• 제목/요약/키워드: Indentation pitch

검색결과 2건 처리시간 0.014초

소구경 전열관 내의 열전달촉진 형상변화에 따른 열전달 및 압력강하 특성에 관한 실험적 연구 (Experimental Study on the Characteristics of the Heat Transfer and the Pressure Drop inside the Small Diameter Tube with the Heat Transfer Enhancing Geometry)

  • 박찬우;진성민;정종수
    • 설비공학논문집
    • /
    • 제18권4호
    • /
    • pp.297-303
    • /
    • 2006
  • Friction and heat transfer coefficients were measured inside the corrugated tube using water as the working fluid. The test is performed for 16 tubes which outer diameter of tubes are 12.7 mm. These specifications are 4 indentation depths and 4 indentation pitches, respectively. The range of the water velocity inside the tube is from 0.5 to 3.0 m/s (8,500

스파이럴리 인덴티드 전열관 내부에서의 압력 강하 및 전열 특성에 관한 고찰 (Investigation on Characteristics of Pressure Drop and Heat Transfer in the Spirally Indented Tubes)

  • 김도형;김익생;김균석;유병훈;김춘동
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2001년도 춘계학술대회논문집D
    • /
    • pp.440-446
    • /
    • 2001
  • The pressure drop and heat transfer of the spirally indented tubes were measured and analyzed. Eight sample tubes of indentation depth 0.4, 0.7mm and indentation pitch 10, 14, 20, 26mm were used in this experimental tests. And all the tubes have same outer diameter of 16mm, and same indentation start number of I. Air was used as the internal fluid from 10000 to 50000 for Reynolds Number. The friction factors and heat transfer coefficients have increased when indentation depths increase and indentation pitches decrease. Finally, the correlations were made between the effect of the tube geometry and characteristics of tubes for the pressure drop and heat transfer.

  • PDF