• Title/Summary/Keyword: Fire case analysis

Search Result 590, Processing Time 0.027 seconds

A parametric study on the use of passive fire protection in FPSO topside module

  • Friebe, Martin;Jang, Beom-Seon;Jim, Yanlin
    • International Journal of Naval Architecture and Ocean Engineering
    • /
    • v.6 no.4
    • /
    • pp.826-839
    • /
    • 2014
  • Fire is a continuous threat to FPSO topside modules as large amounts of oil and gas are passing through the modules. As a conventional measure to mitigate structural failure under fire, passive fire protection (PFP) coatings are widely used on main structural members. However, an excessive use of PFP coatings can cause considerable cost for material purchase, installation, inspection and maintenance. Long installation time can be a risk since the work should be done nearly at the last fabrication stage. Thus, the minimal use of PFP can be beneficial to the reduction of construction cost and the avoidance of schedule delay. This paper presents a few case studies on how different applications of PFP have influence on collapse time of a FPSO module structure. A series of heat analysis and thermal elasto-plastic FE analysis are performed for different PFP coatings and the resultant collapse time and the amount of PFP coatings are compared with each other.

A Study on the Efficiency of Evacuation Guidance and Non-evacuation Guidance in Case of Fire

  • Ko, Eun-young;Hong, Sung-Ho;Cha, Jae-sang
    • International Journal of Advanced Culture Technology
    • /
    • v.8 no.1
    • /
    • pp.243-247
    • /
    • 2020
  • In the era of the fourth industrial revolution, safety of disasters is being emphasized above all else, and electric fires are most frequent during disasters, and human and property damage is very serious. In this paper, we propose a study that can determine the efficiency of evacuation and non-evacuation guidance due to the large difference in casualties depending on the traffic line in the case of fire. Evacuation guidance was assumed to be a situation in which adequate evacuation routes were guided by a recorded voice or a trained staff, and non-evacuation guidance was assumed to be a situation without anything. Evacuation simulations were carried out using a evacuation simulation tool called PATHFINDER and SIMULEX for the analysis of the efficiency of evacuation and non-evacuation guidance. As a result, the evacuation time was similar, but in the case of non-evacuation guidance, it was not guided to the safe zone, which could cause serious damage.

A Study on Structural Analysis for Stability Evaluation According to Design Parameters of a Fire Ladder Vehicle (소방 고가사다리차의 설계 변수에 따른 안정성 평가를 위한 구조해석 연구)

  • Jung, Hoon;Kim, Cheol-Jung;Kim, Hong-Gun
    • Journal of the Korean Society of Manufacturing Process Engineers
    • /
    • v.19 no.8
    • /
    • pp.64-72
    • /
    • 2020
  • In this study, a stability analysis was conducted through finite element analysis (FEA) of a simplified model of a fire ladder truck by changing the ascending angle, turning angle, and boundary conditions between the outrigger and the ground. The results of the analysis showed that decreasing the angle of the ladder car increases the moment due to the ladder weight, decreasing the safety factor despite being under the same load conditions. In the case of a rotating radius, the stability was found to vary depending on the boundary conditions. A comparative analysis in the future with these results and the experimental values from the actual fire ladder truck may determine the most appropriate boundary conditions based on the analysis program. It is expected to predict the risk of damage and rollover by assessing the stability of aerial ladder vehicles under different conditions.

A Model-Analysis for Removal of Fire Fumes in a Road Tunnel during a Fire Disaster (도로터널내 화재 발생시 매연 제거를 위한 모델 해석)

  • 윤성욱;이희근
    • Tunnel and Underground Space
    • /
    • v.7 no.2
    • /
    • pp.100-107
    • /
    • 1997
  • In case of a fire outbreak in a uni-directional road tunnel, the flow of traffic immediately behind the fire disaster will be stalled all the way back to the entrance of the tunnel. Furthermore, when the vehicle passengers try to flee away from the fire toward the entrance of the tunnel, the extremely hot fume that propagates in the same direction will be fatal to the multitudes evacuating, but may also cause damage to the ventilation equipments and the vehicles, compounding the evacuation process. This paper will present the 3-dimensional modelling analysis of the preventive measures of such a fume propagation in the same direction as the evacuating passengers. For the analysis, the fire hazard was assumed to be a perfect combustion of methane gas injected through the 1 m X 2 m nozzle in the middle of the tunnel, and the product of $CO_2$ as the indicator of the fume propagation. From the research results, when the fire hazard occurred in middle of the 400 m road tunnel, the air density decreased around the fire point, and the maximum temperatures were 996 K and 499 K at 210 m and 350 m locations, respectively, 60 seconds after fire disaster occurred, when the fumes were driven out only towards the exit-direction of the tunnel. By tracing the increase of $CO_2$ level over 1% mole fraction, the minimum longitudinal ventilation velocity was found to be 2.40 m/sec. Furthermore, through Analysis of the temperature distribution graphs, and observation of the cross-sectional distribution of $CO_2$ over 1% mole fraction, it was found that the fume did not mix with the air, but rather moved far in a laminar flow towards exit of the tunnel.

