• Title/Summary/Keyword: Faulty Insulator

Search Result 14, Processing Time 0.036 seconds

Correlation Propagation Neural Networks for Safe sensing of Faulty Insulator in Power Transmission Line (송전선로 노화애자의 안전 감지를 위한 상관전파신경망)

  • Kim, Jong-Man
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.58 no.4
    • /
    • pp.511-515
    • /
    • 2009
  • For detecting of the faulty insulator, Correlation Propagation Neural Networks(CPNN) has been proposed. Faulty insulator is reduced the rate of insulation extremely, and taken the results dirty and injured. It is necessary to detect the faulty insulator and exchange the new one. And thus, we have designed the CPNN to be detected that insulators by the real time computation method through the inter-node diffusion. In the network, a node corresponds to a state in the quantized input space. Each node is composed of a processing unit and fixed weights from its neighbor nodes as well as its input terminal. Information propagates among neighbor nodes laterally and inter-node interpolation is achieved. 1-D CPNN hardware has been implemented with general purpose. Experiments with static and dynamic signals have been done upon the CPNN hardware. Through the results of simulation experiments, we define the ability of real-time detecting the faulty insulators.

Development of the equipment for detecting the poor power facilities by receiving electric noises (전자파 잡음을 이용한 전기설비 불량 검출장치 개발)

  • 이복규;강성철
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 1997.10a
    • /
    • pp.1356-1359
    • /
    • 1997
  • There are various methods to detect the faulty electric facilities(esp, insulator) indirectly on power distribution lines at a certain distance apart. This paper describes the proto type equipment to detect a faulty insulator by receiving a electric discharge noises, which are generated with a periodicity of 120Hz.

  • PDF

Propagation Neural Networks based on vision techniques for detecting of Faulty Insulator (불량애자 검출을 위한 비젼 기반 전파 신경망)

  • Kim, Jong-Man;Kim, Young-Min;Hwang, Jong-Sun;Park, Hyun-Chul;Lim, Sung-Ho;Kim, Hyun-Chul
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.07b
    • /
    • pp.1097-1102
    • /
    • 2002
  • For detecting of Faulty Insulator, a new Lateral Information Propagation Networks (LIPN) has been proposed. Energized insulator is reduced the rate of insulation extremely, and taken the results dirty and injured. It is necessary to be actions that detect the faulty insulator and exchange the new one. And thus, we have designed the LIPN to be detected that insulators by the real time computation method through the inter-node diffusion. In the network, a node corresponds to a state in the quantized input space. Each node is composed of a processing unit and fixed weights from its neighbor nodes as well as its input terminal. Information propagates among neighbor nodes laterally and inter-node interpolation is achieved. Through several simulation experiments,real time reconstruction of the nonlinear image information is processed.

  • PDF

Neural Networks for Real-time detecting of Energized Insulator (절연노화 애자의 실시간 감지를 위한 신경회로망의 개발)

  • Kim, Jong-Man;Kim, Won-Sup;Kim, Hyung-Suk;Sin, Dong-Yong
    • Proceedings of the KIEE Conference
    • /
    • 2002.07d
    • /
    • pp.2276-2279
    • /
    • 2002
  • For detecting of Energized Insulator, a new Lateral Information Propagation Networks(LIPN) has been proposed. Faulty insulator is reduced the rate of insolation extremely, and taken the results dirty and injured. It is necessary to be actions that detect the faulty insulator and exchange the new one. And thus, we have designed the LIPN to be detected that insulators by the real time computation method through the inter-node diffusion. In the network, a node corresponds to a state in the quantized input space. Each node is composed of a processing unit and fixed weights from its neighbor nodes as well as its input terminal. Information propagates among neighbor nodes laterally and inter-node interpolation is achieved. Through the results of simulation experiments, we define the ability of real-time detecting the faulty insulators.

  • PDF

Instrumentation based Neural Networks for Real-time detecting of Energized Insulator (오손 애자자의 실시간 검출을 위한 계측기반 신경망)

  • Kim, Jong-Man;Kim, Young-Min
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.05c
    • /
    • pp.25-29
    • /
    • 2004
  • For detecting of Energized Insulator, a new Lateral Information Propagation Networks(LIPN) has been proposed. Faulty insulator is reduced the rate of insulation extremely, and taken the results dirty and injured. It is necessary to be actions that detect the faulty insulator and exchange the new one. And thus, we have designed the LIPN to be detected that insulators by the real time computation method through the inter-node diffusion. 1n the network, a node corresponds to a state in the quantized input space. Each node is composed of a processing unit and fixed weights from its neighbor nodes as well as its input terminal. Information propagates among neighbor nodes laterally and inter-node interpolation is achieved. Through the results of simulation experiments, we difine the ability of real-time detecting the faulty insulators.

