• 제목/요약/키워드: Flush valve or flush tank type

검색결과 1건 처리시간 0.016초

사무소 건물의 급수배관경 산정을 위한 동시사용유량에 관한 연구 (The evaluation of the simultaneous flow rate for sizing the water supply piping in the office building)

  • 이용화
    • 설비공학논문집
    • /
    • 제11권4호
    • /
    • pp.511-517
    • /
    • 1999
  • Determining the simultaneous flow rate in any particular section of piping is the important step in order to determine the size of water supply piping. Now we are using the diversity curve of common water closet in order to determine the simultaneous flow rate of water supply piping, but there is a difference between a determined flow rate of general water closet and that of water closet for water saving. This study aims to find out the fixture unit of a flush valve type water closet for water saving in office building, and to determine the correlation between the fixture units and peak flow rates on the basis of the probability theory. A flush valve type water closet for water saving that have a 7.5 second duration of flush operation with an average design flow rate 72 $\ell$/fin was considered. Simulation results indicate that the number 5 is shown to be reasonable to the fixture unit of water closet for water saving. And the design can be undersized considerably with the revised diversity curves using modified fixture unit.

  • PDF