A Study on the Minimum Ignition Limit Voltages for LPG-Air Mixtures by Discharge Sparks in Radio-frequency Circuits (고주파 전기회로의 개폐불꽃에 의한 LPG-공기 혼합가스의 최소점화한계전압에 관한 연구)

  • Lee Chun-ha;Kim Jae-ouk;Jee Sung-ouk;Song Hun-jik;Lee Gang-sik;Lee Dong-in
    • Journal of the Korean Institute of Gas
    • /
    • v.2 no.4
    • /
    • pp.79-84
    • /
    • 1998
  • This paper describes the minimum ignition limit voltages for LPG-Air 5.25[Vol$\%$] mixture gas by discharge sparks in radio-frequency limits using RF power supply and IEC type ignition spark apparatus. As a result, the minimum ignition limit voltages is increased in proportional to the rate of increasing of frequency in LPG-Air mixture gas. Especially, the minimum ignition limit voltages increase remarkably between 3[KHz] and 10[KHz]. It is considered that ignition is caused by one discharge until 3[KHz] and, beyond 3[KHz] ignitiof is caused by more than two discharges. The reason is analyzed that energy loss is caused by existing pause interval between discharges. It is considered that the result can be used for not only data for researches and development of intrinsically safe explosion-proof RF machines which are applied tole-equipments and detectors used in dangerous areas but also for datum for its equipment tests.