• 제목/요약/키워드: Fire Suppression Nozzle

검색결과 44건 처리시간 0.025초

객차내 환기속도가 고압 미세물분무 화재제어 시스템 성능에 미치는 영향에 대한 실험적 연구 (An Experimental Study for the Effect of Ventilation Velocity on Performance of a High Pressure Water Mist Fire Suppression System)

  • 김동운;배승용;유홍선
    • 한국안전학회지
    • /
    • 제23권4호
    • /
    • pp.1-6
    • /
    • 2008
  • This experiments are perfol1ned to investigate the effect of ventilation velocity on a high pressure water mist tire suppression in train. The experiment is conducted in half scale modeled train of a steel-welled enclosure (5.0m${\times}$2.4m${\times}$2.2m). The ventilation velocity is controlled by the ventilation duct through an inverter in the range of 0 to 3m/s. The coverage-radius and an injection angle of an high pressure water mist system are measured. The mist nozzle with 5-injection holes is operated with pressure 60bar. The heptane pool fires are used. The fire extinguishment times and the temperature are measured for the ventilation velocities. In conclusion, because the momentum of injected water mist is more dominant than that of ventilation air, the characteristics of water mist, the fire extinguishment times and the temperature are affected very little by ventilation velocity.

흡음재 두께가 소화노즐 소음도 저감에 미치는 영향 (Effect of Absorbent Thickness on the Noise Level Reduction of Fire-Extinguishing Nozzle)

  • 김학선;황인주;김윤제
    • 한국화재소방학회논문지
    • /
    • 제33권1호
    • /
    • pp.99-104
    • /
    • 2019
  • 신속한 화재 진압을 목표로 가스계 소화 시스템에서 소화약제는 일반적으로 섭씨 $21^{\circ}C$에서 약 28 MPa의 고압으로 저장되며, 방출시 감압밸브와 오리피스를 지나면서 약 8 MPa의 압력으로 방출한다. 때문에 방출시 약 140 dB 이상의 소음이 발생하게 되는데, 이로 인하여 hard disk drive (HDD)와 같은 전자 부품들이 손상되기도 한다. 따라서 소음문제는 가스계 소화 시스템에 있어서 중요한 문제점으로 대두되고 있다. 소음문제 해결방안으로는 일반적으로 흡음재를 부착하여 소음을 저감시키는 방안이 있으며, 본 연구에서는 흡음재의 두께를 설계 변수로 선정하여 유동소음을 저감하는 방안을 고찰하였다. 관측점에서의 소음도와 노즐내부 유로에 나타나는 유동특성은 상용 코드인 ANSYS CFX ver. 18.1을 이용하여 수치적으로 계산하여 분석하였다.

알칼리 금속염을 함유한 미분무수의 헵탄 Pool Fire 소화 (Extinguishment of n-heptane Pool Fire by Water Mist Containing Alkali Metal Agent)

  • 박재만;신창섭
    • 한국안전학회지
    • /
    • 제20권3호
    • /
    • pp.105-111
    • /
    • 2005
  • An experimental study is performed for extinguishing of n-heptane pool fire by water mist containing potassium acetate as a fire suppression additive. Water mist was generated by a single pressure nozzle in a small-scale chamber. The drop size distribution of water mist was measured using laser diffraction(Malvern particle sizer). The flame temperature, oxygen concentration and carbon monoxide concentration were measured. In case of using additives, the fire extinguishing time was shorter than that of pure water at a given discharge pressure and it was because the momentum of a water droplet containing additives was increased. And also dissociated metal atoms, potassium, were reacted as a scavenger of the major radical species OH, H which were generated for combustion process. Moreover, at a high pressure of 4MPa, the fire was extinguished through blowing effect as well as primary extinguishing mechanisms.

