• 제목/요약/키워드: Industrial chillers

검색결과 8건 처리시간 0.022초

Performance of Alternative Refrigerants in Low Temperature Chillers

  • Jung, Dong-Soo;Kim, Chong-Bo
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제6권
    • /
    • pp.67-79
    • /
    • 1998
  • This paper is about the performance of alternative refrigerants for low temperature and transport refrigeration chillers. A breadboard refrigeration chiller was constructed with counterflow heat exchangers. R502, its transitional alternatives of R402A and R402B, and long-term alternatives of R404A and R507 were tested in an attempt to compare the performance of each refrigerant against R502. Measurements were conducted at two condensing temperatures of 43.3$^{\circ}C$ and 52.$0^{\circ}C$ and the evaporating temperature was varied over a range from -$25^{\circ}C$ to -5$^{\circ}C$. The evaporator superheat and condenser subcooling were maintained constant at about 5$^{\circ}C$ for all tests. Test results showed that all alternative fluids tested in this work can be used as 'drop-in fluids' to replace R502 without any major problem. It is also found that in the long run HFC alternatives are to be used due to their favorable environmental characteristics and better performance.

  • PDF

열펌프를 이용한 R22대체 혼합냉매의 성능에 관한 연구 (A Study on the Performance of HCFC22 and Alternative Refrigerants in Heat Pumps)

  • 송영재;정동수
    • 태양에너지
    • /
    • 제18권1호
    • /
    • pp.69-79
    • /
    • 1998
  • This paper is concerned about the performance of HCFC22 alternative refrigerants used in heat pumps and industrial chillers. A water-to-water breadboard heat pump with counter-current heat exchangers and a hermetic compressor was built to carry out the experiments with various refrigerants. For each test, more than 40 temperatures, 4 pressures, power input, mass flow rates of the heat transfer fluids were measured. Refrigerants tested were HCFC22, R290(Propane), an azeotrope of 45%Propane/55%R134a mixture, and a nonazeotropic mixture of Calor 50. All tests were conducted under ARI test A condition. It is found that the COP and capacity of propane were 18% and 2.5% higher than those of HCFC22 while the COP and capacity of 45%Propane/55%R134a mixture were 3.5% and 5.3% higher than those of HCFC22 respectively. Also the COP and capacity of Calor 50 were 17% and 7.8% higher than those of HCFC22. Compressor discharge temperatures of alternative refrigerants were roughly $35^{\circ}C$ lower than that of HCFC22 indicating that these refrigerants are good from the view point of compressor reliability. The charging amounts for the alternative refrigerants were reduced by 40-60% as compared to that of HCFC22. Overall, it can be said that hydrocarbon containing alternative refrigerants are excellent in thermodynamic performance but should be used with considerable care due to their flammability.

  • PDF

흡착식 냉동기의 열 및 물질전달에 관한 실험적 연구 (An Experimental Study on the Heat and Mass Transfer of Adsorption Chiller)

  • 권오경;윤재호;주영주;김용찬;김종하
    • 설비공학논문집
    • /
    • 제17권8호
    • /
    • pp.746-753
    • /
    • 2005
  • Adsorption chillers have been receiving considerable attentions as they are energy-saving and environmentally benign systems. In order to evaluate adsorption rates, experiments were performed in the batch type adsorption apparatus. Three types of silica gels were investigated under an assortment of experimental conditions that are representatives of the actual operating environments in the adsorber of adsorption chillers. Experimental results revealed the effects of silica gel particle size, bed temperature, and fin pitch of fin tube on the adsorption rate. The $0.25\~1.18mm$ particle size of silica gel with high adsorption rate was selected as a suitable adsorbent. The measured adsorption rate became bigger with decreasing particle size. From the comparison of adsorption rate, it is found that the fin tube has about $21\%$ higher value than that of the bare tube. The effect of heat and mass flux is found to be more significant in the fin tube than in the bare tube.

