• Title/Summary/Keyword: He80%at Transfer Rate

Search Result 1, Processing Time 0.015 seconds

Experimental Study on the Dependence of Variation in Performance of a High-Temperature Generator on Its Operating Conditions (운전조건 변화가 고온재생기의 성능에 미치는 영향에 관한 실험적 연구)

  • Bae, Kyungjin;Kwak, Myoungseok;Cho, Honghyun
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.38 no.5
    • /
    • pp.389-397
    • /
    • 2014
  • An absorption chiller-heater using only a natural refrigerant hardly causes any environmental pollution. In an absorption chiller-heater, the performance of its high-temperature generator, which uses exhaust gases, is essential to achieving superior system performance. To investigate the performance of such a high-temperature generator, a laboratory-scale high-temperature generator working with exhaust gases was designed and tested. Changes in the performance of the high-temperature generator as a function of inlet conditions of the absorbing solution, such as air inlet temperature and mass flow, were investigated. It was observed that when the air mass flow rate ratio was increased from 80% to 120%, the heat capacity was increased by 30%, 33%, 34%, and 37%, respectively. Additionally, when the air inlet temperature was elevated from $170^{\circ}C$ to $210^{\circ}C$ for absorption solution concentrations of 56%, 55%, 545, and 53%, the heat capacity increased by 140%, 160%, 220%, and 224%, respectively.