• 제목/요약/키워드: Fire Detection

검색결과 645건 처리시간 0.036초

국내 원자력발전소 화재안전 대책에 관한 연구 (A Study on the Fire Safety Measures of Korean Nuclear Power Plants)

  • 김학중;손봉세;허만성
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2003년도 춘계학술논문발표회논문집
    • /
    • pp.259-264
    • /
    • 2003
  • The fire protection system of Nuclear Power Plants(NPPs) is an integrated system that is applied multi-field technology. So, it needs synthetic design and analysis, that is, the plan of fire protection, fire compartment, fire detection, fire suppression, and success of safety shut down, etc. In case of a fire in NPPs, secure the safety of reactor and minimize the radioactivity contamination. For this purpose, perform the fire risk analysis and make up the deducted problem through the improvement of design or the change of operation process.

  • PDF

장애경보 방지를 위한 연소 연기입자와 비연소 연기입자의 광 특성 분석 (Analysis of Optical Properties of Fire Smoke and Non-fire Smoke for Reduction of Nuisance Alarm)

  • 지승욱
    • 조명전기설비학회논문지
    • /
    • 제28권10호
    • /
    • pp.49-55
    • /
    • 2014
  • This paper is basic study for development of an advanced photoelectric type smoke detector that has high reliability by reducing the occurrence of nuisance alarms. This paper was attempted to distinguish optical characteristics of the typical fire smoke particle and non-fire smoke particle. According to UL 268 standards, three types of test fires (the paper, the wood and the flammable liquid) were used in this paper for measurement of the fire smoke particles, and the water vapor and the cigarette smoke that were known as the main cause of the nuisance alarms were also used for the non-fire smoke particles. A smoke detection chamber was created, which was equipped with one light source and several light sensors for enabling simultaneous detection of light extinction and scattering, respectively. This paper analyzes the optical characteristics of each smoke particle using this chamber.

Application Studies for Active Fire Monitoring over Korea Using MODIS Direct Broadcast Data

  • Song J.H.;Kim Y.S.
    • 대한원격탐사학회:학술대회논문집
    • /
    • 대한원격탐사학회 2004년도 Proceedings of ISRS 2004
    • /
    • pp.410-414
    • /
    • 2004
  • The MODIS Land Rapid Response System (RRS) has been developed to provide rapid access to MODIS data globally, with initial emphasis on 250 m color composite imagery and active fire data. Fire detection is based on a contextual algorithm that exploits the strong emission of mid-infrared radiation from fires. This algorithm examines each pixel of the MODIS swath, and ultimately assigns to each one of the following classes: missing data, cloud, water, non-fire, fire, or unknown. In this paper, we introduce the MODIS Rapid Response System established at the Korea Aerospace Research Institute (KARI) and present some application results for Korea using the direct broadcast data acquired at KARI ground station.

  • PDF

Forest fire experiment toward the detection of forest fires using RS - Thermal and reflectance environment change observation at ground level -

  • Tanpipat, Veerachai;Honda, Kiyoshi
    • 대한원격탐사학회:학술대회논문집
    • /
    • 대한원격탐사학회 2002년도 Proceedings of International Symposium on Remote Sensing
    • /
    • pp.690-695
    • /
    • 2002
  • In this forest fire experiment the ThermoViewer was set up on the platform built on a tree and observed the temperature change, before, during and after the fire. The fire experiment had been carried out not only the day of the forest fire experiment but also continued for four months after the forest fire had been gone. The results from the experiment showed that the temperature difference is significant in the afternoon; therefore, afternoon satellite passing is better and suitable time for active forest fires and burnt scars detection; moreover, after 83 days, the burnt and un-burnt vegetation become almost the same condition, fully regenerated and the temperature difference become nearly 0$^{\circ}$ Celsius, so there is not enough temperature different between burnt and un-burnt vegetation for current sensors to distinguish the difference anymore.

  • PDF

Algorithm for Detection of Fire Smoke in a Video Based on Wavelet Energy Slope Fitting

  • Zhang, Yi;Wang, Haifeng;Fan, Xin
    • Journal of Information Processing Systems
    • /
    • 제16권3호
    • /
    • pp.557-571
    • /
    • 2020
  • The existing methods for detection of fire smoke in a video easily lead to misjudgment of cloud, fog and moving distractors, such as a moving person, a moving vehicle and other non-smoke moving objects. Therefore, an algorithm for detection of fire smoke in a video based on wavelet energy slope fitting is proposed in this paper. The change in wavelet energy of the moving target foreground is used as the basis, and a time window of 40 continuous frames is set to fit the wavelet energy slope of the suspected area in every 20 frames, thus establishing a wavelet-energy-based smoke judgment criterion. The experimental data show that the algorithm described in this paper not only can detect smoke more quickly and more accurately, but also can effectively avoid the distraction of cloud, fog and moving object and prevent false alarm.

