• 제목/요약/키워드: IEEE Std. C37.011

검색결과 1건 처리시간 0.015초

EMTP-RV를 이용한 대용량 전기설비의 차단기 TRV에 관한 연구 (A Study on the Circuit Breaker Transient Recovery Voltages on Large Commercial Customer using EMTP-RV Program)

  • 조계술;최홍규
    • 조명전기설비학회논문지
    • /
    • 제25권10호
    • /
    • pp.59-66
    • /
    • 2011
  • In electric power system, the circuit breaker is not operated when the higher voltage then the rated TRV(transient Recovery Voltage) appeared in the circuit breaking, The TRV of a circuit breaker means the characteristics of reignition by the arc between two poles. and is decided by the value of connecting Impedance. In this paper we of carried out many kinds of experiments varying the types of bus, the types of installation, the length of installation between 22.9 [kV] level circuit breaker and MTR in general 154/22.9[kV] system, We also simulated the characteristics of TRV using EMTP-RV program. The suitability of TRV in assessed by Uc, RRRV(Rate of Rise of Recovery Voltage) which are defined by the international guide, IEC62271-100. The values of RRRV gained from the cable-made bus are 590[%] lesser than those from the NSPB-made bus respectively. So the triangled type is more rational in the aspect of TRV.