도로터널용 방수노즐 위치제어형 자동소화설비의 화재감지성능실험 (Fire Detection Performance Experiment of the Water Jet Nozzle Position Control Type Automatic Fire Extinguishing Facility for Road Tunnels)

  • 김창용;공하성
    • 한국화재소방학회논문지
    • /
    • 제33권1호
    • /
    • pp.85-91
    • /
    • 2019
  • 이 연구는 불꽃파장 감지기술과 불꽃영상 감지기술을 융합한 도로터널용 자동소화설비의 화재감지성능을 평가하기 위한 실험이다. 화재감지성능을 향상시키기 위한 이 융합기술은 화재 시 화원의 위치를 파악하고, 노즐을 화원으로 향하여 화재가 발생한 장소에만 가압수를 방사함으로서 화재진압에 따른 수손피해를 줄이는 효과를 얻을 수 있었다. 도로터널의 화재 중 불꽃 및 연기가 선행되는 상황에서 각각 15 m, 20 m, 25 m, 30 m, 35 m 거리에 $70cm{\times}70cm$의 목표물을 두었을 때 화원의 위치를 파악하는지를 실험하였다. 실험결과 농연의 간섭으로 인해 자외선 및 삼파장적외선센서의 감지능력이 감쇠되는 결과를 확인하였다. 또한 농연으로 인해 불꽃이 가려진 경우 이미지센서가 농연을 감지하여 화재신호를 발신함을 확인하였다.

지하철 객차 내 환기 속도가 고압 미세물분무 화재제어 시스템의 성능에 대한 실험평가 (An Experimental Evaluation for the Effect of Ventilation Velocity in Subway Train on Performance of a High Pressure Water Mist Fire Suppression)

  • 김동운;배승용;김동석;박원희;유홍선
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2007년도 춘계학술대회 논문집
    • /
    • pp.1307-1312
    • /
    • 2007
  • This experiments are performed to investigate the effect of ventilation velocity on a high pressure water mist fire suppression in subway train. The experiment is conducted in half scale modeled train of a steel-welled enclosure (8.0m*2.4m*2.1m). The ventilation velocity is controlled by the ventilation duct through an inverter in the range of 0 to 2 m/s. The coverage-radius and an injection angle of an high pressure water mist system are measured. The mist nozzle with 7-injection holes is operated with pressure 80 bar. The heptane pool fires are used. The fire extinguishment times and the temperatures are measured for the ventilation velocities. In conclusion, because the momentum of injected water mist is more dominant than that of ventilation air, the characteristics of water mist, the fire extinguishment times and the temperatures are affected very little by ventilation velocity.

  • PDF

ESS 화재전용 소화약제 및 소화시스템 개발에 관한 연구 (A Study on the Development of Fire Extinguishing Agent and Extinguishing System for ESS Fire)

  • 이연호;이주형;김수진;전성호;최병철;오승주;김시국
    • 한국화재소방학회논문지
    • /
    • 제34권2호
    • /
    • pp.147-155
    • /
    • 2020
  • 본 논문은 ESS 화재전용 소화약제 및 소화시스템 개발에 관한 연구이다. ESS 화재를 진압하기 위해 제작된 소화약제는 침윤제 타입으로 주된 소화효과인 냉각작용과 더불어 질식작용과 함께 표면장력 및 점도를 낮춘 침투성이 높은 소화약제로 ESS 모듈 내부의 배터리 셀까지 소화약제가 침투 가능한 특징이 있다. 소화시스템의 경우 랙 단위로 화재를 진압하는 국소방출방식으로 설계하였고, 소화효과를 극대화하기 위해 랙에 장착되는 일반형 노즐과 ESS 모듈 후면 홀에 삽입하는 360° 회전형 노즐을 제작하고, 가스방출압력에 의해 소화약제가 강하게 방사되도록 하였다. ESS 모듈 1단위 및 모듈 3단위 화재진압성능 실험결과 소화약제 방사 후 각각 8 s 및 9 s 만에 눈에 보이는 화염이 모두 소멸되었다. 또한, 소화약제 방사종료 후 600 s 동안 재발화 여부를 확인한 결과 모든 화재진압성능 실험에서 재발화가 일어나지 않고 ESS 화재가 완벽히 진압되는 것을 확인할 수 있었다.

