• Title/Summary/Keyword: Ice storage tank

Search Result 57, Processing Time 0.023 seconds

Study on Performance of Heat Pump using a subcooled refrigerant (냉매과냉각에 의한 열펌프의 성능향상에 관한 연구)

  • 박승준
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2000.05a
    • /
    • pp.159-164
    • /
    • 2000
  • In this paper a new type refrigerant liquid subcooling system which adopts ice storage system is proposed. And the cycle characteristicso of a new system was investigated. Since this system subcools a refrigerant in the daytime using the ice storaged by electric power in the night it is high efficiency heat pump system which have the merit of ice storage system and possible to improve the performance of the heat pump. The running to storage the ie was carried out for 10 hours in the night and th evaporating temperature was set on $-5^{\circ}C.$ Subcooling operation stayed as 430^{\circ}C$ subcooling degree and perfomed till the water in the IST(Ice storage tank) was reached $12^{\circ}C$. The experimental result showed that a new system was superior to the existing refrigeration system generally. The total cooling capacity of a new system was about 11% higher than that of the existing refrigeration system. And the COP of a new system was improved by 22% compared to the existing refrigeration system.

  • PDF

The Performance Characteristics of Heat Pump Using the Refrigerant Subcooling (냉매 과냉각을 이용한 열펌프 시스템의 성능 특성)

  • Roh, Geon-Sang;Son, Chan-Ghyo
    • Transactions of the Korean hydrogen and new energy society
    • /
    • v.18 no.4
    • /
    • pp.413-421
    • /
    • 2007
  • In this paper, the performance characteristics of heat pump system using a new refrigerant subcooling system designed for the study, are introduced. The new heat pump system have the ice storage tank at the outlet of condenser. The experimental apparatus is a well-instrumented water/water heat pump which consisted of working fluid loop, coolant loop, and ice storage tank. The experiment parameters of subcooling ranged as the evaporating temperature from $-5^{\circ}C$ to $8^{\circ}C$, the condensing temperature from $30^{\circ}C$ to $35^{\circ}C$. The test of the ice storage was carried out at evaporating temperature of $-10^{\circ}C$ and the ice storage mode is Ice-On-Coil type. The working fluid was R-22 and the storage materials were city-water. The test results obtained were as follows; The refrigerant mass flow rate and compressor shaft power were unchanged by the degrees of subcooling, that is, they were independent of degrees of subcooling. The cooling capacity of the new heat pump system increase as the evaporating temperature and subcooling degrees increase and is higher by $25{\sim}30%$, compared to the normal heat pump system. The COP of the new heat pump system increases as the degrees of subcooling and evaporating temperature increase and is higher by 28% than that of the normal heat pump system.

An Experimental Study on an Ice Storage System by a Two-Phase Closed Thermosyphon (2상 밀폐 서모사이폰을 이용한 빙축열 시스템의 성능)

  • Kyung, I.S.;Ro, S.T.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.3 no.2
    • /
    • pp.87-96
    • /
    • 1991
  • A two-phase closed thermosyphon is applied to an ice storage system. The thermosyphon is used to freeze the water in a storage tank. The experiment has been performed to investigate the effects of the important parameters such as the quantity of the fluid filled with, the ratio of the length of the evaporator to the condenser, and the temperature and the mass flow rate of the brine. It is found that the higher thermal performance of the thermosyphon is obtained as the ratio of the length of the evaporator section to that of the condenser section is decreased and the temperature of the brine is lowered. The increase of the quantity of the working fluid also favors the performance of the system. The experimental data can be utilized for the basic design of ice storage systems with thermosyphons.