  • PDF

Development of Live-line Insulator Tester and Its Application to 154kV Power Lines - Part 2 : Inspection Algorithm Development (활선애자점검기의 개발 및 154kV 선로에의 적용 - 제2부 : 진단 알고리즘 개발)

  • Park, Joon-Young;Lee, Jae-Kyung;Cho, Byung-Hak;Oh, Ki-Yong
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.59 no.1
    • /
    • pp.89-95
    • /
    • 2010
  • A new live-line insulator tester was developed to detect faulty insulators in 154kV power transmission lines. This paper is the second part of the two-part paper and deals with its inspection algorithm development. Unlike normal condition with low pollution and low humidity, the inspection data measured in the field under high pollution or high humidity showed that the voltage distribution of an insulator string has offsets in comparison with those of others and its insulation resistances are greatly decreased, which leads to wrong results of the existing inspection algorithms under such conditions. To solve this problem, we propose new diagnosis algorithms that can exactly detect faulty insulators from measured data regardless of environmental conditions. Its effectiveness was validated by live-line field tests in actual power lines.

Malfunction Detection of High Voltage Equipment Using Microphone Array and Infrared Thermal Imaging Camera (Microphone Array와 열화상 카메라를 이용한 고압설비 고장검출)

  • Han, Sun-Sin;Choi, Jae-Young;Lee, Jang-Myung
    • Journal of Institute of Control, Robotics and Systems
    • /
    • v.16 no.1
    • /
    • pp.25-32
    • /
    • 2010
  • The paper proposes a hierarchical fault detection method for the high voltage equipment using a microphone array which detects the location of fault and the thermal imaging and CCD cameras which verifies the fault and stores the image, respectively. There are partial arc discharges on the faulty insulators, which generates a specific pattern of sound. Detecting the signal using the microphone array, the location of the faulty insulator can be estimated. The 6th band-pass filter was applied to remove noise signal from wind or external influence. When the mobile robot carries the thermal and CCD cameras to the possible place of the fault insulator, the fault insulators or power transmission wires can be detected by the thermal images, which are caused by the aging or natural erosion. Finally, the CCD camera captures the image of the fault insulator for the record. The detection scheme of fault location using the microphone array and the thermal images have been proved to be effective through the real experiments. As a result of this research, it becomes possible to use a mobile robot with the integrated sensors to detect the fault insulators instead of a human being.

A Neural Network Modulars for Real-time Detection of Bad Materials (불량소자의 검지를 위한 실시간 전송 뉴로 모률라)

  • Kim, Jong-Man;Kim, Won-Sop
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2008.04c
    • /
    • pp.54-57
    • /
    • 2008
  • A new modular Lateral Information Propagation Networks can be implemented in a IC chip with the circuit VLSI technology for detection of bad materials. The proposed modular architecture is propagated the neural network through inter module connections. For such inter module connections, the host(computer or logic) mediates the exchange of information among modules. Also border nodes in each module have capacitors for temporarily retaining the information from outer modules. For detecting of Faulty Insulator, $4\;{\times}\;4$ neural network modules has been designed and simulation of interpolation with the designed networks has been done.

  • PDF

Development of Live-line Insulator Tester and Its Application to 154kV Power Lines - Part 1 : Tester Development (활선애자점검기의 개발 및 154kV 선로에의 적용 - 제1부 : 점검기 개발)

  • Lee, Jae-Kyung;Park, Joon-Young;Cho, Byung-Hak;Oh, Ki-Yong
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.59 no.1
    • /
    • pp.83-88
    • /
    • 2010
  • A new live-line insulator tester was developed to detect faulty insulators in 154kV power transmission lines. This paper is the first part of the two-part paper and deals with its tester development. The developed tester has the following characteristics. First, it automates parts of the insulator inspection process by using a sensor and an actuator, and secondly, it sustains its weight by itself, not by a lineman. Finally, it measures the insulation resistance of an insulator together with its distribution voltage to provide more information for its analysis and diagnosis. These leads to the improvement of its operation efficiency, measurement reliability and usability. Its effectiveness was validated by live-line field tests in actual power lines.

Insulator application and prospect (가공송전선로 애자 적용실태와 향후 전망)

  • Kim, Woo-Kyum;Min, Byeong-Wook;Kim, Tai-Young;Wi, Hwa-Bog;Choi, Jin-Sung;Lee, Buk-Chang
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.327_328
    • /
    • 2009
  • The insulator being used for transmission line is to mount the charged conductor on the tower or other supports. The insulators are classified according to its material: porcelain, glass and polymer. Polymer insulators are also called as composite insulator or non ceramic insulator (NCI). Insulators are a major element of a power transmission system. Since a faulty insulator can lead to a wide spreading blackout, it must have sufficient mechanical and electrical strength. It must be durable, have high electrical insulation and be able to withstand a leakage current. It must also be able to withstand the toughest weather conditions. In Korea, porcelain insulators have been used widely. However, to make compact equipment and keep up with global trends, we have enhanced domestic production of polymer insulator and are encouraging its applications. Accordingly, this thesis will look at types of insulators, use and trends, and prospects of insulators application in the field.