• Title/Summary/Keyword: Heat transfer tube

Search Result 1,313, Processing Time 0.023 seconds

An Experimental Study on Heat Transfer Characteristics of a Ripple Tube (RIPPLE TUBE의 열전달(熱傳達) 특성(特性)에 관(關)한 실험적(實驗的) 연구(硏究))

  • Choi, Seong Sung
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.2 no.4
    • /
    • pp.316-326
    • /
    • 1990
  • The measurements of heat transfer and pressure drop were performed on ripple tube with air flow. The results with the tube were compared with the performance of smooth tube. The enhancements in heat transfer coefficient for ripple tube, being compared with smooth tube, was ranged from 7.4 to 39 percent. The local Nusselt number for the inner fin tube, being compared with that for smooth tube, varied from 7.4% to 39%, while the corresponding increase in friction factors were 4.1 to 8.1%. One of the most direct indications of Nusselt number of ripple tube is given as following equation: $$Nu=0.061Re^{0.75}Pr^{0.4}(Tb/Tw)^{0.5}$$ We can see that Nusselt number for ripple tube in this experiment is consistent with the theoretical one taken from Walkinson's equation at Reynolds number range from 8,000 to 20,000.

  • PDF

A Study on the Characteristics of Evaporative Heat Transfer for Carbon Dioxide in a Horizontal Tube (수평원관 내 이산화탄소의 증발열전달 특성 연구)

  • Cho, E.S.;Yoon, S.H.;Kim, M.S.
    • Proceedings of the KSME Conference
    • /
    • 2000.04b
    • /
    • pp.104-107
    • /
    • 2000
  • Evaporative heat transfer characteristics of carbon dioxide has been investigated. Experiment has been carried out for seamless stainless steel tube with outer diameter of 9.55 mm and inner diameter of 7.75 mm. Direct heating method is used for supplying heat to the refrigerant was uniformly heated by electric current which was applied to the tube wall. The saturation temperature of refrigerant is calculated from the measured saturation pressure by using an equation of state. Inner wall temperature was calculated from measured outer wall temperature, accounting for heat generation in the tube and heat conduction through the tube wall. Mass Quality of refrigerant was calculated by considering energy balance in the preheater and the test section. Heat fluxes were set at 12, 16, 20, 23, and $27kW/m^2$, mass fluxes were controlled at 212, 318, 424, and $530 kg/m^2s$, and saturation temperature of refrigerant were adjusted at 0, 3.4, 6.7 and $10.5^{\circ}C$. From this study, heat transfer coefficients of carbon dioxide have been provided with respect to quality for several mass fluxes, heat fluxes. Finally, the experimental results in this study are compared with the correaltion by Gungor and Winterton(1987).

  • PDF

Two-dimensional Heat Conduction and Convective Heat Transfer a Circular Tube in Cross Flow (원관 주위의 2차원 전도열전달과 국소 대류열전달)

  • Lee Euk-Soo
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.29 no.1
    • /
    • pp.25-33
    • /
    • 2005
  • When a circular tube with uniform heat generation within the wall was placed in a cross flow, heat flows by conduction in the circumferential direction due to the asymmetric nature of the fluid flow around the perimeter of the circular tube The circumferential heat flow affects the wall temperature distribution to such an extent that. in some cases, significantly different results may be obtained for geometrically similar surfaces. In the present investigation, the effect of circumferential wall heat conduction is investigated for forced convection around circular tube in cross flow of air and water Two-dimensional temperature distribution $T_w(r,{\theta})$ is calculated through the numerical analysis. The difference between one-dimensional and two-dimensional solutions is demonstrated on the graph of local heat transfer coefficients. It is observed that the effect of working fluid is very remarkable.

Experimental study of performance characteristics of various fin types for fin-tube heat exchanger (휜-관 열교환기에 있어서 각종 휜 형상의 성능 특성에 관한 실험적 연구)

  • Yoon, Baek;Kim, Young-Saeng;Park, Hwan-Young;Park, Hyun-Yeon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.4
    • /
    • pp.484-491
    • /
    • 1999
  • Air side heat transfer and pressure drop for ø9.52 fin-tube heat exchanger with various types of slit and louver fins were measured, and compared with wave-slit fin. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively. Actual heat exchanger was tested using water, and the tests were performed for 2 row heat exchangers with 3 different fin spacings, 1.3, 1.5 and 1.7mm. The overall performance of the enhanced fins was evaluated by comparing heat transfer coefficient with respect to fan power.

  • PDF

Experimental Study of Performance Characteristics of Various Fin Types for Fin-Tube Heat Exchanger

  • Youn, Baek;Kim, Young-Saeng;Park, Hwan-Young;Park, Hyun-Yeon
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.8 no.2
    • /
    • pp.29-38
    • /
    • 2000
  • Air side heat transfer and pressure drop for f 9.52 fin-tube heat exchanger with various types of slit and louver fins were measured, and compared with wave-slit fin. Longitudinal and transverse tube spacings of the heat exchangers are 21.65 mm and 25mm respectively. Actual heat exchanger was tested using water, and the tests were performed for 2 row heat exchangers with 3 different fin spacings, 1.3, 1.5 and 1.7 mm. The overall performance of the enhanced fins was evaluated by comparing heat transfer coefficient with respect to fan power

  • PDF

Experimental Study on In-Tube Condensation Heat Transfer Characteristics of Helically Coiled Spiral Tubes (코일형 나선 전열관의 내부 응축열전달 특성에 관한 실험 적 연구)