  • PDF

A Study on Optimal Operation of Cooling System Using Dynamic Programing (동적 계획법을 이용한 냉방시스템 최적운전에 관한 연구)

  • Han, Kyu-Hyun;Yoo, Seong-Yeon;Lee, Je-Myo;Lee, Il-Su
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.1061-1064
    • /
    • 2009
  • The objective of this study is to find the optimal operational planning of the hybrid cooling system, which is combined by ice storage system and the absorption chiller. The optimization technique used in this study is dynamic programming. The objective function is summed cost during a day including charge and discharge periods of ice storage system and operation time of absorption chiller. Assuming that initially ice storage tank is stored fully and the cooling load is perfectly predicted for the operational planning. This method provides the most efficient and economic combination of equipment operational planning for cooling with respect to energy consumption cost.

  • PDF

Laboratory Test on Total Flow Control for Ice Slurry System with Inverter Fed Motor Pump (인버터구동 모터펌프를 이용한 아이스 슬러리형 빙축열시스템 전유량제어 운전시험)

  • Choi, Byoung-Youn;Lee, Kyoung-Ho;Lee, Sang-Ryoul;Lee, Hak-Joo
    • Proceedings of the KSME Conference
    • /
    • 2001.06d
    • /
    • pp.260-265
    • /
    • 2001
  • This paper describes total flow control of an ice slurry system for pump energy saving. Similar turbo machinery has a characteristic that input power ratio is proportional to the three time of revolution speed ratio. To reduce the energy cost of brine pump in ice slurry storage systems, inverter is adapted instead of 3-way valve to control the speed of brine pump motor. One type of cooling load profile was used as driving load of the system, generated by a boiler and warm water storage tank. As results of the laboratory test, energy consumption and cost of the pump were reduced by 11.4%.

  • PDF

An Evaluation of Chiller Control Strategy in Ice Storage System for Cost-Saving Operation (운전비 절감을 위한 빙축열시스템 냉동기 운전기법 평가)

  • Lee, Kyoung-Ho;Choi, Byoung-Youn;Lee, Sang-Ryoul
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.2
    • /
    • pp.97-105
    • /
    • 2008
  • This paper presents simulated and experimental test results of optimal control algorithm for an encapsulated ice thermal storage system with full capacity chiller operation. The algorithm finds an optimal combination of a chiller and/or a storage tank operation for the minimum total operation cost through a cycle of charging and discharging. Dynamic programming is used to find the optimal control schedule. The conventional control strategy of chiller-priority is the baseline case for comparing with the optimal control strategy through simulation and experimental test. Simulation shows that operating cost for the optimal control with chiller on-off operation is not so different from that with chiller part load capacity control. As a result from the experimental test, the optimal control operation according to the simulated operation schedule showed about 14 % of cost saving compared with the chiller-priority control.

An experimental study on ice slurry creation by injection of an aqueous solution (수용액 분사에 의한 아이스 슬러리의 제조에 관한 실험적 연구)

  • Lee, Yong-Koo;Oh, Cheol
    • Journal of Navigation and Port Research
    • /
    • v.34 no.1
    • /
    • pp.71-75
    • /
    • 2010
  • This study is experimented to observe an influence of experimental conditions on production characteristics of slurry ice by injection operating water to cooling plate. And at this experiment it used ethylene glycol-water solution and the concentration is 10 to 20wt%. The experimental apparatus was constructed of ethylene glycol-water solution and slurry ice storage tank, brine tank, pumps for ethylene glycol-water solution and brine circulating, a mass flow-meter, data logger for fluid temperature measuring and a vertical circular tube with single copper plate as test section. The experiments were carried out under various conditions, with mean velocity of fluid at the entry ranging from 1.0 to 2.0m/s and the cooling temperature of $-17^{\circ}C$ to $-10^{\circ}C$.

