HFC32/HFC125 혼합냉매의 히트펌프 성능 평가 (Performance of HFC32/HFC125 Mixtures for Heat Pumps)

  • 김욱진;강동규;이요한;정동수
    • 설비공학논문집
    • /
    • 제23권12호
    • /
    • pp.791-798
    • /
    • 2011
  • In this study, performance of R410A(50%R32/50%R125) and HFC32/HFC125 mixture is measured to examine the effect of composition shift of R410A used for various air-conditioners and heat pumps. The composition of HFC32/HFC125 mixture varies from the reference composition of R410A ${\pm}10%$ with 5% interval. Tests carried out in a heat pump bench tester at the evaporation and condensation temperatures of $7/45^{\circ}C$ and $-7/41^{\circ}C$ for summer and winter conditions, respectively. Test results show that both the coefficient of performance (COP) and compressor power of the HFC32/HFC125 mixture have the maximum difference of 2.0% as compared to those of R410A. Compressor discharge temperatures of HFC32/HFC125 mixture are increased up to $6.7^{\circ}C$ as compared to that of R410A. The amount of charge for HFC32/HFC125 mixture vary within 5.6% as compared to that of R410A. Overall, performance of R410A is not appreciably affected by the composition shift of ${\pm}10%$ of R32 under both air-conditioning and heat pumping conditions.

가스계 혼합소화약제의 불꽃소화농도 (Flame Extinguishing Concentrations of Mixed Gaseous Agents)

  • 김재덕;임종성;이윤우;이윤용
    • 한국화재소방학회논문지
    • /
    • 제15권1호
    • /
    • pp.34-40
    • /
    • 2001
  • 가스계 혼합소화약제의 소화성능을 검토하기 위하여 Cup-burner test장치를 설치하고 이성분계 및 삼성분계 혼합물의 불꽃소화농도를 측정하였다. 시험대상 이성분계 혼합물은 이산화탄소/HFC-23, 이산화탄소/HCFC-22, 이산화탄소/HFC-227ea, 이산화탄소/HFC-125, 이산화탄소/FIC-13I1, Hexafluoropropylene/HFC-23이고 삼성분계 흔합물은 이산화탄소/HFC-237HFC-l34a, 이산화탄소/HFC-23/HFC-227ea, 이산화탄소/HFC-23/HFC-125이다. Cup-burner test장치에서 측정된 가스계 혼합물의 소화농도는 단일성분의 소화농도와 혼합물의 구성비로 이루어진 모델에 의해 잘 예측됨을 알 수 있었다. 특히 이 모델은 혼합물의 구성성분이 물리적 소화성능을 지닐 때 잘 적용되며 화학적 소화성능의 영향이 강해질수록 측정값과의 오차가 커진다.

  • PDF

대체 소화제의 열역학적 물성 비교 (Comparison of Thermodynamic Properties of Alternative Fire Extinguishing Agent)

  • 김재덕;여미순;이광진;이윤우;장윤호;노경호
    • 한국화재소방학회논문지
    • /
    • 제18권1호
    • /
    • pp.7-12
    • /
    • 2004
  • 몬트리올 의정서에 의해서 규제 받는 CFCs와 Halon의 대체 물질인 HFC-23, HFC-125, HFC-227ea, HFC-236fa와 불활성 화합물 $Ar, N_2, CO_2$의 열역학적 물성인 포화압력, 밀도, 엔탈피, 점도를 비교하였다. 본 연구에서는 소화제의 물성을 문헌 값을 온도의 함수로서 표시하였다. HFC 화합물의 열역학적 물성은 Halon-1301과 비슷하게 나타내었다. 불활성 화합물은 주로 혼합물로 이용되지만, 불활성 화합물의 물성은 Halon-1301에 비하여 바람직하지 않았다.