전기화재 분야에서 다목적으로 시험장치의 활용범위를 증가시키기 위한 시험장치의 설계 및 구현 (Design and Implementation of a Multi-purpose Test Equipment with a Large Utilization Range for use in Electric Fire)

  • 신동철;고형호
    • 센서학회지
    • /
    • 제32권3호
    • /
    • pp.180-186
    • /
    • 2023
  • Test devices can perform various functions, such as research on detection targets, sensors that detect detection targets, combined products containing sensors, and certification for the launch of combined products. However, the scope of use of test devices is limited because they perform only a single role or could only serve a particular purpose in the past. Therefore, studies on test devices that can perform various functions, such as research on detection targets, sensors that detect detection targets, combined products containing sensors, and certification for the release of combined products are necessary. Accordingly, this study proposes a test device that can increase the scope of use in the technical field of electric fires. In addition, we examine various outcomes of the proposed test device.

영상감시시스템에서 은닉마코프모델을 이용한 불검출 방법 (Fire detection in video surveillance and monitoring system using Hidden Markov Models)

  • ;김정현;강동중;김민성;이주섭
    • 한국정보처리학회:학술대회논문집
    • /
    • 한국정보처리학회 2009년도 춘계학술발표대회
    • /
    • pp.35-38
    • /
    • 2009
  • The paper presents an effective method to detect fire in video surveillance and monitoring system. The main contribution of this work is that we successfully use the Hidden Markov Models in the process of detecting the fire with a few preprocessing steps. First, the moving pixels detected from image difference, the color values obtained from the fire flames, and their pixels clustering are applied to obtain the image regions labeled as fire candidates; secondly, utilizing massive training data, including fire videos and non-fire videos, creates the Hidden Markov Models of fire and non-fire, which are used to make the final decision that whether the frame of the real-time video has fire or not in both temporal and spatial analysis. Experimental results demonstrate that it is not only robust but also has a very low false alarm rate, furthermore, on the ground that the HMM training which takes up the most time of our whole procedure is off-line calculated, the real-time detection and alarm can be well implemented when compared with the other existing methods.

전기화재 예지원리 및 징후검출 시스템 구조 (Prediction Principle and System Structure for the Detection of Incipient Electrical Fire)

  • 김창종
    • 한국조명전기설비학회지:조명전기설비
    • /
    • 제9권4호
    • /
    • pp.71-77
    • /
    • 1995
  • Electrical fire in residential, commercial, and industrial areas occupies 40 percent of overall fire accidents as of the year of 1994. The causes of most electrical fires were studied and, based on this investigation, the principle of the early detection or prediction of the electrical fires is developed. The basic principle is to early detect electrical arcs or sparks caused by faulty connections and insulation failures. the structure of the prediction system based on microcontroller technique is presented.

  • PDF

라만산란을 이용한 광센서 선형 화재감지시스템 개발에 관한 연구 (Study on the Development of Optical Sensor Linear Fire Detection System Using Raman Scattering)

  • 이건호;임우섭;김시국
    • 한국화재소방학회논문지
    • /
    • 제30권4호
    • /
    • pp.27-38
    • /
    • 2016
  • 본 논문은 현재 국외기술에 의존하고 있는 광센서 선형감지기를 이용한 화재감지시스템인 분산온도감지(DTS) 시스템을 국산화 기술로 개발하기 위한 연구이다. 이에 본 연구에서는 광섬유 내에서 발생되는 빛의 역산란광 중 온도감지에 주로 사용되는 라만산란광의 전기적 신호파형을 오실로스코프를 이용하여 분석하였다. 측정결과 Stokes 신호파형은 온도가 상승해도 변화량이 거의 없었으나, 온도에 민감한 anti-Stokes 신호파형은 상대적으로 그 값이 증가하는 것을 확인할 수 있었다. 그리고 라만산란광을 이용하여 화재를 감지할 수 있는 광중계기 및 광수신기로 구성된 광센서 선형 화재감지시스템인 K-DTS 시스템을 개발하였다. 개발된 K-DTS 시스템에 대하여 차동식 및 정온식 감도시험기를 이용하여 차동식 및 정온식 감지기로서의 감도시험을 진행해 본 결과 형식승인 기준을 만족하고 있는 것을 확인할 수 있었다. 또한, 개발된 K-DTS 시스템의 성능평가를 위해 국외에서 수입되어 가장 많이 사용되고 있는 S-DTS 시스템과 성능비교실험을 진행하였다. 모형터널을 이용한 성능실험결과 화재감지위치 및 화재온도 측정에서 유사한 성능을 나타내는 것을 확인할 수 있었다.

자동소화설비에 대한 연구 (A Study on Automatic Sprinkler System)

  • 권오승
    • 한국화재소방학회논문지
    • /
    • 제2권3호
    • /
    • pp.11-15
    • /
    • 1988
  • This study is explained about operation function and maintenance of components for automatic fire extinguishing systems. Which is included the wetting agent, detection devices and automatic values for pre-engineered type extinguishing systems.

  • PDF