    • 전기학회논문지P
    • /
    • 제55권4호
    • /
    • pp.190-195
    • /
    • 2006
  • In this paper, safety algorithm of transformer is introduced for the sake of MV/LV distribution customers by using fuzzy theory. The current-carrying capacity of transformer is usually determined by the maximum temperature at which the transformer is permitted to operate. Overload of transformer has an effect on transformer utilization rate and maximum temperature rises as well as maximum ambient temperature of insulating materials. Therefore, we proposed the safety algorithm considering the overload of transformer and ambient temperature in this paper. We introduced the correlational equations between each parameters using experimental data of IEEE std C57.91-1995, and deduced the result using fuzzy reasoning. We guessed the safety algorithm making a diagnosis for the safety status of oil-immersed transformer.

주상변압기용 절연지의 가속화 후 전기적 특성 (Electrical Characteristics of Insulating Paper for Pole Transformers after Accelerated Ageing)

  • 송일근;정종욱;이병성;한용희;김찬영
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 C
    • /
    • pp.1591-1593
    • /
    • 2001
  • In this paper, the electrical characteristics of Insulating paper, for pole transformers, subjected to accelerated ageing were observed and the results were compared with those of virgin insulating paper. For the experiment, insulating materials for pole transformers were enclosed together in an oil bath and thermally aged under the real pole transformer operating conditions. After the accelerated ageing of the insulating materials, the dielectrics were measured and compared with the results of the virgin ones.

  • PDF

절연유의 전기전도에 미치는 첨가제의 영향(II) (The Effect of Additive on the Electric conductivity of Insulating Oil)

  • 정광현;김영봉;김영일;박상현;박재윤;이덕출
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 하계학술대회 논문집 C
    • /
    • pp.1630-1632
    • /
    • 1996
  • The static charges are generated by streaming electrification phenomena when insulating oil flowing by force for the purpose of cooling at the internal of Ultra-high power transformer. In this thesis, their elimination method was studied. In this paper the effect of Additive on the electric conductivity of Insulating oil is studied. The variation of electric conductivity disappear when Additive is molten in insulating oil, the variation of Additive is not enough to decrease streaming electrification of insulating oil(${\sigma}>10^{-12}$[S/cm]).

  • PDF

절연유의 전기전도에 미치는 첨가제의 영향 (The Effect of Additive on the Electric conductivity of Insulating Oil)

  • 정광현;김영봉;김용운;임헌찬;이덕출
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1996년도 춘계학술대회 논문집
    • /
    • pp.158-161
    • /
    • 1996
  • The static charges are generated by streaming electrification phenomena in insulating oil flowing by force for the purpose of cooling at the internal of Ultra-high power transformer. In this thesis, their elimination method was studied. In this paper the effect of Additive on the electric conductivity of Insulating oil is studied. The variation of electric conductivity disappear when Additive is molten in insulating oil BTA(Benzotriazole) appear more variation of electric conductivity than that of SP-S10(Sorbitan mono-stearate). But the variation is not enough to decrease streaming electrification of insulating oil($\sigma$>10$\^$-12/[S/cm]).

  • PDF

발전소 주변압기 운전중 진동 기준치 설정에 관한 연구

  • 이욱륜;이준신
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2005년도 춘계학술대회논문집
    • /
    • pp.587-592
    • /
    • 2005
  • Main transformer's integrity assessment in nuclear power plant is estimated by the electrical test of electrical core and wire and the chemical analysis of insulating oil. Mechanical test or analysis has not been so far. So this study makes it with the vibration velocity rating. The vibration velocity rating in main transformer which is based on the real data of vibration velocity measurement under operating and other machinery vibration code such as ISO code is renewed.

  • PDF

초고압 GAS Voltage Transformer의 장기 과전압 시험에 관한 연구 (The study on the Long-Term overvoltage test of EHV Gas Voltage Transformer)

  • 송희석;박경원;계장석;정장근
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 추계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.157-159
    • /
    • 2002
  • In order to obtain reliability and extend life of GAS Voltage Transformer in GIS, it has to prevent aging by overvoltage considered to insulation characteristics of insulating material. This paper describes some characteristics of V-T characteristics and partial discharges.

  • PDF

전력설비 절연유 열팽창 계산식 개선에 관한 연구 (A study on the improvement of the thermal expansion formula of the insulating oil in electric facilities)

  • 임성황;문봉수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.153-156
    • /
    • 2001
  • The transformer and the OF cable are cooled and insulated by insulating oils in their body. The insulating oil expands or contracts with the heat transfer according to the operating conditions of the electric facilities. So we install the $N_2$ gas tank connected with the insulating oil system to overcome the change. The change of the insulating oil volume for the operation temperature range must be calculated to decide the $N_2$ gas volume and to set the alarm point for safe operation. It is known that this change is proportional to the temperature change and to the insulating oil volume if the temperature change is small enough.[1][11] However this proportional formula has been accepted generally in the design of electric facilities for wide operation temperature range such as $40^{\circ}C{\sim}125^{\circ}C$. Hence, it makes large errors in calculation which car result in serious damage against safe operation of the electric facilities. This paper presents a improved method of calculating the accurate change of the insulating oil volume to insure the safe operation of electric facilities.

  • PDF

Fluorocarbon에서의 변압기권선 절연용 PET필름의 전기적 특성연구 (Electrical characteristics of PET film for wire insulation of transformer in fluorocarbon)

  • 허창수;이재복
    • E2M - 전기 전자와 첨단 소재
    • /
    • 제9권5호
    • /
    • pp.483-489
    • /
    • 1996
  • Power transformer have many unsymmetrical structure and electric field is enhanced in that area. Those unsymmetrical area are not covered oftenly by solid insulating material which is used as a framework specially in gas transformer. By that result there is a possibility to decrease the total insulation class of the transformer. So in this study the electrical characteristic of $FC+SF_6$ mixture gas which is used as coolants for large power gas insulated transformer and its effects on electrical characteristics of structural material are investigated. Also breakdown characteristic with the tension of taping and curvature of the coil are studied which could be used as a design factor of large power transformer.

  • PDF