• 제목/요약/키워드: Ground-based Measurement

검색결과 495건 처리시간 0.037초

봉상전극 접지임피던스의 측정과 이론적 분석 (Theoretical analysis and measurement of Ground impedance of Ground rods)

  • 이복희;이태형;이수봉;엄주홍
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 C
    • /
    • pp.1876-1878
    • /
    • 2004
  • A systematic approach of measurement, modeling and analysis of grounding system impedance is presented. The measurement and analysis system of ground impedance is based on a computer aided technique. The ground impedances of the ground rod are considerably dependent on the frequency. The ground impedance is mainly resistive in the frequency range of 3-20 kHz. At higher frequencies, the reactive components of the ground impedances are no longer negligible and the inductance of the ground rod was found to be the core factor deciding the ground impedance. As a consequence, the equivalent circuit model based on the measured data was proposed, and the calculated results were in approximately agreement with the measured data.

  • PDF

봉상접지전극의 접지임피던스의 주파수의존성의 분석 (Analysis of the Frequency Dependent Characteristics of Ground Impedance of a Ground Rod)

  • 이복희;엄주홍
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제53권8호
    • /
    • pp.426-432
    • /
    • 2004
  • This paper presents a systematic approach of measurement, modeling and analysis of grounding system impedance in the field of lightning protection system and intelligent power equipments. The measurement and analysis system of ground impedance is based on a computer aided technique. The magnitude and phase of ground impedance were determined by the novel measurement and analysis using the revised fall-of-potential method. The ground impedances of the ground rod of 50 m long are considerably dependent on the frequency. The ground impedance is mainly resistive in the frequency range of 3-20 kHz. At higher frequencies, the reactive components of the ground impedances are no longer negligible and the inductance of the ground rod was found to be the core factor deciding the ground impedance. Although the steady-state ground resistance of the ground rod of 50 m was less than that of the ground rod of 10 m, the ground impedances of the ground rod of 50 m over the frequency range of more than 60 kHz were much greater than those of the ground rod of 10 m. Furthermore, the equivalent circuit model based on the measured data was proposed. and the calculated results were in approximately agreement with the measured data.

지면 평행 직선의 3차원 방향 추정에 의한 비전 기반 파렛트 측정 방법 (A Vision Based Pallet Measurement Method by Estimating 3D Direction of A Line Parallel to The Ground)

  • 김민환;변성민
    • 한국멀티미디어학회논문지
    • /
    • 제23권10호
    • /
    • pp.1229-1235
    • /
    • 2020
  • A line parallel to the ground is frequently shown in our daily life, which enables us to guess its direction. Especially, such a guess tends to become clear when a vanishing line of the ground is shown together. In this paper, a vision based pallet measurement method is suggested, which uses a technique for estimating three-dimensional direction of a line parallel to the ground. The technique computes actually a vector heading to intersection of a given imaged line parallel to the ground and the ground vanishing line determined previously on calibrating a measurement camera. Through an experiment of measuring a real commercial pallet with various orientation and distance, we found that the technique could measure the orientation of the pallet correctly and accurately. The technique worked well even though an edge line available on the front plane of a pallet was almost parallel to the ground vanishing line.

접지임피던스의 주파수 의존성 측정기법 (Measurement Method of the Frequency Dependent Characteristics of Ground Impedance)

  • 엄주홍;이복희
    • 한국정보통신설비학회:학술대회논문집
    • /
    • 한국정보통신설비학회 2004년도 하계학술대회
    • /
    • pp.211-214
    • /
    • 2004
  • The measurement system of ground impedance is based on a computer aided technique. The magnitude and phase of ground impedance were determined by the novel measurement and analysis using the revised fall-of-potential method. The ground impedances of the ground rod of 30 m long are considerably dependent on the frequency. The ground impedance is mainly resistive in the frequency range of 3-20 kHz. At higher frequencies, the reactive components of the ground impedances are no longer negligible and the inductance of the ground rod was found to be the core factor deciding the ground impedance.

  • PDF

접지전류 측정에 의한 다중 접지계통의 접지저항 측정 (Measurement of Resistance of Multi-Grounded System by Ground Current Measurement)

  • 최종기;안용호;정길조;한병성;김경철
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제53권4호
    • /
    • pp.234-237
    • /
    • 2004
  • Measuring ground resistance has been a popular method of evaluation of the grounding electrode performance. If some portions of grounding electrodes are lost by corrosion, aging or other reasons, consequent deteriotation of the grounding performance would be resulted. It is one of the reasons why it is required to evaluate the performance of grounding systems regularly. However, in case of the electric facilities with multi-grounded system such as power substations with multi-grounded overhead ground wires and/or distribution line neutrals, it is practically difficult to disconnect neutrals or skywires from the substation grounding mesh for the ground resistance measurement. In this paper, a method for the grounding performance measurement of multi-grounded systems, which is based on the measuring ground current distributions, has been proposed. A field test results has shown the validity of the proposed test method.

