• Title/Summary/Keyword: Flow Field Numerical Anyalysis

Search Result 1, Processing Time 0.014 seconds

A study of flow characterisitics in a clean room with work table (작업대가 있는 청정실내의 유동특성에 관한 연구)

  • 이재헌;이진원;이상렬
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.10 no.6
    • /
    • pp.852-860
    • /
    • 1986
  • The effect of placing a worktable in a vertical laminar flow clean room is invesgiated by a numerical simulation. The model clean room is assumed to be a rectangular square of 2m*2m, in which a worktable of 0.8m long and 0.1m thick is located at 0.7m above the floor. Major parameters are the horizontal position of the table and the inlet flow velocity. The flow is assumed to be laminar throughout the clean room. Navier-Stokes equations with the pressure terms are directly solved by the SIMPLE algorithm. Boundary conditions at the two exits are given in terms of pressure conditions. The flow pattern, pressure loss due to viscous friction, the ratio of flow rates through each exit and pressure imbalance at the exits are calculated. All of the flow characteristics are seen to vary substantially with the location of the table, but are quite insensitive to the inlet flow velocity(Reynolds number). As an example, the flow rate through each exit can very by as much as 30% depending on the location of the table.