• Title/Summary/Keyword: Flicker transfer coefficient

Search Result 2, Processing Time 0.018 seconds

A Study on Flicker Management Standard for Distribution Power System in Korea based on IEC 61000-3-7 (IEC 기반의 배전계통 플리커 관리기준 연구)

  • Kang, Moon-Ho;Lee, Heung-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.9
    • /
    • pp.1663-1667
    • /
    • 2011
  • Voltage variation caused by large loads such as arc furnace and large motors, which use the large and instantaneous currents, can cause the voltage flicker. The flicker irritates the human's eyes and also has an adverse effect on protection device, rotating machine and electronic device etc, therefore the flicker needs to be managed effectively. Recently, the Korea power quality standard has been established on the IEC standards. This paper presents the flicker management standard for distribution power system and suggests the flicker transfer coefficients for Korea power system based on the IEC 61000-3-7.

A Study on the Flicker Transfer Coefficient of IEC 61000-3-7 in Korea Power System (IEC 기반의 플리커 관리기준 수립을 위한 플리커 전달계수 산정 연구)

  • Kang, Moon-Ho;Lee, Beong-Sung;Choi, Won-Suk
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.995-996
    • /
    • 2011
  • 전압의 시간적 변동으로 인하여 시각적 혹은 심리적으로 인식되는 불편함을 나타내는 플리커는 인간의 생체심리학적 인지능력과 관련이 있으며, 인간의 눈은 0.3%에서 0.4%의 매우 작은 전압변동에 대하여 5Hz에서 20Hz의 변조 주파수에서 민감하게 반응하며, IEC는 실증시험을 통해 8.8Hz의 전압변동에서 가장 민감하게 인식하는 것을 확인하였다. 이러한 플리커는 시각적 불쾌감과 함께 지속적인 경우 회전기와 같은 기기들에 악영향을 주며, 전자장비, 전구, CRT 장비, UPS 동기상실, 제어설비 및 보호설비의 오동작 발생으로 효과적으로 관리가 필요하다. 현재 국내 전기품질 관리기준은 IEC 국제규격을 바탕으로 제 개정 작업이 진행되고 있어 본 논문에서는 IEC 61000-3-7 국제규격을 국내 적용을 위해 필요한 국내 전력계통의 플리커 전달계수를 제시하였다.

  • PDF