• Title/Summary/Keyword: Ice slurry

Search Result 92, Processing Time 0.023 seconds

A Control of Ice Packing Factor of Ice Slurry in a Pipe using IPF Controller (IPF 조절기를 이용한 배관내 아이스 슬러리의 빙충전율 제어)

  • Kwon, Jae-Sung;Lee, Yoon-Pyo;Yoon, Seok-Mann
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.1105-1110
    • /
    • 2008
  • An experimental study was performed to control Ice Packing Factor (IPF) of ice slurry in a pipe in a real time. This paper presented the concept that IPF can be adjusted by the amount of the solution contained to ice slurry. Based on this concept, we designed IPF controller consisting of the outlet tube providing ice slurry and the upper tube discharging only a solution through holes, and investigated the technical validity and efficiency of the controller experimentally. As a result, the original proposed IPF controller could not control IPF of ice slurry in a pipe. This is because an ice of ice slurry was drained out into not only the outlet but also the upper of the controller due to the size of the holes relatively large compared to the ice particle. Therefore, we changed the hole size of IPF controller surface using fine meshes and then, observed that IPF in a pipe was increased by $4{\sim}7$ percent when the hole size was $80{\mu}m$ and less.

  • PDF

Continuous Ice Slurry Production and Control of Ice Packing Factor in a Pipe for the District Cooling (지역냉방을 위한 아이스슬러리의 연속제조 및 배관내 빙충전율 조절)

  • Kwon, Jae-Sung;Lee, Yoon-Pyo;Lee, Sang-Hoon;Yoo, Ho-Seon;Yoon, Seok-Mann
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.12
    • /
    • pp.825-832
    • /
    • 2008
  • The ice slurry maker which can produce the ice slurry well for the ice particle in-flowing condition was revised. We removed the stagnant region at the top of the ice slurry maker, and IPF 40% could be realized. The IPF controller with 6 mm diameter holes at the bottom was designed. But the IPF controller with only 6 mm diameter holes could not control IPF in a pipe. This is because the ice particles at ice slurry flow exist homogeneously not only at the upper part but also at the bottom part. We changed the hole size of IPF controller surface using fine meshes and then, IPF in a pipe was increased by 70% when the hole size was $80{\mu}m$ and less.

A Field Application Case of Direct Ice Slurry Transporting System for District Cooling (지역냉방용 직접순환식 아이스슬러리 시스템의 현장적용 사례)

  • Yoo, Ho-Seon;Lee, Sang-Hoon;Lee, Yoon-Pyo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.9
    • /
    • pp.496-504
    • /
    • 2009
  • In order to investigate the feasibility of a direct ice slurry transporting system for the purpose of district cooling, a case study of field application is performed. The research aims include the field measurement of ice packing factor, the performance of coldness delivery, and the branching characteristics of ice slurry. Two representative types of pipe branch are dealt with in this work. For the slurry flow with ice volume fraction of 0.16 or less, the pipe blocking due to aggregation is not observed. Based on the time-wise variation of temperature in the storage tank, a calculating method of ice packing factor is newly developed, which seems to be useful when the brine concentration is unknown. It is confirmed that the mass flow rate of ice slurry per unit cooling load is markedly reduced with increasing the ice content. The pumping power also decreases, but remains unchanged for high ice fractions. The distribution of ice particle before and after branching shows a good uniformity within the range of 5% difference, but yields a unique trend depending on the flow rate.

Effect on the Adhesion of Ice Slurry by the Characteristic of Cooling Surface (냉각면 성상이 빙부착에 미치는 영향)

  • Seung Hyun;Hong Hi Ki;Kang Chae Dong
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.2
    • /
    • pp.183-190
    • /
    • 2005
  • In the process of ice-slurry making, ice adhesion on cooling wall or in narrow flow Path disturbs continuous ice formation. In this study, the effect on the ice adhesion to cooling surface by some freezing experiments was investigated, quantitatively. Three types of solutions were frozen in various coating vessels with stirring. In the experiment, the ice adhesion between cooling wall and Ice-slurry was evaluated by measuring stirring power. From the result, the stirring power of slurry mixture in PTFE-coating vessel was smaller than those in PE-coating, PFA-coating and bare SUS vessel. Especially, in EG H PG 1.S/ HD 1.5 mass$\%$ solution, the stirring power in the PE-coating vessel was smaller than that in the PFA-coating or SUS vessel.

The Experimental Study on the Heat Transfer Characteristics of Ice Slurry Generator Using Air Cylinder (공압구동형 제빙기의 열전달 특성에 관한 실험적 고찰)

  • Kim, Min-Jun;Kim, Joung-Ha;Yun, Jae-Ho;Park, Il-Hwan;Lee, Kyu-Chil
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.11
    • /
    • pp.743-750
    • /
    • 2007
  • In this study, ice slurry generator using air cylinder was designed and manufactured to investigate the heat transfer characteristic of the ice slurry generator. The ice slurry generator has the same shape as the shell-and-tube type heat exchanger. Refrigerant is flowing in the shell side and ethylene glycol solution in the tube side. The experiment was conducted on performance of ice slurry generator using air cylinder with standard condition and the results are plotted on the time scale. The experimental tests on the various concentration of ethylene glycol solution, the various solution velocity in the tube side and the various tube size have been carried. For the above experimental conditions, ice making characteristics of the ice slurry generator are evaluated in terms of the overall heat transfer coefficient. And the experimental results show that the overall heat transfer coefficient of the system is increased as the tube size and the concentration of ethylene glycol decreases.