초월임계 운전에 의한 저온 열원 랭킨 동력 사이클의 출력 향상 가능성 (Power Enhancement Potential of a Low-Temperature Heat-Source-Driven Rankine Power Cycle by Transcritical Operation)

  • 백영진;김민성;장기창;이영수;나호상
    • 대한기계학회논문집B
    • /
    • 제35권12호
    • /
    • pp.1343-1349
    • /
    • 2011
  • 본 연구에서는 $100^{\circ}C$의 저온 열원을 이용하여 구동되는 랭킨 동력 사이클에 대하여, HFC-134a를 이용한 아임계 운전을 할 경우의 출력과 HFC-125 를 이용한 초월임계 운전을 할 경우의 출력을 서로 비교함으로써, 초월임계 운전에 의한 출력 향상 가능성을 연구하였다. 서로 다른 두 사이클들의 출력을 공정하게 비교하기 위하여, 각 사이클들을 3 개의 설계인자를 이용하여 최적화 하였다. 이 때, 보다 현실적인 결과를 위하여 기존의 연구와는 달리, 열교환 과정에서 작동유체의 열전달 및 압력강하 특성을 고려하였다. 시뮬레이션 결과, HFC-125 초월임계 사이클의 출력이 HFC-134a 아임계 사이클의 출력에 비해 본 연구의 시뮬레이션 조건 하에서 9.4% 향상 될 수 있음을 보였다.

혼합냉매의 풀비등 열전달 상관식 (Pool Boiling Heat Transfer Correlation for Mixture Refrigerants)

  • 고영환;김종곤;박진석;정동수;김영일
    • 설비공학논문집
    • /
    • 제13권2호
    • /
    • pp.122-133
    • /
    • 2001
  • Pool boiling heat transfer coefficients(HTCs) of HFC32/HFC134a, HFC125/HFC134a, HFC32/HFC125 and HFC32/HFC125/HFC134a were measured on a horizontal smooth tube. The experimental apparatus was specially designed to simulate the real heat transfer tube with the use of the secondary fluid of water. Data were taken in the order of decreasing heat flux starting at 80kW/$m^2\; and\; ending\; at\; 5kW/m^2$ in the pool temperature at $7^{\circ}C$. Test results showed that HTCs of these mixtures were 11~38% lower than those of ideal HTCs calculated by a linear mixing rule with pure fluids、 HTCs. Experimental data were compared with Stephan & Korner, Thome, Schlunder, Thome & Shakir、s correlations only to find that those correlations were not satisfactory for all fluids. Hence, a new correlation based on the present data was proposed which could be applied even to the ternary mixture. The correlation predicts the degradation of HTCs of mixtures well, showing a mean deviation of less than 15% for all the mixture data.

  • PDF

HFC125/134a계의 기-액상평형에 관한 연구 (Investigation of vapor-liquid equilibrium of HFC125/134a system)

  • 김창년;박영무
    • 설비공학논문집
    • /
    • 제10권2호
    • /
    • pp.238-250
    • /
    • 1998
  • Vapor-liquid equilibrium apparatus is designed and set up. The vapor-liquid equilibrium data of the binary system HFC125/134a are measured in the range between 268.15 and 283.15K at five compositions. Twenty-five equilibrium data are obtained. To verify consistency of these data, they are tested for thermodynamic consistency. Based upon the present data, the binary interaction parameter for CSD and RKS equation of state is calculated at five isotherms and comparison with the data in the open literatures is made. Results of Nagel and Bier are in very good agreements with those from this study within 0.32∼1.11% for bubble point pressure and -0.66∼0.18% for vapor mole fraction.

  • PDF

HFC 순수냉매 및 3성분 혼합냉매의 수평관내 응축열전달 (Condensation Heat Transfer for Pure HFC Refrigerants and a Ternary Refrigerant Mixture Inside a Horizontal Tube)

  • 오종택;비원 영치
    • 대한기계학회논문집B
    • /
    • 제24권2호
    • /
    • pp.233-240
    • /
    • 2000
  • An experimental study of condensation heat transfer was performed for pure refrigerants HFC32, HFCI25, and HFC134a, and a ternary refrigerant mixture of HFC32/125/134a (23/25/52wt%). The heat transfer coefficients were measured inside a horizontal smooth tube 5.8 mm I.D. and 8.0 m long. The refrigerant temperature at inlet was 40 $^{\circ}C$, and the mass flux was varied from 150 to 400 $kg/m^2s$. As for the pure refrigerants, the heat transfer coefficient of HFC32/125/l34a decreased as the quality decreased. In addition, the heat transfer coefficient of HFC32/l25/134a was about 20 % lower than HFC 134a at a low mass flux but showed no reduction at a high mass flux. The heat transfer coefficient of ternary refrigerant mixtures was 30% lower on the average than that of the pure refrigerant.

