• Title/Summary/Keyword: Fire suppression nozzle

Search Result 44, Processing Time 0.025 seconds

An Experimental Study for the Effect of Ventilation Velocity on Performance of a High Pressure Water Mist Fire Suppression System (객차내 환기속도가 고압 미세물분무 화재제어 시스템 성능에 미치는 영향에 대한 실험적 연구)

  • Kim, Dong-Woon;Bae, Seung-Yong;Ryou, Hong-Sun
    • Journal of the Korean Society of Safety
    • /
    • v.23 no.4
    • /
    • pp.1-6
    • /
    • 2008
  • This experiments are perfol1ned to investigate the effect of ventilation velocity on a high pressure water mist tire suppression in train. The experiment is conducted in half scale modeled train of a steel-welled enclosure (5.0m${\times}$2.4m${\times}$2.2m). The ventilation velocity is controlled by the ventilation duct through an inverter in the range of 0 to 3m/s. The coverage-radius and an injection angle of an high pressure water mist system are measured. The mist nozzle with 5-injection holes is operated with pressure 60bar. The heptane pool fires are used. The fire extinguishment times and the temperature are measured for the ventilation velocities. In conclusion, because the momentum of injected water mist is more dominant than that of ventilation air, the characteristics of water mist, the fire extinguishment times and the temperature are affected very little by ventilation velocity.

Effect of Absorbent Thickness on the Noise Level Reduction of Fire-Extinguishing Nozzle (흡음재 두께가 소화노즐 소음도 저감에 미치는 영향)

  • Kim, Hak-Sun;Hwang, In-Ju;Kim, Youn-Jea
    • Fire Science and Engineering
    • /
    • v.33 no.1
    • /
    • pp.99-104
    • /
    • 2019
  • In a gas system fire extinguishing system, extinguishing agents are usually stored with approximately 280 bar at $21^{\circ}C$ and are released at approximately 8 MPa through the decompression valve and orifice to quickly suppress the fire. When extinguishing agents are discharged, they cause a loud noise (approximately 140 dB), which can damage electronics, such as hard disk drives (HDDs). Therefore, the noise is becoming a serious issue in the gas extinguishing system. The method of the noise reduction by adding an absorbent is most general and in this study, the thickness of the absorbent was as a selected design variable. The noise level at the observation point and the flow characteristics inside the nozzle were numerically calculated and analyzed using the commercial code ANSYS CFX ver. 18.1.

Extinguishment of n-heptane Pool Fire by Water Mist Containing Alkali Metal Agent (알칼리 금속염을 함유한 미분무수의 헵탄 Pool Fire 소화)

  • Park, Jae-Man;Shin, Chang-Sub
    • Journal of the Korean Society of Safety
    • /
    • v.20 no.3 s.71
    • /
    • pp.105-111
    • /
    • 2005
  • An experimental study is performed for extinguishing of n-heptane pool fire by water mist containing potassium acetate as a fire suppression additive. Water mist was generated by a single pressure nozzle in a small-scale chamber. The drop size distribution of water mist was measured using laser diffraction(Malvern particle sizer). The flame temperature, oxygen concentration and carbon monoxide concentration were measured. In case of using additives, the fire extinguishing time was shorter than that of pure water at a given discharge pressure and it was because the momentum of a water droplet containing additives was increased. And also dissociated metal atoms, potassium, were reacted as a scavenger of the major radical species OH, H which were generated for combustion process. Moreover, at a high pressure of 4MPa, the fire was extinguished through blowing effect as well as primary extinguishing mechanisms.

Fire Detection Performance Experiment of the Water Jet Nozzle Position Control Type Automatic Fire Extinguishing Facility for Road Tunnels (도로터널용 방수노즐 위치제어형 자동소화설비의 화재감지성능실험)

  • Kim, Chang-Yong;Kong, Ha-Sung
    • Fire Science and Engineering
    • /
    • v.33 no.1
    • /
    • pp.85-91
    • /
    • 2019
  • This study evaluated the fire detection performance of an automatic fire extinguishing system for road tunnels, which combines flame wavelength detection technology with flame image detection technology. This fusion technique to improve the fire detection capability can reduce the damage caused by the fire suppression by locating the fire source in the fire and discharging the pressurized water only at the fire source. Experiments were conducted to determine the position of a fire source when a $70cm{\times}70cm$ target was placed at a distance of 15 m, 20 m, 25 m, 30 m, and 35 m, respectively, in a situation where there is a flame and smoke in a tunnel. The performance of the ultraviolet and triple wavelength infrared (IR3) sensors was attenuated due to the interference of thick smoke. In addition when the flame was blocked by thick smoke, the image sensor sensed the smoke and emitted a fire signal.