  • Park, Jong-Un;Gwon, Yeong-Cheol;Han, Gyu-Il
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.25 no.12
    • /
    • pp.1676-1683
    • /
    • 2001
  • An experimental study on condensation heat transfer characteristics of helically coiled spiral tubes was performed. The refrigerant is R-113. A refrigerant loop was established to measure the condensation heat transfer coefficients. Experiments were carried out uniform heat flux of 15 kw/m$^2$, refrigerant quality of 0.1∼0.9, curvature ratio of 0.016, 0.025 and 0.045. The curvature of a coil was defined as the ratio of the inside diameter of the tube to the diameter of the bending circle. To compare the condensation heat transfer coefficients of coiled spiral tubes, the previous results on coiled plain tubes and straight plain tubes were used. The results shows that the condensation heat transfer coefficients of coiled spiral tubes largely increase, as increasing Re and quality, compared to those of coiled plain tubes and straight plain tubes. As increasing degree of subcooling, however, the condensation heat transfer coefficients on coiled spiral tubes decrease. It is found that the heat transfer enhancement is more better than coiled plain tubes and straight plain tubes, as increasing curvature ratio.

Flow Boiling Heat Transfer of R-410A in 0.5mm & 3.0mm Diameter Horizontal Tube (R-410A 비등열전달에 미치는 미세관경 0.5mm와 3.0mm의 영향)

  • Pamitran, A.S.;Choi, Kwang-Il;Oh, Jong-Taek;Hrnjak, Pega
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.154-159
    • /
    • 2008
  • Two-phase flow boiling heat transfer of R-410A in horizontal small tubes was reported in the present experimental study. The local heat transfer coefficients were obtained over a heat flux range of 5 to 40 kW/$m^2$, a mass flux range of 170 to 600 kg/$m^2s$, a saturation temperature range of 3 to $10^{\circ}C$, and quality up to 1.0. The test section was made of stainless steel tubes with inner diameters of 0.5 and 3.0 mm, and lengths of 330 and 3000 mm, respectively. The section was heated uniformly by applying a direct electric current to the tubes. The effects on heat transfer of mass flux, heat flux, inner tube diameter, and saturation temperature were presented. The experimental heat transfer coefficient is compared with six existing heat transfer coefficient correlations. A new boiling heat transfer coefficient correlation based on the superposition model for R-410A in small tubes was developed with mean deviation of 10.13%.

  • PDF

Heat Transfer and Pressure Drop Characteristics for Various Tube Geometries in Modular Tube Bundle Heat Exchanger (모듈형 관군 열교환기에서의 관 형상에 따른 열전달 및 압력강하 특성에 관한 연구)

  • Yoon, Joon-Shik;Park, Byung-Kyu;Kim, Cham-Jung
    • Proceedings of the KSME Conference
    • /
    • 2000.11b
    • /
    • pp.105-111
    • /
    • 2000
  • A numerical study has been performed to obtain the heat transfer and pressure drop characteristics for shell-and-tube heat exchanger with various shapes of tubes. The Tubes have variation of Aspect Ratio, Pitch and Rotation. Results are presented as plots of Colburn j factor and friction factor f against Aspect Ratio, Pitch and Rotation. As Aspect Ratio increases, j factor and f factor decreases. As Pitch increases, j factor decreases. j/f have optimized Pitch for each Aspect Ratio. Accordingly, there is fitness of Aspect Ratio and Pitch fur most effective cases. The Rotation of tubes are of no meaning for both heat transfer and pressure drop.

  • PDF

NUMERICAL ANALYSIS FOR LONGITUDINAL PITCH EFFECT ON TUBE BANK HEAT TRANSFER (관군 배열에서의 종간 간격이 열전달에 미치는 영향에 대한 수치 해석적 연구)

  • Lee, D.;Ahn, J.;Shin, S.
    • Journal of computational fluids engineering
    • /
    • v.17 no.3
    • /
    • pp.39-44
    • /
    • 2012
  • In this study, a longitudinal pitch effect on in-line tube bank heat transfer has been analyzed numerically. To verify the accuracy of the solver model and boundary conditions, global Nusselt number(Nu) and pressure drop across the 2 row tube bank are compared with the existing experimental correlations under 500 ~ 2,000 Reynolds number(Re) range. By changing transverse pitch($S_T$) or longitudinal pitch($S_L$) separately in tube bank, we're trying to identify the each effect on heat transfer. We found that the effect of transverse pitch can be accounted for Reynolds number evaluated with maximum velocity($V_{max}$) at the smallest flow area similar to most existing correlations. Variation of the longitudinal pitch($S_L$) has a greater impact on the heat transfer compared to the transverse pitch($S_T$). Overall Nusselt number increases with larger longitudinal pitch($S_L$), however individual Nusselt number of the tube row has significant difference after the first row.

Heat Transfer Performance of Various Tubes for an Air-cooled Absorber with Surfactant

  • Yoon, Jung-In;Kim, Eun-Pil;Moon, Choon-Geun;Kwon, Oh-Kyong
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.8 no.2
    • /
    • pp.1-10
    • /
    • 2000
  • This research is concerned with the enhancement of heat transfer by surfactant added to the aqueous solution of LiBr. Different vertical tubes were tested with and without an additive of normal octyl alcohol. The test tubes are a bare tube, a groove tube, a corrugated tube and a spring-inserted tube. The additive concentration is about 0.08 mass%. The heat transfer coefficient is measured as a function of the film Reynolds number in the range of 20~200. Experiments are carried out at higher cooling water temperature of $35^{\circ}C$to simulate an air cooling condition for several kinds of absorber testing tubes. The experimental results with and without surfactant are compared. The enhancement of heat transfer by Marangoni convection effect which is generated by addition of the surfactant is observed in each test tube. Especially, it is clarified that the tube with an spring-inserted has the enhancement effect.

  • PDF