흡수식 냉동기의 재생기에 사용되는 전열촉진관의 관 내측 열전달계수 및 마찰계수에 대한 실험적 연구 (An Experimental Study on Tube-Side Heat Transfer Coefficients and Friction Factors of the Enhanced Tubes Used in Regenerators of Absorption Chillers)

  • 김내현
    • 한국산학기술학회논문지
    • /
    • 제17권3호
    • /
    • pp.716-723
    • /
    • 2016
  • 전열 촉진관은 흡수식 냉동기에 널리 사용되고 있다. 본 연구에서는 흡수식 냉동기의 재생기에 주로 사용되는 평활관, 리브 튜브, 코류게이트 튜브, 플로랄 튜브에 대하여 관 내측 열전달계수 및 마찰계수를 측정하였다. 실험 결과 열전달계수 및 마찰계수는 코류게이트 튜브에서 가장 크게 나타나고 다음으로 리브 튜브에서 크게 나타났다. 한편 플로랄 튜브의 열전달계수 및 마찰계수는 평활관 값과 4% 내에서 일치하였다. 이로부터 플로랄 튜브의 열전달 및 압력손실 특성이 수력직경으로 적절히 표현될 수 있음을 알 수 있다. 실험 데이터로부터 코류게이트 튜브와 리브 튜브의 B(e+)와 g(e+) 상관식을 구하였는데 코류게이트 튜브의 B(e+)와 g(e+)는 기존 상관식의 예측치와 20% 내에서 일치하였다. 본 연구 결과는 고온 영역에서 재생기용 전열촉진관의 관 내측 열전달 계수 및 마찰계수 산정에 활용될 수 있을 것이다.

수평 평활관에서 관직경 및 표면 과냉도가 R1234ze(E) 및 R1233zd(E) 막응축 열전달에 미치는 영향 (Effects of Tube Diameter and Surface Sub-Cooling Temperature on R1234ze(E) and R1233zd(E) Film Condensation Heat Transfer Characteristics in Smooth Horizontal Laboratory Tubes)

  • 전동순;고지운;김선창
    • 설비공학논문집
    • /
    • 제29권5호
    • /
    • pp.231-238
    • /
    • 2017
  • HFO refrigerants have recently come to be regarded as promising alternatives to R134a for use in turbo chillers. This study provides results from experiments evaluating the film condensation heat transfer characteristics of HFO refrigerants R1234ze(E) and R1233zd(E) on smooth horizontal laboratory tubes. The experiments were conducted at a saturation vapor temperature of $38.0^{\circ}C$ with surface sub-cooling temperatures in the range of $3{\sim}15^{\circ}C$. We observe that the film condensation heat transfer coefficient decreases as surface sub-cooling temperatures increase. In the case of laboratory tubes with a diameter of 19.05 mm, the film condensation heat transfer coefficients of R1234ze(E) and R1233zd(E) were approximately 11% and 20% lower than those of R134a, respectively. Furthermore, our investigation of the effect of tube diameter on film condensation heat transfer coefficients, demonstrates an inverse relationship where the film condensation heat transfer coefficient increases as laboratory tube diameter decreases. We propose experimental correlations of Nusselt number for R1234ze(E) and R1233zd(E), which yield a ${\pm}20%$ error band.

핀튜브형 흡착탑에서 열 및 물질전달 수치해석 (Numerical Analysis of the Heat and Mass Transfer in a Fin Tube Type Adsorber)

  • 권오경;정재동
    • 설비공학논문집
    • /
    • 제25권8호
    • /
    • pp.457-463
    • /
    • 2013
  • Nowadays, adsorption chillers have been receiving considerable attention, as they are energy saving and environmentally benign systems. A fin tube type heat exchanger in which adsorption/desorption takes place is required with more compact size. The adsorption chiller is expected to have high energy efficiency in utilizing the waste heat exhausted from a process. The objectives of this paper are to scrutinize the effect of design parameters on the adsorption performance, especially the fin pitch of the fin tube, and to develop an optimal design fin tube heat exchanger in a silica gel/water adsorption chiller. From the numerical results, the fin pitch of 2.5 mm shows the highest adsorption rate, compared to other fin pitches, such as 5 mm, 7.5 mm and 10mm. Also, the adsorption rate is affected by the cooling water and hot water temperature.

가스흡수식 냉방기용 4성분계 작동매체의 물성 향상 연구 (A Study on Improvement of the Physical Properties of 4 Component Working Fluid in Gas Fired Absorption Chillers)