접지전류 측정에 의한 다중 접지계통의 접지저항 측정 (Measurement of Resistance of Multi-Grounded System by Ground Current Measurement)

  • 최종기;안용호;정길조;한병성;김경철
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제53권4호
    • /
    • pp.234-234
    • /
    • 2004
  • Measuring ground resistance has been a popular method of evaluation of the grounding electrode performance. If some portions of grounding electrodes are lost by corrosion, aging or other reasons, consequent deteriotation of the grounding performance would be resulted. It is one of the reasons why it is required to evaluate the performance of grounding systems regularly. However, in case of the electric facilities with multi-grounded system such as power substations with multi-grounded overhead ground wires and/or distribution line neutrals, it is practically difficult to disconnect neutrals or skywires from the substation grounding mesh for the ground resistance measurement. In this paper, a method for the grounding performance measurement of multi-grounded systems, which is based on the measuring ground current distributions, has been proposed. A field test results has shown the validity of the proposed test method.

지표면전위 해석에 의한 접지저항 측정기법에 관한 연구 (A Study on the Measurement of Grounding Resistance based on the Earth Surface Potential Analysis)

  • 윤장완;안용호;정길조;한병성
    • 조명전기설비학회논문지
    • /
    • 제16권4호
    • /
    • pp.117-123
    • /
    • 2002
  • 접지저항의 측정은 접지계통의 접지성능이 적정한가를 평가하기 위한 가장 기본적이고 중요한 작업이라고 할 수 있다. 그러나 실제 현장에서, 특히 접지극의 크기가 큰 경우일수록 접지저항을 정확히 측정하기란 쉽지 않은데, 이는 정확한 접지전위 측정을 위한 기준전위 점을 찾기가 힘들기 때문이다. 본 논문에서는 접지극 주변에서 측정한 지표면전위를 분석하여 기준전위 점의 위치를 정확히 식별하는 방법과 그 정당성을 제시하였다.

미세진동 측정을 통한 지반응답특성 평가 (Estimation of Ground Response Characteristics by Microtremor)

  • 조성호;이일화;고학송
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2005년도 춘계학술대회 논문집
    • /
    • pp.718-721
    • /
    • 2005
  • The purpose of the study is to evaluate the usage of microtremor in estimation of subsurface structure and ground response to ground motion. Ground motion amplification based on site condition of an area is an important parameter for dynamic design. Microtremor cover the characteristics in a low frequency range, while forced vibrations cover them in a high-frequency range. Microtremor consider ground characteristics and offer transfer function in area. To determine the dominant frequency, the passive microtremor measurement is performed and to determine the transfer function of test site, active microtremor measurement is performed. Microtremor measurement in the site is compared with theoretical transfer function calculated from the known structures.

  • PDF

홍수 위험도 척도 및 예측모형 연구 (Study on Measurement of Flood Risk and Forecasting Model)

  • 권세혁;오현승
    • 산업경영시스템학회지
    • /
    • 제38권1호
    • /
    • pp.118-123
    • /
    • 2015
  • There have been various studies on measurements of flood risk and forecasting models. For river and dam region, PDF and FVI has been proposed for measurement of flood risk and regression models have been applied for forecasting model. For Bo region unlikely river or dam region, flood risk would unexpectedly increase due to outgoing water to keep water amount under the designated risk level even the drain system could hardly manage the water amount. GFI and general linear model was proposed for flood risk measurement and forecasting model. In this paper, FVI with the consideration of duration on GFI was proposed for flood risk measurement at Bo region. General linear model was applied to the empirical data from Bo region of Nadong river to derive the forecasting model of FVI at three different values of Base High Level, 2m, 2.5m and 3m. The significant predictor variables on the target variable, FVI were as follows: ground water level based on sea level with negative effect, difference between ground altitude of ground water and river level with negative effect, and difference between ground water level and river level after Bo water being filled with positive sign for quantitative variables. And for qualitative variable, effective soil depth and ground soil type were significant for FVI.

접지임피던스 측정시 보조전극의 배치 기준 연구 (Placement Standard Research of Auxiliary Probes when Measuring Ground Impedance)

  • 김동우;길형준;김동욱;이기연;문현욱
    • 전기학회논문지
    • /
    • 제60권10호
    • /
    • pp.1984-1991
    • /
    • 2011
  • Among ground impedance measurement methods, the fall-of-potential method is the most thorough and reliable method. In the fall-of-potential method, ground electrode and auxiliary probes are placed in a straight line, and then, auxiliary potential probe is moved away from the ground electrode. The point at which plotted resistance curve flattens out is taken as right position of auxiliary potential probe. However, in some cases, it is hard to place ground electrode and auxiliary probes in a straight line. Therefore, we provided alternative placement method in this research. The method can be easily applicable to placing auxiliary probes. Also, this paper analyzed and compared ground impedance measurement standards of large grounding systems. Based on the analysis, practical measurement method using an earth tester was proposed. The proposed methods presented in this paper will be useful when determining locations of auxiliary probes in alternative positions, and the methods can be applied practically and easily.