• 제목/요약/키워드: Ground Wye Connection

검색결과 1건 처리시간 0.012초

22.9kV급 병렬 커패시터 뱅크 내부의 아크 고장 판별을 위한 전압차동 보호 알고리즘의 개선 방안 (Improvement of the Protection Algorithm Based on Voltage Difference Method for Detecting Arcing Faults within 22.9kV Shunt Capacitor Banks)

  • 임정욱;권영진;강상희;육유경
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제54권2호
    • /
    • pp.61-66
    • /
    • 2005
  • This paper presents a refined protection algorithm of the unfused 22.9kV shunt capacitor banks in grounded wye connection to improve the existing algorithm using the voltage difference method. It is difficult to detect ground faults with arc near the input points or ground faults near the grounding point by the existing algorithm using only the voltage balanced relay. This paper shows that ground faults with arc near the input point can be detected by harmonics analysis of the differential voltage and that it has no impact of harmonics out of nonlinear loads which have the quantitative influence on capacitor banks. Thus the proposed method using harmonics analysis can be a proper detection method. In case of ground faults near the grounding point, an OVGR is being added recently and its validity is verified in this paper. The proposed method is applied to a 22.9kV example system and is verified that the proposed algorithm can detect clearly faults which are not easy to detect by the existing method.