• Title/Summary/Keyword: Impulse ground impedance

Search Result 44, Processing Time 0.03 seconds

Behaviors of Impulse Ground Impedances Associated with the Current Injection Point in a Ground Rod (봉상 접지전극에시 전류유입위치에 따른 임펄스 접지임피던스의 특성)

  • Lee, Bok-Hee;Jeong, Dong-Cheol;Lee, Su-Bong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.1
    • /
    • pp.94-100
    • /
    • 2005
  • This paper presents the behaviors of transient and effective impulse impedances of a long ground rod associated with the current injection points. The laboratory test for the time domain performance of actual-sized model ground rod subjected to a lightning stroke current has been carried out The transient ground impedances of long ground rods under impulse currents were higher than the ground resistance. Both of the ground resistance and the effective impulse ground impedance decrease with increasing the length of the ground rods. Also, the effective impulse ground impedances are significantly increased in fast rise time ranges. The reduction of the ground resistance is decisive to improve the impulse impedance characteristics of grounding systems. When the test current is injected at the bottom of ground rod, the oscillating pulses with high frequency are included on the wave front of ground rod potential and the effective impulse impedances are higher than any other cases.

Modeling of Impedance Characteristics of Grounding Electrode for Distribution Line Pole (배전전주의 봉상 접지전극 형태별 임피던스 특성의 모델링)

  • Shim, Keon-Bo;Kim, Kyung-Chul;Lee, Hyung-Soo;Park, Jae-Duck;Choi, Jong-Kee;Park, Sang-Man
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.694-696
    • /
    • 2005
  • Although DC ground resistance is a good index of grounding performance for grounding electrodes, it does not reflect the grounding performance during transient state. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute index due to its dependence on impulse current shape. In this paper, ground impedance characteristics of ground electrodes has been measured in frequency domain ranging from 1 Hz to hundreds of kHz. Equivalent circuit models and transfer function models of the ground rod have been identified from the measured values of ground impedance in frequency domain.

  • PDF

Effects of Length of Down Conductor on Transient Ground Impedance (인하도선 길이에 따른 과도접지임피던스 특성)

  • Lee, B.H.;Jeong, D.C.;Lee, S.B.;Lee, T.H.;Jung, H.U.;Lee, K.S.;Lee, S.C.
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2235-2237
    • /
    • 2005
  • This paper presents the transient impedance behaviors of grounding systems to lightning impulse current. The potential rise and effective impulse ground impedance of the test grounding electrodes were measured as a function of the rise time of impulse currents and lengths of down conductor. The transient ground impedances strongly depend on the configuration and size of grounding electrodes, the impulse current shapes and lengths of down conductor, and the inductance of reduce of grounding electrode inductance is an important factor to improve the transient ground impedance.

  • PDF

Transient Ground Impedance of Small-sized Ground Electrode considering Underground Discharge in Frozen Soil (동결 토양에서 지중방전을 고려한 소규모 전극의 과도접지임피던스 특성)

  • Lee, Tae-Hyung;Cho, Sung-Chul;Eom, Ju-Hong;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.05a
    • /
    • pp.324-327
    • /
    • 2009
  • This paper presents the transient impedance in a discharge region when high voltage lightning impulse is applied to small-sized ground electrodes in frozen soil. For a realistic analysis of ionization characteristics near the ground electrode in the soil, ground rod installed outdoors and high voltage impulse voltage generator were used. From the analysis of response voltage and current flowing ground electrode to earth, it was verified that the ionization near the ground electrode contributes to reduction of ground impedance and limits the ground potential rise effectively under high impulse voltage.

  • PDF

Transient Ground Impedance of Small-sized Needle-rod Electrodes due to Underground Soil Discharge (토양의 지중방전에 따른 소형 침봉전극의 과도접지임피던스)

  • Lee, Tae-Hyung;Cho, Sung-Chul;Eom, Ju-Hong;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.10a
    • /
    • pp.211-215
    • /
    • 2008
  • This paper deals with the transient ground impedance of small-sized needle-rod installed in a test field, Impulse voltage generator was used to inject lightning impulse on a ground electrode and modified fall-of potential method was proposed to measure the high ground potential rise. Transient ground impedance was analysed with impedance curve and I-V curve as respects the resistivity of soil. Soil ionization near the ground electrode is activated in high resistivity soil and have an effect on the reduction of transient ground impedance significantly.

  • PDF

Characteristics of Transient Ground Impedance of a Scaled Grounding Grid on the High Current Impulse (대전류 임펄스에 대한 소규모 메쉬전극의 과도접지임피던스 특성)

  • Lee, Tae-Hyung;Cho, Sung-Chul;Eom, Ju-Hong;Yoo, Yang-Woo;Lee, Bok-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.1418_1419
    • /
    • 2009
  • This paper presents the transient impedance when high current impulse up to 5 kA is applied to a scaled grounding grid in test field. For a realistic analysis of transient impedance on the high current impulse in the ground systems, grounding electrode installed outdoors and impulse current generator was used. The results were discussed based on its voltage and current trace, impulse impedance and V-I curve.