  • 백영순;오영삼;이용원;박달령;구기갑
    • 공업화학
    • /
    • 제10권3호
    • /
    • pp.400-406
    • /
    • 1999
  • 고효율 가스흡수식 냉방기를 위한 신 작동매체로 기존의 $LiBr-H_2O$ 용액에 $LiNO_3$, LiCl, LiI 성분을 첨가하여 4성분 용액을 제조하였다. 본 연구를 통하여 제조된 4성분계의 작동매체에 대한 용해도와 증기압을 측정하여 기존의 $LiBr-H_2O$계와 비교 분석하였으며, 이들에 대한 최적혼합 몰비를 각각 구하였다. 용해도 측면에서 $LiBr-LiNO_3-LiCl$계는 5:1:1~2, $LiBr-LiNO_3-LiCl$계는 5:1:1, LiBr-LiI-LiCl계의 경우 5:1:0.5~1로 나타났다. 한편 $LiBr-LiNO_3-LiCl-H_2O$계를 제외하고 모두 증기압이 $LiBr-H_2O$계에 비해 높게 나타났다. $LiBr-LiNO_3-LiCl-H_2O$계를 이용한 흡수성능 실험시 $LiBr-H_2O$계 보다 우수한 특성을 지녔다.

  • PDF

설비공학 분야의 최근 연구 동향 : 2010년 학회지 논문에 대한 종합적 고찰 (Recent Progress in Air-Conditioning and Refrigeration Research : A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2010)

  • 한화택;이대영;김서영;최종민;김수민;권영철;백용규
    • 설비공학논문집
    • /
    • 제23권6호
    • /
    • pp.449-469
    • /
    • 2011
  • This article reviews the papers published in the Korean Journal of Air-Conditioning and Refrigerating Engineering during 2010. It is intended to understand the status of current research in the areas of heating, cooling, ventilation, sanitation, and indoor environments of buildings and plant facilities. Conclusions are as follows. (1) Research trends of thermal and fluid engineering have been surveyed as groups of general thermal and fluid flow, fluid machinery, and new and renewable energy. Various topics were presented in the field of general thermal and fluid flow. Research issues mainly focused on the thermal reliability of axial fan and compressor in the field of fluid machinery. Studies on the design of ground source heat pump systems and solar chemical reactors were executed in the field of new and renewable energy. (2) Research works on heat transfer area have been reviewed in the categories of heat transfer characteristics and industrial heat exchangers. Researches on heat transfer characteristics included heat transfer in thermoelectric cooling/power generation systems, combined heat and power systems, carbon nano fluid with PVP, channel filled with metal foam and smoke ventilation in a rescue station of a railroad tunnel. Also the studies on flow boiling of R123/oil mixture in a plain tube bundle and R410A charge amount in an air cooled mini-channel condenser were reported. In the area of industrial heat exchangers, researches on plate heat exchanger, shell and tube heat exchanger, enthalpy exchanger, micro channel PCHE were performed. (2) Research works on heat transfer area have been reviewed in the categories of heat transfer characteristics and industrial heat exchangers. Researches on heat transfer characteristics included heat transfer in thermoelectric cooling/power generation systems, combined heat and power systems, carbon nano fluid with PVP, channel filled with metal foam and smoke ventilation in a rescue station of a railroad tunnel. Also the studies on flow boiling of R123/oil mixture in a plain tube bundle and R410A charge amount in an air cooled mini-channel condenser were reported. In the area of industrial heat exchangers, researches on plate heat exchanger, shell and tube heat exchanger, enthalpy exchanger, micro channel PCHE were performed. (3) Refrigeration systems with alternative refrigerants such as hydrocarbons, mixed refrigerants, and CO2 were studied. Performance improvement of refrigeration systems are tried applying various ideas of refrigerant subcooling, dual evaporator with hot gas bypass control and feedforward control. The hybrid solar systems combining the solar collection devices with absorption chillers or compression heat pumps are simulated and studied experimentally as well to improve the understanding and the feasibility for actual applications. (4) Research trend in the field of mechanical building facilities has been found to be mainly focused on field applications rather than performance improvements. Various studies on heating and cooling systems, HVAC facilities, indoor air environments and energy resources were carried to improve the maintenance and management of building service equipments. In the field of heating and cooling systems, papers on a transformer cooling system, a combined heat and power, a slab thermal storage and a heat pump were reported. In the field of HVAC facilities, papers on a cooling load, an ondol and a drying were presented. Also, studies on HVAC systems using unutilized indoor air environments and energy resources such as air curtains, bioviolence, cleanrooms, ventilation, district heating, landfill gas were studied. (5) In the field of architectural environment and energy, studies of various purposes were conducted such as indoor environment, building energy, renewable energy and green building. In particular, renewable energy and building energy-related researches have mainly been studied reflecting the global interest. In addition, many researches which related the domestic green building certification of school building were performed to improve the indoor environment of school.