A Field Application Case of Direct Ice Slurry Transporting System for District Cooling (지역냉방용 직접순환식 아이스슬러리 시스템의 현장적용 사례)

  • Yoo, Ho-Seon;Lee, Sang-Hoon;Lee, Yoon-Pyo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.9
    • /
    • pp.496-504
    • /
    • 2009
  • In order to investigate the feasibility of a direct ice slurry transporting system for the purpose of district cooling, a case study of field application is performed. The research aims include the field measurement of ice packing factor, the performance of coldness delivery, and the branching characteristics of ice slurry. Two representative types of pipe branch are dealt with in this work. For the slurry flow with ice volume fraction of 0.16 or less, the pipe blocking due to aggregation is not observed. Based on the time-wise variation of temperature in the storage tank, a calculating method of ice packing factor is newly developed, which seems to be useful when the brine concentration is unknown. It is confirmed that the mass flow rate of ice slurry per unit cooling load is markedly reduced with increasing the ice content. The pumping power also decreases, but remains unchanged for high ice fractions. The distribution of ice particle before and after branching shows a good uniformity within the range of 5% difference, but yields a unique trend depending on the flow rate.

Performance Enhancement of the Heat Pump Using the Refrigerant Subcooling System (냉매 과냉각 시스템을 이용한 열펌프의 성능향상에 관한 연구)

  • 손창효;윤찬일;박승준;이동건;오후규
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2001.05a
    • /
    • pp.106-111
    • /
    • 2001
  • The performance characteristics of heat pump system using the new refrigerant subcooling system were investigated. The new heat pump system has the ice storage tank to accumulate the latent heat of the refrigerant during the night-time. The heat is released to subcool the saturated refrigerant liquid at the outlet of a condenser in the daytime. The experimental apparatus is a well-instrumented heat pump which consisted of a refrigerant loop and a coolant loop. The test sections(condenser and evaporator) were made of tube-in-tube heat exchanger with the horizontal copper tube of 12.7[mm] outer diameter and 9.5[mm] inner diameter. The evaporating temperatures ranged from $-5[^{\circ}C]$ to $0[^{\circ}C]$ and the subcooling degrees of the refrigerant varied from $15[^{\circ}C]$ to $25[^{\circ}C]$. The test of the ice storage was carried out at evaporating temperature of $-10[^{\circ}C]$ and the ice storage mode is an ice-on-coil type. The main results were summarized as follows ; The refrigerant mass flow rate and compressor shaft power of the heat pump system were independent of the subcooling degrees. The cooling capacity o the heat pump system increases as the evaporating temperature and subcooling degree increases. The cooling capacity of the heat pump system is about 25 to 30% higher than that of normal heat pump system. The COP of the heat pump system which subcooled the refrigerant liquid at the outlet of the condenser is about 28% higher than that of the normal heat pump system.

  • PDF

Flow Analysis and an Experimental Study on Formation of Slurry Ice in the Reversing Flow Layer (역전 유동층 내의 유동해석 및 슬러리아이스 생성에 관한 연구)

  • Oh, Cheol;Choi, Young-Gyu
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.35 no.4
    • /
    • pp.421-428
    • /
    • 2011
  • Thermal energy storage(TES) cooling system using cheaper electricity of off-peak time has been applied to relieve a significant portion of the peak demand of electricity during the daytime in summer. Slurry ice type thermal energy storage cooling system is one kind of more efficient ice-thermal energy storage cooling system than Ice-on-Coil type or Encapsulated type TES cooling system, even though, which are more popular TES system. This experimental study was carried out to observe flow pattern and formation of slurry ice in reversing flow layer to improve efficiency of heat transfer between fluid and freezing tube and to disturb ice adhesion on tube surface. The reversing flow layer was made by using reversing materials in heat exchanger section(test section) to disturb ice adhesion. At this experiment, styrofoam balls and poly propylene balls were used as reversing materials, and a 20wt% solution of ethylene glycol was used as reversing flow layer. The experimental apparatus was constructed of the test section for making/storing slurry ice, the brine tank, pumps for circulating of a 20wt% solution of ethylene glycol and brine, a flow-meter, a data logger for measuring the temperature. The experiments were carried out under various conditions, with volumetric flow rate, ball filling rate and air filling rate.