  • PDF

Analysis of Causes of Casualties in Jecheon Sports Center Fire - Focus on Structural Factors of Building and Equipment - (제천 스포츠센터 화재의 다수 사상자 발생원인 분석 - 건물과 설비의 구조적인 요인을 중심으로 -)

  • Lee, Eui-Pyeong
    • Fire Science and Engineering
    • /
    • v.32 no.4
    • /
    • pp.86-94
    • /
    • 2018
  • A sports center fire in Jecheon caused 29 deaths and 40 injuries. This study focused only on the structural factors of the building and equipment to investigate the causes of casualties based on the fire investigation results at the sports center. The structural factors of the building and equipment were a piloti-type parking lot, lack of a fire compartment between the piloti-type parking lot and lobby, lack of an installed sprinkler system, lack of an installed fire door in the main stairs on the $1^{st}$ floor, lack of an installed fire water tank on the rooftop, an installed pocket fire door in the main entrance on the $2^{nd}$ floor, poor fire compartments in an EPS space and a pipe pit and on each floor, a leak in the joint of a drain pipe, plywood installed in the hoistway of the freight elevator and interior wall, illegal remodeling of a closed rooftop structure, which cannot discharge smoke and heat, installed styrofoam insulation in the inside of the parking lot ceiling, an installed tempered glass window, which cannot be opened in the ladies bathroom on the $2^{nd}$ floor, and a finished dryvit exterior wall.

Analysis of the Causes of Casualties of Jecheon Sports Center Fire - Focus on an Initial Response and Management - (제천 스포츠센터 화재의 다수 사상자 발생원인 분석 -초기대응과 관리적인 측면을 중심으로-)

  • Lee, Eui-Pyeong
    • Fire Science and Engineering
    • /
    • v.32 no.5
    • /
    • pp.57-66
    • /
    • 2018
  • A sports center fire in Jecheon that caused 29 deaths and 40 injuries was analyzed based on initial response and management in order to investigate the causes of the casualties. The aspects of initial response included delay of reporting 119, not being guided to the exit for the body scrubber on the $2^{nd}$ floor for escape, opening the fire doors of the exits on the $1^{st}$ floor and $3^{rd}$ floor, not closing the fire door of the main stairs on the $3^{rd}$ floor, and not doing an emergency broadcast. The management aspects included closing the alarm valve of the sprinkler system on the $1^{st}$ floor, starting-stop of the fire pump controller, neglecting leakage of water and electricity between the false ceiling and ceiling in the parking lot, hiding the exit light in the ladies bathroom lounge on the $2^{nd}$ floor and piling up things in the exit, neglecting the button of an automatic door on the $2^{nd}$ floor, conventional fire safety management, insufficient inspection of fire equipment, and not working fire shutters and smoke exhaust windows.

Numerical Study on Atmospheric Dispersion and Fire Possibility in Toluene Leakage (톨루엔 누출 시 대기확산 및 화재가능성에 관한 수치해석 연구)

  • Ko, Jae Sun;Kim, Joo-Seok
    • Fire Science and Engineering
    • /
    • v.31 no.3
    • /
    • pp.1-10
    • /
    • 2017
  • This study examined the risk of accidents when handling hazardous materials in hazardous materials storage facilities without safety facilities. In the case of illegal dangerous cargo containers, the burning rate is very fast in the case of fire, which leads to explosions, that are damaging and difficult to control. In addition, accidents that occur in flammable liquid hazardous materials are caused mostly by accidents that occur in the space due to leakage. Therefore, the variables that affect these accidents were derived and the influence of these variables was investigated. Numerical and computational fluid dynamics programs were used to obtain the following final results. First, when a flammable liquid leaks into a specific space, it is influenced by temperature and relative humidity until a certain concentration (lower limit of combustion) is reached. In the case of temperature, it was found that the reaching time was shorter than the flash point In addition, the effect of variables on pool fire accidents of leakage tanks is somewhat different, but the variables that have the largest influence are the wind speed. Therefore, it is expected that the results of this study will be used as basic data for similar numerical analysis and it will provide useful numerical information about the accidental leakage of hazardous materials under various research conditions.