  • PDF

Comparative Analysis on Ground Impedance for a Carbon Block and a Copper Rod (탄소블록과 동봉의 접지임피던스 비교 분석)

  • Seo, Jae-Suk;Park, Hee-Chul;Kil, Gyung-Suk;Oh, Jae-Geun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.26 no.6
    • /
    • pp.472-477
    • /
    • 2013
  • This paper carried out the comparative analysis on ground impedance of a carbon block and a copper rod. Two types of grounding electrode were compared ; a carbon block (L : 1 m, ${\Phi}$ : 245 mm) buried at a depth of 0.8 m and a three-linked copper rod (L : 1 m, ${\Phi}$ : 10 mm) of equilateral triangles with 1 m spacing. Ground impedance depending on applied current source was evaluated by the application of a sine wave current with 60 Hz ~ 3.5 MHz, a fast-rise pulse with rising time of 200 ns, a standard lightning impulse of $8/20{\mu}s$ and a 600 Hz square wave. Ground impedance for both electrodes were almost the same value below 100 kHz, and increased rapidly afterwards. The maximum ground impedance appeared $400{\Omega}$ at around 1.5 MHz. Ground impedance of the carbon block was lower at the square wave and was higher at fast-rise pulse than that of the copper rod. Also, ground impedance as ages showed no difference for the last 8 months. From the results, it is likely that ground performance for both electrodes shows no difference against commercial frequency and lightning impulse current, while the copper rod shows better performance against a fast-rise pulse with rise-time of a few hundred ns.

Effective impulse impedances of a deep-driven ground rod combined with other grounding electrodes (다른 형상의 접지전극에 접속된 심매설 접지전극의 실효임펄스임피던스)

  • Lee, Bok-Hee;Chang, Keun-Chul;Lee, Su-Bong
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.565-569
    • /
    • 2004
  • This paper deals with the characteristics of potential rise and effective impulse impedance of deep-driven ground rods that are used in high resistivity soil or in confined places such as downtown. Also the effects of the impulse and fault currents on the deep-driven ground rods combined with different type grounding electrodes like as mesh grids and counterpoises are described. The $8/20{\mu}s$ impulse current and other wave currents with different rise times are injected into the test ground rod and the effective impedances are examined. The most effective way to obtain the fine transient impedance behaviors of deep-driven ground rods is to reduce the inductive component of grounding electrode systems combined with other ground electrodes.

  • PDF

Characteristics of Transient Grounding Impedance under Surge Currents (서지전류에 대한 과도접지임피던스의 특성)

  • Lee, Deok-Hui;Park, Jong-Sun
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.48 no.11
    • /
    • pp.717-723
    • /
    • 1999
  • The transient characteristics of grounding systems play a major role in the protection of power equipments, electronic circuits and info-communication facilities against surges which arise from lightning or ground faults. Electronic devices are very weak against lightning surges injected from grounding systems and can be damaged. The malfunction and damage of electronic circuits bring about bad operation performances, a lot of economical losses, and etc. Therefore, in order to obtain the effective protection measure of electronic devices from overvoltages and lightning surges, the analysis of the transient grounding impedances in essential. One of this work is to examine the transient behaviors of grounding impedances under steplike currents for various grounding systems. And the other of this work is to evaluate the transient behaviors of a grid with rods under impulse currents and to investigate the effect of grounding lead wire. Transient grounding impedances of a grid with rods under impulse current waves have been measured as a parameter of the length of the grounding leads. Z-t, Z-i and V-i curves of transient grounding impedance under impulse current waveforms have been measured and analyzed. It was found that the grounding impedance gives the inductive, resistive and capacitive aspects under steplike current. Transient grounding impedance characteristics were very different with shapes, geometries of ground electrodes. Also, they were dependent on the waveform and magnitude of impulse current.

  • PDF

Charicteristics of Stationary and Transient Ground Impedance of Large-Scale Grounding Piles (임펄스 전류에 대한 대규모 접지시스템의 정상상태 및 과도상태의 접지임피던스 특성)

  • Lee, B.H.;Lee, S.C.;Park, J.S.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2296-2298
    • /
    • 1999
  • The stationary ground resistance and the transient ground impedance of grounding system are very important parameters in the field of lightning and surge protection. But, it is very difficult to obtain correct values of them in large-scale grounding system. In this paper, the stationary and transient ground impedances of a large-scale grounding system have been measured and analyzed under impulse currents. In order to obtain correct values of them, we have described Z-v(impedance vs ground potential rise) distributions and Z-t waveforms. The transient ground impedance of 36 [m] long three-parallel grounding piles have showed the inductive aspects and the hysterisis region under impulse currents.

  • PDF