• 제목/요약/키워드: Flame hight

검색결과 3건 처리시간 0.015초

Pool fire에서의 화염의 높이 계산에 관한 실험식의 비교연구 (Comparative study of experimental equations on measurement of fire hight on pool fire)

  • 황운기;권창희
    • 대한안전경영과학회지
    • /
    • 제19권1호
    • /
    • pp.9-13
    • /
    • 2017
  • In this study, the height of the flame required to estimate the heat flow path and flame spread in pool fire has been applied by the empirical formula, but it is calculated without applying the pressure and temperature parameters of the fire room. Until now, the height of the flame applied to pool fire was $l_F=0.235Q^{2/5}-1.02D$ in the Heskestad empirical formula, but accurate temperature calculation was not possible due to the temperature and pressure which are not influenced by the flame height. Therefore, applying the temperature and pressure around it can calculate the exact flame height, which can be applied to fire investigation and fire dynamics. The structure of the flame is divided into a continuous flame, an intermittent flame, and a buoyancy flame, but it is assumed that the flame height is calculated from the visual aspect to the intermittent flame region, and the temperature of the buoyancy flame is very low. The effect of heat of vaporization on the height of flame was investigated. The results showed that flame height was different according to the pressure and temperature around the fire room.

가스터어빈 연소기의 화염 안정화와 제어 (Flame Stabilization and Control in Gas Turbine Combustor)

  • 최경민
    • 한국분무공학회지
    • /
    • 제8권4호
    • /
    • pp.24-30
    • /
    • 2003
  • This paper presents the characteristics of lifted height and flame length from non-premixed jet flames in highly preheated air to investigate the detail combustion mechanism in the gas turbine or HCCI engine, etc. Special attention was paid to the effect of preheated air temperature, oxygen concentration and fuel injection flow rate on flame length and lifted hight. By using highly preheated air, stable flames were formed even in low oxygen concentration condition. The lifted height increased with decreasing preheated air temperature, where the flame length showed opposed phenomena. The flamelet model, which is thought to have very thin flamelet, is difficult to applicable to the present flame conditions which is formed In low oxygen concentration in highly preheated air.

  • PDF

IR 불꽃화재감지기 개발

  • 권오승;이복영;박상태
    • 방재기술
    • /
    • 통권29호
    • /
    • pp.39-45
    • /
    • 2000
  • All objects emit thermal radiation and this radiation is the basis of the techniques used to detect flames. The usual phenomena occurring in the initial stage of a fire are generally invisible products of a combustion and visible smoke. Liquid or gaseous materials do not undergo a smoldering stage such fires develop very rapidly. Also, the heat generated by the initial flames is usually not sufficient to active a heat detector. In this case the most effective criterion for automatic fire detection is the flame. In fire regulation of korea, the compulsory standard provided that a flame detector shall be installed a place of the attachment hight of detector is higher than 20 m, chemical plants, hangar, refinery, etc.. The result of the research and development are discriminated between a flame and other radiant emitters, developed PZT pyroelectric element is based on the use of photo-voltanic cell, developed IR band-pass filter that only allow a 4.3 radiation wavelength to reach the sensors and developed IR flame detector.