A study on the selection of the optimal smoke control mode in train platform through quantitative risk assessment (정량적 위험도 평가를 통한 열차 승강장 화재시 최적 제연모드 선정에 관한 연구)

  • Lee, Bo-Hoon;Hong, Seo-Hee;Baek, Doo-San;Lee, Ho-Hyung
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.24 no.6
    • /
    • pp.539-552
    • /
    • 2022
  • In the case of train stations, due to the specificity of underground spaces with limited smoke emissions, if appropriate removal equipment is not equipped, the damage caused by fire smoke may increase in the event of a fire. As a result, the need for measures to ensure the safety of evacuation of underground stations has been highlighted, and research for safe evacuation of platform users in case of fire is continuously being conducted at home and abroad. However, although the smoke removal area is currently divided by smoke boundary walls and platform screen doors (PSD) and installed in the train platform, standards for smoke removal methods (air supply or exhaust) for each fire removal area, that is, smoke removal mode, are not presented. In this study, fire analysis and evacuation analysis were performed to estimate the number of deaths and to derive F/N guidance in order to quantitatively evaluate the fire risk according to the fire station fire, and the total risk was the lowest in the case of fire area exhaust and supply to adjacent areas.

A numerical study on the performance of the smoke exhaust system according to the smoke exhaust method in emergency station for railway tunnel (철도터널 구난역의 제연방식에 따른 제연성능에 관한 수치 해석적 연구)

  • Ryu, Ji-Oh;Kim, Jin-Su;Seo, Jong-Won
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.19 no.6
    • /
    • pp.845-856
    • /
    • 2017
  • In the long railway tunnel, in order to secure safety in case of fire, it is required a emergency station. However, there is no standard or research results on smoke exhaust method and exhaust flow rate in emergency station, so it is necessary to study the smoke exhaust system for emergency station. In this study, we are created a numerical analysis model for emergency station where the evacuation cross passage connected to the service tunnel or the relative tunnel was installed at regular intervals (40 m intervals). And the fire analysis are carried out by varying the fire intensity (15, 30MW), the smoke exhaust method (only air supply, forced air supply and exhaust, forced air exhaust only), and the air flow rate (7, 14, $40m^3/s$). From the results of fire analysis, temperature and CO concentration are analyzed and ASET based on the limit temperature are compared at various condition. As a result, in the case with fire intensity of 15 MW, it is shown that a sufficiently safe evacuation environment can be ensured by applying forced air supply and exhaust method or forced air exhaust only method when the air flow rate is $7m^3/s$ above. In case of fire intensity of 30 MW, it is impossible to maintain the safety evacuation environment for more than 900 seconds when the exhaust air volume is below $14m^3/s$. And when the air flow rate is $40m^3/s$, the exhaust port is disposed at the side portion of the upper duct, which is most advantageous for securing the temperature-based safety.

Numerical Study on the Definition of the Exhaust Effectiveness of Smoke under Fire in a Large Space (대공간 화재시 배연효율 정의에 관한 수치해석적 연구)

  • Kim, Jung-Yup;Jang, Kyung Jin;Han, Hwataik
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.26 no.11
    • /
    • pp.535-540
    • /
    • 2014
  • This paper investigates the exhaust effectiveness of smoke, in the case of fire in a large atrium space. Numerical analysis was conducted to simulate transient fire growth in a test room, modeled by the Murcia atrium fire test. Various indices representing the exhaust performance of the exhaust system were obtained, such as the height of the smoke layer, and the instantaneous and accumulative capture efficiency of the smoke. The residual life time of smoke from the fire was also obtained, by injecting tracer gases at the fire location, depending on the airflow rate, and the location of the exhausts. The capture efficiency based on smoke concentration at the exhausts exhibits how much smoke can be removed by the exhaust system; whereas, the exhaust effectiveness based on residual life time indicates how rapidly the smoke can reach the exhaust locations, before being exhausted. The definitions and meanings of the indices to be used in representing the exhaust performance of a smoke exhaust system installed in a large space are discussed.