수평평활관내의 비공비 혼합냉매의 응축에 대한 예측모델 (A Prediction Model for Condensation of Zeotropic Refrigerant Mixtures Inside a Horizontal Smooth Tube)

  • 이상무;박병덕
    • 설비공학논문집
    • /
    • 제13권4호
    • /
    • pp.262-270
    • /
    • 2001
  • This paper deals with a prediction method for the condensation of ternary refrigerant mixture inside a horizontal smooth tube. Based on some reliable assumptions, the governing equations for the local heat and mass transfer characteristics are derived, and the prediction for the condensation of ternary zeotropic refrigerant mixtures composed of HFC32/HFC125/HFC134a, including R407C, is carried out. The local values of vapor quality, thermodynamic states at bulk vapor, vapor-liquid interface and bulk liquid, mass flux etc. are obtained for a constant wall temperature and a constant wall heat flux conditions, and the effects of the composition of HFC32/HFC125/HFC134a on heat transfer characteristics are examined. The prediction result is also compared with experimental data for condensation of ternary refrigerant mixtures. The predicted wall temperature distribution has a similar trend with experimental data but the predicted local heat transfer coefficients are 20-30% higher than the experimental data.

  • PDF

대체냉매의 2중관 응축기 열 및 물질전달과 성능평가 (Heat and Mass Transfer Characteristics and Performance Evaluation of a Double-Tube Condenser for an Alternative Refrigerant)

  • 이상무;박병덕;소산번
    • 설비공학논문집
    • /
    • 제14권6호
    • /
    • pp.468-476
    • /
    • 2002
  • This paper deals with heat and mass transfer characteristics and performance evaluation of a counter flow double-tube condenser for a multi-component refrigerant mixture. The local heat and mass transfer characteristics of ternary zeotropic refrigerant mixtures composed of HFC32/HFC125/HFC134a are evaluated for a counter flow double-tube condenser cooled by water. Then, the local values of vapor quality, thermodynamic states at bulk vapor, vapor-liquid interface and bulk liquid, heat flux and condensation mass flux are obtained. The heat exchange performance for ternary zeotropic refrigerant mixtures composed of HFC32/HFC125/HFC134a on the total pressure drop and the heat transfer characteristics are also compared with those for R404A, R410A, R502, R22, R32, Rl23 and R134a.

고압가스계 소화약제(HFCs계열)와 질소의 상호용해도 측정 (Measurement of Mutual Solubility of High-pressure Gaseous Fire Extinguishing Agents(HFCs) and Nitrogen)

  • 임종성;박지영;이병권;김재덕;이윤용
    • 한국화재소방학회논문지
    • /
    • 제16권3호
    • /
    • pp.26-31
    • /
    • 2002
  • Bromotrifluoromethane(halon-1301)과 bromochlorodifluoromethane(halon-1211)은 우수한 열역학적 성질에 의해 소화제로 널리 사용되어 오고 있다. 그러나 halon-1301과 halon-1211의 사용과 생산은 국제 환경조약인 Montreal protocol에 의해 점차 사용이 중지되고 있으며, 본격적인 규제에 대한 대책 마련이 요구되는 시점에 있다. 그리하여, 할론 사용규제와 더불어 각국은 할론 소화제 대신 HFCs를 사용하는 방안이 제시되었으며, 이미 선진국에서는 다양한 종류의 소화제 개발을 발표하고 있다. 본 연구에서는 대체 소화제로서 소화제의 배출시간을 단축시켜주는 가압가스 nitrogen과 halon 대체 물질인 HFCs 계열 물질중 chlorodifluoromethane(HFC-22), pentafluoroethane(HFC-125), 1,1,1,2-tetrafluoroethane(HFC-l34a)을 선정하여 이들간의 이성분계 혼합물에 대한 상호 용해력을 알아보기 위해 상평형을 측정하였다. 상평형은 기-액 순환이 동시에 이루어지는 circultion type 장치에서 측정되었으며, 실험온도는 실제 소화제 저장탱크의 온도범위인 283.15-303.15K로 선정하였고, 압력범위는 이 온도범위에서 탱크에 걸릴 수 있는 최저압력과 최고압력보다 충분히 여유를 두어 3.0-10.0 MPa조건에서 실험하였다. 실험데이터는 Peng-Robinson 상태방정식 및 Wong-Sandler mixing rules을 사용하여 혼합물의 거동을 예측하였고, 이를 실험 결과와 비교 검토하였다.