Ro-Ro 구역용 미분무 소화설비의 개발을 위한 실험적 연구 (An experimental study on development of water mist fire-fighting systems for Ro-Ro spaces)

  • 곽지현;김영한
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제37권8호
    • /
    • pp.946-952
    • /
    • 2013
  • 선박의 Ro-Ro 구역이나 특별범주구역의 화재방호를 위해 설치하는 고정식 수계소화설비의 개발 및 실용화를 위해, 특히 방수량이 적으며 관련기준에서 요구하는 성능요건을 만족하는 미분무 노즐을 개발하고자 실물화재실험을 수행하였다. 본 설비의 화재시나리오는 크게 두 가지로 트럭화물화재와 승용차화재로 구분되며, 각각 고정 설치된 미분무 노즐과 화원과의 세 가지 위치에 대한 시나리오로 이루어져 있다. 모든 화재실험은 30분간 진행되었으며 천장부의 가스온도와 우드펠릿의 손상율, 타깃합판의 착화여부로 판단되었다. 본 논문은 두 가지 화재실험 중 조건이 더욱 까다로운 트럭화재용 미분무 노즐의 결과를 위주로 방수압력과 방수량, 미분무수의 유동특성에 따른 화재실험결과와 화재진압특성을 고찰하였으며, 수십 회의 반복실험 결과 분당 약 40 L의 유량을 가지는 저압 미분무 노즐로 Ro-Ro구역의 화재진압이 가능한 것으로 나타났다.

스프링클러 헤드의 방향성 살수 특성 비교 연구 (Directional Water Spray Characteristics of Sprinkler Heads)

  • 박용환
    • 한국화재소방학회논문지
    • /
    • 제18권4호
    • /
    • pp.35-41
    • /
    • 2004
  • 스프링클러 헤드의 살수 특성은 화재의 초기 진화 성능을 결정짓는 매우 중요한 요소이며, 이는 헤드노즐의 형상에 크게 좌우된다. 본 연구에서는 국내 시장점유율이 가장 높은 4개 제조사의 헤드 제품군에 대하여 방수계수 값과 방향성 살수 분포 특성을 규명하였다. 방수계수는 모두 기준 값을 상회하였지만, 헤드 종류별로 동일한 설계 값을 가짐에도 불구하고 큰 차이를 보이는 것으로 나타나 제품 간 품질차이가 큰 것으로 나타났다. 다만, 방수계수는 압력변화에 관계없이 비교적 일정하게 나타났다. 방향별 살수 분포 특성은 일부 헤드 샘플의 경우 매우 심각한 편향 분포를 나타냄으로써 성능개선 연구가 시급한 것으로 판단되었다

목조한옥에 대한 저압식 미분무 소화설비의 소화성능에 관한 연구 (He Study of Fire Suppression Capability of Low Pressure Water-Mist System for Wooden Cultural Properties)

  • 노삼규;김동철;함은구
    • 한국재난정보학회 논문집
    • /
    • 제8권4호
    • /
    • pp.401-410
    • /
    • 2012
  • 목조한옥은 가연성의 재질로 구성되어 있어 화재라는 측면에서 취약하며, 방화의 경우 화재의 성상 초기부터 화원의 규모가 다양하게 나타날 수 있다. 본 연구는 국내 목조문화재의 화재 소화에 적용하고 있는 저압의 미분무 소화시스템의 소화성능을 확인하기 위하여 소화실험을 수행하였다. 소화실험의 유형은 화원의 규모별 및 한옥의 규모별로 구분하였고 소화시간을 확인하여 소훼의 정도를 평가하였다. 실험결과 소화성능이 문화재 규모에서 중요한 차이는 없었으며, 화원의 규모가 0.5단위 이하의 작은 화재에 대하여 소화효과가 나타났고, 화원의 규모가 1단위 이상에서는 소화능력이 현저히 부족하였다. 실제 목조문화재의 화재 성장 환경이 소화실험 모형보다 취약하다는 측면을 고려해볼 때, 미분무 소화설비를 목조한옥에 대한 범용 자동소화설비로 적용하기 위하여 소화성능 면에서 충분한 검증이 요구된다.