A Study on the Measuring Method of Ice Slurry Viscosity Using the Falling Sphere Viscometer (낙구식 점도계를 이용한 아이스슬러리의 점도측정에 관한 연구)

  • Kim, Myoung-Jun;Yu, Jik-Su;Lim, Jae-Keun;Choe, Soon-Youl
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.8
    • /
    • pp.593-598
    • /
    • 2007
  • The present study has dealt with the measuring method of ice slurry viscosity using falling sphere viscometer. The experimental apparatus was composed by test section and high-speed video system. And the spheres used in this study were alumina and glass. The main parameters were ice packing factor (IPF) and falling velocity of sphere so the acquired results were discussed for these parameters. The viscosity of ice slurry was calculated by using measured falling velocity and moving distance at instantaneous time and the Stokes hypothesis was used for this calculation. It was clarified that possible measuring range was $IPF\;=\;0.06{\sim}0.14$ of this type of measuring device and measuring method. In addition, it was clarified that the viscosity of ice slurry increased to increase of ice packing factor (IPF) of ice slurry.

Ice Slurry Formation of a Solution in a Pressurized Plate Heat Exchanger (가압 판형 열교환기에 의한 수용액의 아이스슬러리 생성)

  • Lee Dong-Gyu;Kim Byung-Seon;Peck Jong-Hyeon;Hong Hi-Ki;Kang Chae-Dong
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.7
    • /
    • pp.596-602
    • /
    • 2006
  • Ice adhesion and blockage problems have been issued in continuous ice slurry making process. So we composed continuous ice slurry making device using a commercial small plate heat exchanger (PHX), and investigated character of ice formation. An experiment of ice formation was peformed with an aqueous solution of ethylene glycol 7 mass%. In the experiment, the effect of the pressurization on ice slurry formation during the cooling process was investigated. The pressurization test for the aqueous solution was performed by setting valves at the PHX inlet and outlet. At the results, the time of continuous ice formation increased as the pressure of the plate heat exchanger increased for cooling temperature of $-5^{\circ}C$. Also continuous ice formation at the cooling temperature of $-7^{\circ}C$ showed a possibility. It was found that the pressurization may contribute to suppress the dissolution of supercooled aqueous solution in the PHX.

Ice-slurry Generation of Ice Thermal Energy Storage System using Ultrasonic Vibration (초음파 진동을 이용한 빙축열 시스템의 아이스 슬러리 생성 연구)

  • Byon, Sung-Kwang;Gong, Chun-Su;Kim, Nam Woong
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.14 no.2
    • /
    • pp.578-584
    • /
    • 2013
  • Ice slurry that is a mixture of fine ice crystals and liquid water is a widely used working fluid in the ice thermal energy storage system due to its flowability and large latent heat of fusion. Generally ice slurry is made from supercooled water. But the excessive supercooling causes the water to freeze even worse to block the pipe. Additionally large degree of supercooling of water degrades the efficiency of the ice thermal energy storage system. Therefore the effective method to control the phase change from supercooled water to ice slurry is needed. In this paper we experimentally studied a novel method to generate the ice slurry from the supercooled water using the ultrasonic vibration. It was found that the cavitation impact of supercooled water by ultrasonic vibration can help the generation of ice slurry.

A study on ice-slurry production by water spray (수분무에 의한 아이스 슬러리 생성에 관한 연구)

  • Kim, B.S.;Lee, Y.P.;Yoon, S.Y.;Lee, J.H.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.9 no.2
    • /
    • pp.134-143
    • /
    • 1997
  • A theoretical and experimental study has been performed to investigate the characteristics of ice-slurry product. By diffusion-controlled model, the possibility of ice slurry has been theoretically anticipated. The water vapor evaporated from the surface of droplets is extracted continuously from the chamber by a vacuum pump. The droplet diameter was measured by silion immersed method. The ice slurry has been obtained by spraying droplets of ethylene-glycol aqueous solution in the chamber where pressure is maintained under the triple point of water. The droplet of which the diameter is $300{\mu}m$, and the initial temperature is $20^{\circ}C$, was changed into ice particle within the chamber of which the height is 1.33m.

  • PDF

A Study on Ice Slurry Production by Water Spray

  • Kim, Byeong-Sun;Lee, Yoon-Pyo;Yoon, Seong-Young;Lee, Jin-Ho
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.6
    • /
    • pp.45-55
    • /
    • 1998
  • A theoretical and experimental study is performed to investigate the characteristics of ice slurry product. By diffusion-controlled evaporation model the possibility of ice slurry is theoretically anticipated. The water vapor evaporated from the surface of droplets is extracted continuously from the chamber by a vacuum pump. The droplet diameter is measured by silicon immersion method. The ice slurry is obtained by spraying droplets of ethylene glycol aqueous solution in the chamber where pressure is maintained under the triple point of water. The droplet with the diameter of 300 $\mu\textrm{m}$and the initial temperature of 2$0^{\circ}C$ was changed into ice particle within the chamber of 1.33m in height.

  • PDF