An Experimental Evaluation for the Effect of Ventilation Velocity in Subway Train on Performance of a High Pressure Water Mist Fire Suppression (지하철 객차 내 환기 속도가 고압 미세물분무 화재제어 시스템의 성능에 대한 실험평가)

  • Kim, Dong-Woon;Bae, Seung-Yong;Kim, Dong-Suk;Park, Won-Hee;Ryou, Hong-Sun
    • Proceedings of the KSR Conference
    • /
    • 2007.05a
    • /
    • pp.1307-1312
    • /
    • 2007
  • This experiments are performed to investigate the effect of ventilation velocity on a high pressure water mist fire suppression in subway train. The experiment is conducted in half scale modeled train of a steel-welled enclosure (8.0m*2.4m*2.1m). The ventilation velocity is controlled by the ventilation duct through an inverter in the range of 0 to 2 m/s. The coverage-radius and an injection angle of an high pressure water mist system are measured. The mist nozzle with 7-injection holes is operated with pressure 80 bar. The heptane pool fires are used. The fire extinguishment times and the temperatures are measured for the ventilation velocities. In conclusion, because the momentum of injected water mist is more dominant than that of ventilation air, the characteristics of water mist, the fire extinguishment times and the temperatures are affected very little by ventilation velocity.

  • PDF

A Study on the Development of Fire Extinguishing Agent and Extinguishing System for ESS Fire (ESS 화재전용 소화약제 및 소화시스템 개발에 관한 연구)

  • Lee, Yeon-Ho;Lee, Joo-Hyung;Kim, Soo-Jin;Chon, Sung-Ho;Choi, Byoung-Chul;Oh, Seung-Ju;Kim, Si-Kuk
    • Fire Science and Engineering
    • /
    • v.34 no.2
    • /
    • pp.147-155
    • /
    • 2020
  • This paper presents a study on the development of a fire extinguishing agent and extinguishing system for an energy storage system (ESS) fire. The fire extinguishing agent designed to extinguish an ESS fire is a highly permeable fire extinguisher that reduces the surface tension and viscosity while bringing about cooling action. This is the main extinguishing effect of this type of wetting agent, which displays the characteristics of fire extinguishing agents used for penetrating the battery cells inside the ESS module. For the fire extinguishing system, a local application system was designed to suppress fire on a rack-by-rack basis. A 360° rotating nozzle was inserted into the rear hall of the ESS module, and general nozzles were installed in the rack to maximize the fire extinguishing effect. The fire extinguishing agent was strongly discharged by virtue of the gas release pressure. Experiments on fire suppression performance with ESS module 1 unit and module 3 units showed that all visible flames were extinguished in 8 s and 9 s, respectively, by the fire extinguishing agent. In addition, based on confirming reignition for 600 s after the fire extinguishing agent was exhausted, it was confirmed that the ESS fire was completely extinguished without reignition in all fire suppression performance experiments.

An experimental study on development of water mist fire-fighting systems for Ro-Ro spaces (Ro-Ro 구역용 미분무 소화설비의 개발을 위한 실험적 연구)

  • Kwark, Ji-Hyun;Kim, Young-Han
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.37 no.8
    • /
    • pp.946-952
    • /
    • 2013
  • Large scale fire tests were conducted to develop water mist nozzles as a component of fixed water- based fire fighting systems for Ro-Ro spaces and special category spaces. Fire scenarios for this system consist of two cases which are for cargo fire in a simulated truck and for passenger vehicle fire, and each case has 3 different tests according to the position between fixed water mist nozzles and fire source. Every experiment proceeded for 30 minutes and acceptance criteria were based on gas temperature, fuel package's damage and ignition of targets. This study primarily dealt with the experimental results of cargo fire and focused on fire suppression capability in accordance with discharge pressure, flow rate and flow characteristics like swirl and penetration of the developed water mist nozzles. It appeared that low pressure water mist nozzles with about 40 L/min were able to control fire occurred in Ro-Ro spaces.

Directional Water Spray Characteristics of Sprinkler Heads (스프링클러 헤드의 방향성 살수 특성 비교 연구)

  • Park Yong-Hwan
    • Fire Science and Engineering
    • /
    • v.18 no.4
    • /
    • pp.35-41
    • /
    • 2004
  • The water spray characteristics of the sprinkler heads is a very important factor affecting the fire suppression performance, and it is largely dependent on the shape of the head nozzle. This study investigated shape factors and spray distribution performances for the sprinkler heads of four domestic companies with big market shares. The experimental results revealed that all flow constants exceeded the required regulation limits, however showed big differences between head types although they have the same design limit. They were however relatively consistent regardless of the pressure increases. The spray distribution of some head samples showed severe directional eccentricity, which suggests more study for the improvement.

He Study of Fire Suppression Capability of Low Pressure Water-Mist System for Wooden Cultural Properties (목조한옥에 대한 저압식 미분무 소화설비의 소화성능에 관한 연구)

  • Roh, Sam-Kew;Kim, Dong-Cheol;Ham Eun-Gu
    • Journal of the Society of Disaster Information
    • /
    • v.8 no.4
    • /
    • pp.401-410
    • /
    • 2012
  • The study verified the extinguishing performance of the low pressure water-mist system, which is used to extinguish fire at domestic wooden architecture, through a fire test. Made of inflammable materials, a wooden house is vulnerable to fire, and the size of fire may vary from the early stage in case of arson. With the discharging pressure of 8 bar and the flow rate of 35 lpm, the low pressure water-mist nozzle used in the experiment has considerable discharging amount compared to other water-mist nozzles. The extinguishing performance was tested based on the size of fire and architecture. Test results demonstrated that the extinguishing performance was not affected by the size of a house, but decreased significantly when the size of fire was above unit 1. Taking into account that the environment of actual wooden cultural properties is more vulnerable than that of the experiment model, sufficient investigation on extinguishing performance is required to apply the water-mist extinguishing system to wooden architecture.